13
4. ENCLOSURE
CONTROLS
5. MANUAL
CYCLE
5.1 WHEN
5.1.1
A manual clean cycle is typically initiated when the unit is in the
MANUAL mode. A manual clean cycle is typically initiated when
personnel wish to clean the GRD regardless of grease level or
when supervision is required.
5.2 HOW
5.2.1
To begin a manual clean cycle rotate the Auto/Manual mode switch
to the MANUAL position. The following messages will be displayed
at this point.
MANUAL OPERATING MODE
DyCyc:XX WkCyc:XX MoCyc:XX YrCyc:XXX
MANUAL OPERATING MODE
PRESS “START” TO BEGIN CLEAN CYCLE
5.2.2
To initiate the manual clean cycle press the START button.
5.3 PROCESS
5.3.1
Once the START button is pressed, the clean cycle will begin, the
controller will beep and the following message will be displayed:
MANUAL CLEAN CYCLE INITIATED
X.XX MINUTES BEFORE CLEAN CYCLE STARTS
HTR
ON
TEMP
SW
ON
GREASE
LEVEL
HI
ACTIVITY
1
ACTIVITY
2
PUMP
CAL
MODE
/UP
CC
RATE
/DN
TEST
/CANCEL
ENTER
RESET
CONTROLLER LCD DISPLAY
Cal Mode/Up
Initiates the water level sensor calibration
mode and adjusts time and date values
in the time and date entry mode.
CC Rate
Initiates the clean cycle rate adjustment
mode.
Test Mode /Cancel
Initiates the test mode operation.
Enter
Mode selection and data entry switch.
Reset
Soft Reset