8
6. TESTING
6.1 G.R.D.
TEST
6.1.1
Confirm that the unit is level and unlatch and lift off the large cover
on the GI-2000 tank.
6.1.2
Run water through the drain installation until the unit is full. The unit
is full when water runs out of the outlet of the GI-2000.
6.1.3
Check the system installation for leaks.
6.1.4
Turn the Auto/Manual mode switch located on the front of the
controller to the MANUAL position.
6.1.5
Apply power to the GI-2000. The controller will beep and start the
initialization procedures. Wait until the display indicates the unit is
in MANUAL mode. This will take approximately 15 seconds. Should
any part of the diagnostics fail, the unit will beep every 5 seconds
and display a message about the failure. (See Controller Operating
Section and Troubleshooting Guide for details on addressing
possible problems with the GI-2000)
6.2 HEATER TEST
6.2.1
Open the controller door by loosening the front panel screws on the
controller door.
6.2.2
Press the TEST button once and the following message will be
displayed:
PRESS UP OR DOWN KEYS UNTIL
DESIRED TEST APPEARS
6.2.3
Press UP or DOWN until the following message is displayed:
HEATER TEST (DO NOT RUN DRY): HEATER:OFF
PRESS ENTER TO CYCLE HEATER STATUS
6.2.4
Press ENTER to turn the heaters on and ensure that they are
operating. Evidence that they are operating can be detected by
heat waves and bubbles forming around the heater elements.
Pressing ENTER again will turn the heater off. Check the display
and green LED indicator to ensure proper operation. The heaters
will also automatically shut off after three minutes.
WARNING!
Do not run the heater dry! Running the heater dry may
cause damage to the heaters and the unit.
6.3 PUMP TEST
6.3.1
Open the controller door by loosening the front panel screws on the
controller door.