background image

9

ENGLISH

•  The appliance must always be started up with the firebox empty, without pellets and without unburned fuel from previous 

use.

•  Do not attempt to ignite the fuel with inflammable liquids or solids; the stove must ignite automatically via the electrical 

components installed onboard.

•  Do not load pellets manually into the firebox before or whilst the appliance is running.
•  Keep the ventilation grids in the area the appliance is installed in clean conditions.
•  Never load any fuel other than pellets into the stove storage hopper. Corn, nuts or other combustible materials must not be 

used as fuel for the appliance.

•  Check and periodically clean the fume exhaust pipe, from the appliance to the flue (Union).
•  It is strictly prohibited to start up the product with the combustion chamber door open or allow it to run with the glass broken.
•  The user should contact an authorised JOLLY-MEC Technical Assistance Centre if any operating problems persist.

•  Never try to start the device using ethyl alcohol or other flammable liquids.

 

02.3  

SAFETY REGULATIONS FOR EXTRAORDINARY MAINTENANCE AND INSTALLATION

•  The user and/or owner of the product is required, in accordance with the laws in force, to assign the installation and 

maintenance to qualified and specialised operators, and acknowledge the risks and hazards should they fail to observe 

this requirement.

•  The installation of the heat generator and the relative combustion product exhaustion system, the electrical connections, 

the commissioning and extraordinary maintenance MUST always be performed by Qualified and/or Licensed Professional 

Technicians or those Authorised by the Manufacturer.

•  The product must be installed in accordance with the laws and standards in force in the State, Region or Area in which 

the machine is installed.

•  Installation in bedrooms, rooms with a volume below 15 m

3

 or with explosive atmospheres is strictly prohibited.

•  The system installer MUST issue a Declaration of compliance for the work performed after commissioning the system, 

in accordance with the laws in force related to system safety standards.

•  The installation technician must inform the user on safe equipment use.
•  The installation operator is responsible for the installation and is therefore required to perform the work to top workmanship 

standards.

•  The appliance must be connected to a combustion product exhaustion flue built in accordance with applicable 

standards and certified with a declaration of compliance.

•  The installation technician is in charge of installation and must check emissions following first installation.
•  Should any installation defects arise during commissioning, the Authorised Jolly-Mec Technician can refuse to endorse 

use of the product for safety reasons and submit a written Servicing Report to the User informing him that he and the 

Installation operator shall be jointly liable for any damage to persons, animals or things if used.

•  Before installing the machine, the customer and installation operator must ensure that the flooring on which it will be 

positioned is suitably levelled and can support the weight (see 

CHAP.06 - TECHNICAL DATA

). IIf there is any doubt 

on the solidity of the flooring, it is essential to have a Structural Engineer verify relative installation feasibility.

•  Only specialised and qualified personnel may work or carry out checks inside the machine, complying with safety 

regulations.

•  Prior to installation, the user and installer are obliged to check that the mains electrical supply to which the machine will be 

connected, corresponds to the voltage on the identification plate (see 

CHAP.05.2 - PRODUCT IDENTIFICATION

), 

check that the system is sized so as to bear the maximum load required of the product, and also that it is equipped with 

Summary of Contents for I-DEA IDRO

Page 1: ...SM094 EN REV05 2016_03 I DEA IDRO INSTALLATION USE AND MAINTENANCE MANUAL To be kept by the purchaser Pellet fired stove with boiler QUADRA FRONTALE ANGOLO...

Page 2: ...y read and keep this sheet before using the equipment This sheet provides necessary information and suggestions on how to correctly install use clean and maintain the product Knowing and observing the...

Page 3: ...HAP 05 DESCRIPTION 12 05 1 PRODUCT PRESENTATION 12 05 2 PRODUCT IDENTIFICATION 14 CHAP 06 TECHNICAL DATA 15 06 1 HOMOLOGATION 15 06 2 RECOMMENDED FUELS 16 06 3 COMPONENTS 17 06 4 OPTIONALS 18 06 5 DIM...

Page 4: ...appropriate This manual cannot be given to third parties for perusal without the written permission of Jolly Mec Caminetti S p A The technical directions for installation contained in this manual sho...

Page 5: ...61000 3 3 Electromagnetic compatibility EMC Limits Limitation of voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 16 A per phase a...

Page 6: ...g and maintenance of services supplying water for domestic use within buildings and their curtilages Complimentary guidance to BS EN 806 BS EN 14961 Solid biofuels Fuel specifications and classes Part...

Page 7: ...product was marketed The manufacturer reserves the right to make modifications to the product and consequently the relative manual without any obligation to update previous editions 01 5 MANUFACTURER...

Page 8: ...for children persons with acknowledged reduced psycho physical and sensory abilities and persons who lack experience in using such machines unless they are supervised by designated persons responsibl...

Page 9: ...hine is installed Installation in bedrooms rooms with a volume below 15 m3 or with explosive atmospheres is strictly prohibited The system installer MUST issue a Declaration of compliance for the work...

Page 10: ...IPMENT FOR OPERATORS AND MAINTENANCE PERSONNEL Every operator performing maintenance on the machine must wear safety garments and personal protective equipment 1 Protection headphones 2 Gloves hand pr...

Page 11: ...D TRANSPORT Personnel in charge of handling the product must have read and thoroughly understood the safety prescriptions in CHAP 02 ACCIDENT PREVENTION SAFETY REGULATIONS of this manual and must wear...

Page 12: ...nd DO NOT disperse the packaging into the environment but take it to waste disposal centres for recycling All packaging can be recycled as it consists of wood polyethylene film polystyrene and cardboa...

Page 13: ...cated on the rear of the stove The pellets are fed by an auger driven by a gear motor that picks the pellets from the hopper and channels them to the firebox via a chute The I DEA IDRO heating stove c...

Page 14: ...hermostats pellet hopper safety and water safety Painted steel pellet container cover Vertical exhaustion of fumes by removing the screw cap to make room for the fumes tube Combustion chamber door wit...

Page 15: ...d Nominal Reduced Ignition Working 110W Dust 13 O 11 0mg m Nominal S 400 mm n DOP JM 00054 the dop was drafted on the basis to the test report of accredited laboratory the accreditation number of the...

Page 16: ...ir distance from inflammable side wall 400 400 mm Minimum air distance from inflammable rear wall 200 200 mm Frontal air distance from inflammable material 150 150 cm Testing pressure 6 6 bar Maximum...

Page 17: ...ts that are very hard and with different dimensions the mechanical parts are sized and tested for use with pellets with the above mentioned characteristics No breakdown or malfunction depending on the...

Page 18: ...h pan 6 Combustion chamber door safety microswitch 7 Fume inspection flap 8 Pellet hopper 9 Heat circulation pump 10 Pellet loading auger gear motor 11 Pellet loading auger 12 Electronic control unit...

Page 19: ...alled in the home it is used to easily control stove operations and adjust necessary temperatures from within the home Temperature time settings or personalised heating profiles can be set Zone module...

Page 20: ...connect the generator to the flue T union for fume exhaust with condensate drain cap To be installed at generator output 80mm for union connection and 100mm for flue connection Fume exhaust pipe 80mm...

Page 21: ...21 ENGLISH 06 5 DIMENSIONS All measurements are in mm Frontale Quadra Angolo A 1134 1134 1134 B 346 346 346 C 852 852 862 Frontale Quadra Angolo A B C A B C A B C...

Page 22: ...CHAP 07 6 HYDRAULIC KIT FOR THE SYSTEM FEED THE COLD WATER MUST BE CONNECTED TO THE APPLIANCE NOTE At the end of installation accurately clean the heating system to eliminate all work residue Dirt dep...

Page 23: ...ainless steel pipes The use of pipes in fibre cement for connecting the equipment to the flue is forbidden Exhaust pipes must not run through rooms where the installation of combustion equipment is fo...

Page 24: ...s the point of discharge of the flue or 150 mm above the insulation whichever is the lower Point Where flue passes through weather surface Notes 1 2 Clearances to flue outlet A At or within 600 mm of...

Page 25: ...installation work issue a declaration of conformity as per Ministerial Decree 37 08 On the other hand the purchaser MUST assign all work to a qualified professional technician The device must be insta...

Page 26: ...se a spare fuse in the pan and a bipolar switch In the event that the control unit does not switch on even after turning the switch to I ONE check that the fuse has not blown 1 Control unit manual 2 E...

Page 27: ...mostat with manual reset terminal AC3 18 PRESSOSTATO 2 Fume exhaust fan safety depressimeter terminal AC5 19 MICRO 1 Door contact safety microswitch terminal IN9 23 SONDA 3 Stove water temperature pro...

Page 28: ...ow Green Black Blue Brown Green Violet Yellow Black Red Black Red Violet Red Orange White Black Red Blue Black Grey Black Red Blue Pressure Safety H2O Safety Ther Safety Therm BLACK BLUE YELLOW Yellow...

Page 29: ...NC CN1 NO CN2 N CN3 F CN2 O2 CN2 N CN12 CN12 CN2 O7 reen TERMINAL B Aux Buffer Pump Terminal B Terminal B Terminal B TERMINAL A CN9 IN10 CN9 IN10 CN10 IN3 CN10 IN3 CN10 IN1 CN10 IN1 CN9 IN11 CN9 IN11...

Page 30: ...with a standard pre installed hydraulic kit without domestic hot water production DHW In Fig 1 e 3 illustrate hydraulic kit component Following is an itemised list of these components 1 3 litre expans...

Page 31: ...adjust the position of Variable p Venting cycle and the Constant p Pump led colour key LED DESCRIPTION OF FUNCTIONS Off Circulator not connected to the mains Flashing green With the vertical knob in a...

Page 32: ...e room probe connection In this case the internal probe must be disconnected or the probe on board the device can remain connected if a room thermostat is connected H Terminal for gas stove connection...

Page 33: ...rceptions between the device and system that could slow water flow and thus cause stove water overtemperature alarms Alarm AL19 THERMIC WATER For the room probe type a thermostat or chronothermostat c...

Page 34: ...l meets set temperature settings When the puffer temperature is met the appliance switches to ECONOMY mode turning off the pump When puffer temperature drops 5 C default value that can be adjusted in...

Page 35: ...he functions described in CONFIGURATION 1 while the boiler takes precedence over the heating system request The boiler probe connected to the boiler back terminal board works with a 5 C temperature di...

Page 36: ...ce see manual SM096 EN attached 08 2 CONTROL UNIT The electronic control unit controls all appliance functions and is controlled via a control display The electronic control unit features a timer func...

Page 37: ...red temperature level for each time band The message ORDINARY SERVICE is periodically displayed every 100 hours of operation to remind the user to clean the stove thoroughly CHAP 08 6 ROUTINE MAINTENA...

Page 38: ...side of the device below the side panel see Fig 1 positions A or B 3 Press the button A or B until you hear a CLICK 4 Refit the hood 5 Reset the alarm from the device on board display by pressing But...

Page 39: ...esidual pellets from clogging and subsequently damaging the components Every 300 kg of pellets loaded into the container check that there are no deposits of sawdust on the bottom and remove any sawdus...

Page 40: ...ost suitable cleaning frequency can also be established a few days after use according to the actual amount of deposited residue and may vary from recommended Jolly Mec intervals NOTE ORDINARY CLEANIN...

Page 41: ...ition resistance has to be properly centred in the burning pot casing and the support seat must be standing level with the casing compartment Fig 8 Check that the gasket located under the burning pot...

Page 42: ...n the fume inspection flap Fig 21 e 22 Loosen the locking knobs Fig 23 of the fume inspection door and remove the cap Fig 24 Use the brush supplied to clean the ash pan Fig 25 26 and use the ash vacuu...

Page 43: ...ush inward to unhook it from the front supports Fig 33 Lower the deflector vertically and slightly rotate it to remove Fig 34 35 Use the brush supplied to remove any ash content from the fume deflecto...

Page 44: ...or invalidation of the warranty on these parts No claims can arise concerning the colour variations of the painted surfaces especially if the different materials and finishes are subject to different...

Page 45: ...c electrical system plug it into the socket fitted on the back of the right side panel Fig 49 50 threading it through the groove on the back of the stove making sure the switch is in the O position Af...

Page 46: ...l focus on horizontal segments and the chimney pot Stove fume pass cleaning Cleaning of any deposits in the stove Cleaning of fans Check safety valves Checking good water circulator operations Check a...

Page 47: ...sits in the stove T Cleaning of fans T Check air breather valves T Checking good water circulator operations T Check air breather valves T Check expansion tank pressure T Check good ignition resistanc...

Page 48: ...settings change the comburent air flow value Check air inlet in the burner The appliance switches off when running at minimum power The combustion fan speed is very high and the pellets are burning t...

Page 49: ...t content in the tank Make sure the pellet load auger works correct start the component from menu PELLET LOAD MENU 7 After completing the Load Pellet sequence in Menu 7 the brazier must be emptied i e...

Page 50: ...he firebox air flow holes are perfectly clean Check that the fume inspection cap is firmly closed Make sure the door is closed AL13 NON STOP PEL LOAD Pellet load is continuous and thus incorrect Make...

Page 51: ...ust only be used with the combustion chamber door closed AL27 DHW LO FAILURE The boiler Lo probe is disconnected or broken Check probe wiring If correct replace the probe AL28 SERVICE 24H The device c...

Page 52: ...SM094 EN REV05 2016_03 Via S Giuseppe 2 24060 Telgate Bg Italy Tel 39 035 83 59 211 Fax 39 035 83 59 203 www jolly mec it info jolly mec it...