TABLE 8:
Inverter Drive Fault/Status Code Display
Inverter Drive
Description
LED
1
Blink
Codes
OD Display Text
Possible
Causes
Solution
Inverter - Faults
C+B6:H16
Compressor
Phase Over Current
LED604 / LED2 1 or 3
COMPRESSOR
PHASE OVER CURRENT –
INVERTER DRIVE
Loose or incorrect
wire connections
Check lead to the compressor
plug and at inverter drive.
W: Black Wire (BLK).
V: Red Wire (RED).
U: Brown Wire (BRN).
Phase imbalance or
shorted compressor
windings.
Check compressor winding resistance
at the compressor terminals.
2 Ton - 0.681
3 Ton - 0.203
4 Ton - 0.203
5 Ton - 0.203
High compressor load.
Verify system is within operating
conditions as outlined in IOM.
High compressor load
caused by
internal damage.
Check compressor and if all looks normal and
problems still persist when all other solutions
have been vetted, replace compressor.
LED 603 / LED3
4
Sensor on drive not
reading properly
Replace drive.
Compressor Phase
Current Foldback
Timeout
LED604 / LED2
16
COMPRESSOR PHASE
CURRENT FOLDBACK –
INVERTER DRIVE
See Compressor
Phase Over Current.
See Compressor Phase Over Current.
AC Input
Over Current
LED604 / LED2
11
AC INPUT OVER
CURRENT –
INVERTER DRIVE
Reduced input voltage
Check the line voltage if it is < 187VAC.
14
Distorted input voltage
Check the line voltage for noise.
Call an electrician or the power
company if noise is found.
15
High compressor load.
Check the compressor is operating
with in specified limits.
Drive component issue.
Replace drive.
AC Input Current
Sampling Fault
LED 603 / LED3
5
Sensor on drive not
reading properly.
Replace drive.
DC Bus
Over Voltage
LED604 / LED2
7
DC BUS OVER
VOLTAGE –
INVERTER DRIVE
High input voltage
Check the DC bus voltage if it is
> 385 VDC. Use bus voltage terminals
found in Figures 12-14.
Check the line voltage if it is > 265VAC.
(If high, contact utility provider.)
Damaged Inverter Board
Replace drive.
DC Bus
Under Voltage
LED604 / LED2
8
DC BUS UNDER
VOLTAGE –
INVERTER DRIVE
Low input voltage
Check the DC bus voltage if it is < 385VDC. Use
bus voltage terminals found in Figures 12-14.
Check the line voltage if it is < 187VAC.
(If low, contact utility provider.)
Damaged Inverter Board
Replace drive.
AC Input
Over Voltage
LED604 / LED2
10
AC INPUT OVER
VOLTAGE –
INVERTER DRIVE
High input voltage
Check the line voltage if it is > 265VAC.
(If high, contact utility provider.)
Check the DC bus voltage if it is > 385VDC. Use
bus voltage terminals found in Figures 12-14.
Damaged Inverter Board
Replace drive.
AC Input
Under Voltage
LED604 / LED2
9
AC INPUT UNDER
VOLTAGE –
INVERTER DRIVE
Low input voltage
Check the line voltage if it is < 187VAC.
(If low, contact utility provider.)
Check the DC bus voltage if it is < 385VDC. Use
bus voltage terminals found in Figures 12-14.
Damaged Inverter Board
Replace drive.
Power Module
Over Temp
LED604 / LED2
4
POWER MODULE
OVER TEMP –
INVERTER DRIVE
Outdoor airflow is
too low or off.
Verify proper airflow over the drive heat sink.
Inverter component
damage.
Replace drive.
PFC-IGBT
Over Temp
LED604 / LED2
5
PFC-IGBT OVER TEMP –
INVERTER DRIVE
Outdoor airflow is
too low or off.
Verify proper airflow over the drive heat sink.
Inverter component
damage.
Replace drive.