5284792-UIM-D-1017
Johnson Controls Unitary Products
17
Lost Rotor
Position
LED604 / LED2
2
LOST ROTOR POSITION –
INVERTER DRIVE
Loose or incorrect
wire connections
Check lead to the compressor plug
and at inverter drive.
W: Red Wire (RED).
V: Black Wire (BLK).
U: Brown Wire (BRN).
Phase imbalance or
shorted compressor
windings.
Check compressor winding resistance
at the compressor terminals.
2 Ton - 0.681
3 Ton - 0.203
4 Ton - 0.203
5 Ton - 0.203
Inverter component
damage.
Replace drive.
Internal compressor
damage.
Replace compressor.
Compressor Phase
Current Imbalance
LED 603 / LED3
14
COMPRESSOR PHASE
CURRENT IMBALANCE –
INVERTER DRIVE
Loose or incorrect
wire connections
Check lead to the compressor plug
and at inverter drive.
W: Black Wire (BLK).
V: Red Wire (RED).
U: Brown Wire (BRN).
Phase imbalance or
shorted compressor
windings
Check compressor winding resistance
at the compressor terminals.
2 Ton - 0.681
3 Ton - 0.203
4 Ton - 0.203
5 Ton - 0.203
Inverter component
damage.
Replace drive.
Internal compressor
damage.
Replace compressor.
Microelectronic
Fault
LED 603 / LED3
13
MICROELECTRONIC
FAULT –
INVERTER DRIVE
Digital Signal
Processor self-check.
Remove power to drive for 2 minutes. Reapply
power. If problem remains, replace drive.
EEPROM Fault
LED 603 / LED3
12
Digital Signal
Processor self-check.
Remove power to drive for 2 minutes. Reapply
power. If problem remains, replace drive.
Power Module Temp
Low or Sensor
Open Fault
LED 603 / LED3
2
POWER MODULE TEMP
LOW / SENSOR OPEN –
INVERTER DRIVE
Temperature
sensor on the drive
is potentially faulty.
Remove power to drive for 2 minutes. Reapply
power. If problem remains, replace drive.
DC Bus
Under Voltage
LED604 / LED2
17
NA
Low input voltage
Check the DC bus voltage if it is < 385VDC. Use
bus voltage terminals found in Figures 12-14.
Check the line voltage if it is < 187VAC.
(If low, contact utility provider.)
Damaged Inverter Board
Replace drive.
AC Input Current
Foldback Timeout
LED 603 / LED3
15
AC INPUT CURRENT
FOLDBACK –
INVERTER DRIVE
Reduced input voltage
Check the line voltage if it is < 187VAC.
Distorted input voltage
Check the line voltage for noise.
Call an electrician or the power
company if noise is found.
High compressor load.
Check the compressor is operating
with in specified limits.
Drive component issue.
Replace drive.
Sensor on drive not
reading properly.
Replace drive.
Modbus
Communication Lost
LED 603 / LED3
11
MODBUS COMM LOST –
INVERTER DRIVE
Loose or
disconnected
communication
harness.
Validate harness connection.
Broken or damaged
communication
harness.
Check continuity of harness wires. If an problem
is found, replace communication harness.
Damaged OD
Control Board
Remove power to system for 2 minutes.
Reapply power. If problem remains,
replace OD Control Board.
Damaged
Inverter Board
Remove power to drive for 2 minutes. Reapply
power. If problem remains, replace drive.
TABLE 8:
Inverter Drive Fault/Status Code Display
Inverter Drive
Description
LED
1
Blink
Codes
OD Display Text
Possible
Causes
Solution