background image

5284792-UIM-D-1017

4

Johnson Controls Unitary Products

ADD-ON REPLACEMENT/RETROFIT

When this unit is being used as a replacement for an existing R-410A
unit, these are matched systems and the indoor coil and outdoor unit
must be replaced. The following steps should be performed in order to
insure proper system operation and performance. Line-set change out
is also recommended.

1. Change-out of the indoor coil to an approved R-410A coil / air han-

dling unit combination with the appropriate metering device.

2. Change-out of the line-set when replacing an R-22 unit with an

R410-A unit is highly recommended to reduce cross-contamination
of oils and refrigerants.

3. If change-out of the line set is not practical, then the following pre-

cautions should be taken.

• Inspect the line set for kinks, sharp bends, or other restrictions,

and for corrosion.

• Determine if there are any low spots which might be serving as oil

traps.

• Flush the line set with a commercially available flush kit to remove

as much of the existing oil and contaminants as possible.

• Install a suction line filter-drier to trap any remaining contami-

nants, and remove after 50 hours of operation.

4. If the outdoor unit is being replaced due to a compressor burnout,

then installation of a 100% activated alumina suction-line filter drier
in the suction-line is required, in addition to the factory installed bi-
flow liquid-line drier. Operate the system for 10 hours. Monitor the
suction drier pressure drop. If the pressure drop exceeds 3 psig,
replace both the suction-line and liquid-line driers. After a total of 10
hours run time where the suction-line pressure drop has not
exceeded 3 psig, replace the liquid line drier, and remove the suc-
tion-line drier. Never leave a suction-line drier in the system longer
than 50 hours of run time.

GROUND INSTALLATION

The unit may be installed at ground level on a solid base that will not
shift or settle, causing strain on the refrigerant lines and possible leaks.
The unit must be installed in as level a position as possible while main-
taining the clearances shown in Figure 2.

Normal operating sound levels may be objectionable if the unit is placed
directly under windows of certain rooms (bedrooms, study, etc.).

Elevate the unit sufficiently to prevent any blockage of the air entrances
by snow in areas where there will be snow accumulation. Check the
local weather bureau for the expected snow accumulation in your area.

Isolate the unit from rain gutters to avoid any possible wash out of the
foundation.

ROOF INSTALLATION

When installing units on a roof, the structure must be capable of sup-
porting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibra-
tion into the conditioned space.

WALL MOUNT INSTALLATION

Care must be taken to mount the outdoor unit on a solid base that is
sloped to shed water, secure from settlement, and is isolated from the
structural foundation or walls to prevent sound and vibration transmis-
sion into the living space.

On occasion, site conditions may require direct wall mounted brackets
to be used to locate and support the outdoor unit. In these applications,
care must be taken to address unit base pan support, structural integ-
rity, safe access and serviceability, as well as the possible sound and
vibration transmission into the structure. Wall mounting requires 3
mounting brackets and best served by a properly engineered solution.

See price pages for specific part number for your application.

UNIT PLACEMENT

1. Provide a base in the pre-determined location.

2. Remove the shipping carton and inspect for possible damage.

3. Ensure that compressor tie-down bolts remain tightened.

4. Position the unit on the base provided.

LIQUID LINE FILTER-DRIER

The air conditioning unit's copper spun filter/dryer is located on the liq-
uid line.

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora-
tor coil using field supplied refrigerant grade (ACR) copper tubing that is
internally clean and dry. Units should be installed only with the tubing
sizes for approved system combinations as specified in tabular data
sheet. The charge given is applicable for total tubing lengths up to 15
feet (4.6 m).

PRECAUTIONS DURING LINE INSTALLATION

Install the refrigerant lines with as few bends as possible. Care must be
taken not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending around
obstruction is necessary. If soft copper must be used, care must be
taken to avoid sharp bends which may cause a restriction.

1. The lines should be installed so that they will not obstruct service

access to the coil, air handling system, or filter.

2. Care must also be taken to isolate the refrigerant lines to minimize

noise transmission from the equipment to the structure.

3. The vapor line must be insulated with a minimum of 1/2” foam rub-

ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight, high temperatures, or excessive humidity
must also be insulated.

4. Tape and suspend the refrigerant lines as shown. DO NOT allow

tube metal-to-metal contact. See Figure 3.

 WARNING

The outdoor unit should not be installed in an area where mud or ice
could cause personal injury.

!

 CAUTION

Failure to use the same as the original factory drier or using a substi-
tute drier or a granular type may result in damage to the equipment.

NOTICE

Replacements for the liquid line drier must  be  exactly  the  same  as
marked on the original factory drier. See Source 1 for O.E.M. replace-
ment driers.

R-410A Filter-Drier Source 1 Part No.

Apply with Models

S1-02922195000

All

NOTICE

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant.

 WARNING

Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or death.

 CAUTION

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery system must
be designed to handle R-410A. If you are unsure, consult the equip-
ment manufacturer.

!

!

!

Summary of Contents for YXV SERIES

Page 1: ...II SAFETY This is a safety alert symbol When you see this symbol on labels or in manuals be alert to the potential for personal injury Understand and pay particular attention to the signal words DANGER WARNING or CAUTION DANGER indicates an imminently hazardous situation which if not avoided will result in death or serious injury WARNING indicates a potentially hazardous situation which if not avo...

Page 2: ...r below refer to the Optional Cold Weather Charging procedures near the end of SECTION VI SYSTEM CHARGE There is an Optional Cold Weather Charging accessory kit to prevent the outdoor unit from taking in cold air below 55 F The kit part number can be found in the list of accessory kits on the UPGNET web site Provide adequate structural support for the unit CAUTION This product must be installed in...

Page 3: ...QWHU EUDFH XQGHU FHQWHU RI FRPSUHVVRU 127 QVXUH DGHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO FIGURE 2 Alternative Installation Clearances 0 1 080 5 1 7 1 81 76 127 OHDUDQFH EHWZHHQ WZR XQLWV PD EH UHGXFHG WR PLQLPXP SURYLGHG WKH VHUYLFH DFFHVV FOHDUDQFH LV LQFUHDVHG WR PLQLPXP DQG WKH FOHDUDQFH RQ HDFK UHPDLQLQJ VLGH LV PDLQWDL...

Page 4: ... conditions may require direct wall mounted brackets to be used to locate and support the outdoor unit In these applications care must be taken to address unit base pan support structural integ rity safe access and serviceability as well as the possible sound and vibration transmission into the structure Wall mounting requires 3 mounting brackets and best served by a properly engineered solution S...

Page 5: ...e vapor service port connection After this connection has cooled remove the nitrogen source from the liquid fitting ser vice port 6 Braze the liquid line to the evaporator liquid connection Nitrogen should be flowing through the evaporator coil 7 Slide the grommet away from the vapor connection at the indoor coil and wrap with a wet rag as shown in Figure 5 Braze the vapor line to the evaporator v...

Page 6: ...eatherproof disconnect switch outdoors and within sight of the unit per local code 2 Remove the screws at the top and sides of the corner cover Slide the control box cover down and remove from unit 3 Run power wiring from the disconnect switch to the unit 4 Route wires from disconnect through power wiring exit provided and into the unit control box as shown in Figure 1 and view the openings in Fig...

Page 7: ...al set up process using the HxTM thermostat additional fine tuning of the airflow is accomplished by selecting on of the three operating profiles The three operating profiles include humid dry or normal Select the one that best reflects the out door environment where the conditioned space is located This selec tion adjusts the how the indoor blower and the compressor work together to manage temper...

Page 8: ...nce visits the charge verification display can be used to quickly check overall system condition and the system charge without attaching a separate manifold gauge set or temperature sensors 6 Permanently mark the unit data plate with the total amount of refrig erant in the system FIGURE 9 System Charging Connections 6 5 7 0 521 8 5HTXLUHG IRU HYDFXDWLRQ SURFHGXUH RQO 9 880 3803 7 6 7 03 5 785 1 72...

Page 9: ...door transformer secondary 24 VAC volt age and provides low voltage protection for the heat pump and its com ponents If the voltage drops below approximately 22 VAC the control continues to energize any outputs that are already energized If the volt age drops below approximately 19 VAC the control immediately de energizes the outputs and can no longer energize any outputs until the voltage level i...

Page 10: ...oltage is applied The control will scroll and display STANDBY when there are no active calls for compressor operation TABLE 4 Same Priority Fault Storage Control Description Time of Fault Fault Priority Inverter Control Fault Microelectronic Fault 10 15 00 1 Outdoor Control Fault Inverter Control Communications Fault 10 15 01 1 TABLE 5 Status Code Display Description Required Condition LED Color N...

Page 11: ...on Saved Configuration Selection The system will save all individual con figuration selections made on the Outdoor Display Upon returning to a previously saved configuration the system shall display the previously saved configuration setting s Not the Default setting s unless the saved selection was in fact the default selection Operational Mode The system will display Inverter profile and revers ...

Page 12: ...m in high pressure switch lockout last mode of operation was normal compressor RED Solid HPS HARD LOCKOUT NORMAL See HPS fault See HPS fault X Low Voltage 19 VAC RED Solid LOW VOLTAGE BELOW 19VAC Under Voltage Check input power supply wires Check input power supply and 24VAC circuit before and during operation to verify voltage is within range given in manual 197 252Vac and 19 Check 24Vac transfor...

Page 13: ...ure See Ambient Sensor failure X COIL TEMP SENSOR OPEN HARD LOCKOUT See Ambient Sensor failure See Ambient Sensor failure X Liquid line temperature sensor failure short not in lockout yet RED Solid LIQUID TEMP SENSOR SHORT See Ambient Sensor failure See Ambient Sensor failure X Liquid line temperature sensor failure short RED Solid LIQUID TEMP SENSOR SHORT SOFT LOCKOUT See Ambient Sensor failure S...

Page 14: ...pressure sensor failure high voltage RED Solid DISCHARGE PRESSURE SENSOR HIGH VOLTAGE SOFT LOCKOUT See Discharge Pressure Sensor Fault See Discharge Pressure Sensor Fault X Suction pressure sensor failure low voltage RED Solid SUCTION PRESSURE SENSOR LOW VOLTAGE SOFT LOCKOUT Bad wiring harness Check harness for continuity X Bad OD control board If supply voltage across BLK and BLU WHT doesn t read...

Page 15: ...motor operation and airflow restrictions Dirty ID coil External static is too high correct duct work ID air temp out of range Verify the ID ambient temperature is with the range listed in the IOM design parameters Reduced or no ID airflow due to motor limits Check motor current against limits Check input voltage to ensure within range Insufficient charge Check refrigerant charge compared to tech s...

Page 16: ...nt issue Replace drive AC Input Current Sampling Fault LED 603 LED3 5 Sensor on drive not reading properly Replace drive DC Bus Over Voltage LED604 LED2 7 DC BUS OVER VOLTAGE INVERTER DRIVE High input voltage Check the DC bus voltage if it is 385 VDC Use bus voltage terminals found in Figures 12 14 Check the line voltage if it is 265VAC If high contact utility provider Damaged Inverter Board Repla...

Page 17: ... Temp Low or Sensor Open Fault LED 603 LED3 2 POWER MODULE TEMP LOW SENSOR OPEN INVERTER DRIVE Temperature sensor on the drive is potentially faulty Remove power to drive for 2 minutes Reapply power If problem remains replace drive DC Bus Under Voltage LED604 LED2 17 NA Low input voltage Check the DC bus voltage if it is 385VDC Use bus voltage terminals found in Figures 12 14 Check the line voltag...

Page 18: ...is too low or off Verify proper airflow over the drive heat sink Inverter component damage Replace drive Compressor Model Configuration Error LED 604 LED2 22 COMPRESSOR MODEL CONFIGURATION ERROR INVERTER DRIVE Compressor model and configuration code do not match Check system configuration and select proper system tonnage in repair part menu If proper option is not available the correct drive has n...

Page 19: ...ls Unitary Products 19 FIGURE 12 2 Ton Inverter Drive LED Location 86 92 7 7 50 1 6 FIGURE 13 3 4 Ton Inverter Drive LED Location 86 92 7 7 50 1 6 FIGURE 14 5 Ton Inverter Drive LED Location OO V DUH EHQHDWK WKH SODWH 86 92 7 7 50 1 6 ...

Page 20: ...ower before servicing Wait 2 minutes to ensure that drive capacitors are discharged before servicing Use compressor with grounded system only Molded electrical plug must be used for connection to compressor BURN HAZARD Failure to follow these warnings could result in serious personal injury or property damage Ensure that materials and wiring do not touch high temperature areas of the compressor Pe...

Page 21: ...8 118 4 3889 110 230 0 517 13 8 6 65219 49 120 2 3743 111 231 8 503 12 10 4 61711 50 122 0 3603 112 233 6 489 11 12 2 58415 51 123 8 3469 113 235 4 476 10 14 0 55319 52 125 6 3340 114 237 2 463 9 15 8 52392 53 127 4 3217 115 239 0 450 8 17 6 49640 54 129 2 3099 116 240 8 437 7 19 4 47052 55 131 0 2986 117 242 6 425 6 21 2 44617 56 132 8 2878 118 244 4 413 5 23 0 42324 57 134 6 2774 119 246 2 401 4...

Page 22: ... a low suction pressure fault is recognized regardless of a bypass time SECTION IX INSTRUCTING THE OWNER Assist the owner with registering the unit warranty using the warranty card included with the unit or preferably online at www upgproductregistration com It is strongly recommended to com plete a startup sheet showing the critical readings of the unit at the time of commissioning which can be u...

Page 23: ...TEMP SENSOR TB TERMINAL BLOCK XFMR TRANSFORMER BLK BLACK BLU BLUE BLU WHT BLUE w WHITE STRIPE BRN BROWN GRN GREEN PUR PURPLE RED RED RED WHT RED w WHITE STRIPE WHT WHITE YEL YELLOW YEL PINK YELLOW w PINK STRIPE 5295812 UWD C 0217 FERRITE RING CHOKE DS LTS AMB CTS R C P6 P7 P8 P10 P2 P3 P1 P5 P4 A B C A R B C G S V G S V DTS DPT SPT STS RV DR C O Y OD FAN RS485 COMM EEV COMM RS485 COMM 3A COMPRESSO...

Page 24: ... WITH THIS UNIT MUST BE REPLACED IT MUST BE REPLACED WITH 105 C THERMOPLASTIC OR ITS EQUIVALENT 1 2 AMB AMBIENT TEMP SENSOR DPT DISCHARGE PRESSURE DR DEMAND RESPONSE DS DISPLAY SWITCH DTS DISCHARGE TEMP SENSOR HPS HIGH PRESS SWITCH LTS LIQUID TEMP SENSOR SPT SUCTION PRESSURE STS SUCTION TEMP SENSOR TB TERMINAL BLOCK XFMR TRANSFORMER BLK BLACK BLU BLUE BLU WHT BLUE w WHITE STRIPE BRN BROWN GRN GREE...

Page 25: ...272 7 273 8 273 7 272 6 85 294 8 295 8 295 7 293 6 90 318 8 319 8 318 7 316 5 95 343 8 344 9 343 7 341 5 100 370 9 371 9 370 7 367 5 105 398 9 399 9 398 8 395 6 110 428 9 429 10 427 8 425 6 115 459 10 460 10 458 9 457 7 120 491 10 492 10 491 9 490 8 125 525 11 526 11 525 10 525 9 YXV48B21S HIGH SPEED COOLING SUBCOOLING CHARGING CHART OUTDOOR AMBIENT DB F INDOOR WET BULB F AT 80 F DRY BULB 57 62 67...

Page 26: ...5284792 UIM D 1017 26 Johnson Controls Unitary Products NOTES ...

Page 27: ...lts AC 230 volt AC Measured voltage L1 to L2 Total amperes L1 L2 Compressor amperes L1 L2 Measured voltage R and C outdoor unit control board Air Flow Setup Cooling Supply static inches of water column Supply air dry bulb temperature Return air dry bulb temperature Temperature drop A B C D Blower Type Set Up Outside air dry bulb temperature Return air wet bulb temperature Supply air wet bulb tempe...

Page 28: ...dditional Job Details Provide owner with the owner s manual Explain thermostat use and programming if applicable to owner Unit Operation and Cycle Test Operate the unit through continuous fan cycles from the thermostat noting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Job site has been cleaned indoor and outdoor debris...

Reviews: