59
JOHNSON CONTROLS
FORM 100.50-EG12 (918)
TABLE 28 -
SUPPLY, RETURN, AND EXHAUST FAN MOTOR DATA
PREMIUM EFFICIENCY - ODP
PREMIUM EFFICIENCY - TEFC
MOTOR
HP
NOMINAL VOLTAGE
MOTOR
HP
NOMINAL VOLTAGE
208/3/60 230/3/60 460/3/60 575/3/60
208/3/60 230/3/60 460/3/60 575/3/60
FLA
FLA
FLA
FLA
FLA
FLA
FLA
FLA
5
14
13.2
6.6
5.3
5
13.9
13.4
6.7
5.3
7.5
20.4
19.4
9.7
8
7.5
20
19
9.5
7.6
10
26
25
12.5
10
10
25.4
24
12
9.6
15
38
36
18
14.2
15
38
36.2
18.1
14.6
20
52
48
24
18.9
20
52
48
24
19.2
25
64
60
30
24.5
25
64
62
31
24
30
76
72
36
28
30
78
76
38
29
40
99
98
49
40
40
102
96
48
37
50
121
114
57
46
50
128
116
58
45
60
144
136
68
56
60
149
135
67.8
54.4
TABLE 29 -
POWER SUPPLY VOLTAGE LIMITS
Nominal Voltage
Power Supply
Minimum Voltage
Maximum Voltage
208
200V/3Ph/60Hz
187
218
240
230V/3Ph/60Hz
216
252
480
460V/3Ph/60Hz
432
504
600
575V/3Ph/60Hz
540
630
TABLE 30 -
CONDENSER FAN MOTOR RLA
RLA EACH MOTOR
208V/3PH/60HZ
230V/3PH/60HZ
460V/3PH/60HZ
575V/3PH/60HZ
7.3
6.2
3.1
2.5
MODEL
QUANTITY OF FANS
208V/3PH/60HZ
230V/3PH/60HZ
460V/3PH/60HZ
575V/3PH/60HZ
YPAL070–105
6
43.8
37.2
18.6
15.0
TABLE 31 -
MISCELLANEOUS ELECTRICAL DATA
DESCRIPTION
NOMINAL VOLTAGE
208V
230V
460V
575V
380V-60
AMPS
AMPS
AMPS
AMPS
AMPS
Control Transformer 750 VA
3.6
3.3
1.6
1.3
2.0
Control Transformer 1.0 KVA
4.8
4.4
2.2
1.8
2.6
Convenience Outlet
9.6
8.7
4.4
3.5
N/A
Gas Heat
9.6
8.7
4.4
3.5
5.3
TABLE 32 -
ELECTRIC HEAT AMP DRAW
KW*
200V/3Ph/60Hz
240V/3Ph/60Hz
480V/3Ph/60Hz
600V/3Ph/60Hz
AMPS
AMPS
AMPS
AMPS
80
193
193
96
80
108
260
260
130
109
150
181
151
200
241
201
250
301
251
NOTE
Heaters will be sized as follows: 208V heaters rated at 208V, 230V heaters rated at 240V, 460V heaters rated at 480V, 575V heaters rated