Supply Fan Data
TABLE 14 -
YPAL070–080: 28X25 FORWARD-CURVED FAN
TOTAL STATIC PRESSURE (IWG)
CFM
STD. AIR
1.0
2.0
3.0
4.0
5.0
6.0
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
18,000
513
10.0
616
13.9
20,000
520
11.7
619
15.9
717
20.8
22,000
527
13.6
629
18.3
712
22.9
808
28.9
24,000
537
15.8
637
20.9
720
25.9
795
31.1
26,000
549
18.3
643
23.6
729
29.1
801
34.5
28,000
562
21.2
651
26.6
736
32.6
810
38.5
30,000
574
24.2
662
30.1
742
36.3
819
42.8
32,000
585
27.4
674
34.0
750
40.3
825
47.2
34,000
597
30.9
686
38.2
760
44.8
NOTE:
For performance at operating points not included in these tables, consult your local Johnson Controls representative.
TABLE 15 -
YPAL070–105: 32-INCH AIRFOIL FAN
TOTAL STATIC PRESSURE (IWG)
CFM
STD. AIR
1.0
2.0
3.0
4.0
5.0
6.0
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
18,000
937
12.8
1046
17.0
1149
21.7
1249
26.8
20,000
970
14.6
1071
18.9
1168
23.7
1261
28.8
22,000
906
12.4
1006
16.6
1101
21.1
1192
26.0
1280
31.2
24,000
951
14.5
1046
18.9
1136
23.6
1222
28.7
1305
34.0
26,000
900
12.4
998
16.8
1088
21.5
1174
26.4
1255
31.7
1334
37.2
28,000
954
14.8
1047
19.5
1133
24.4
1214
29.6
1292
35.0
1367
40.7
30,000
1008
17.4
1097
22.4
1179
27.6
1256
33.1
1331
38.7
1402
44.6
32,000
1064
20.5
1148
25.8
1226
31.2
1300
36.9
1372
42.8
1440
48.9
YPAL090–105 Only
34,000
1119
23.8
1200
29.4
1275
35.2
1346
41.1
1414
47.3
1481
53.6
36,000
1176
27.6
1252
33.5
1324
39.5
1393
45.7
1459
52.1
1523
58.7
NOTE:
For performance at operating points not included in these tables, consult your local Johnson Controls representative.