19
JOHNSON CONTROLS
FORM 100.50-EG12 (918)
Physical Data
TABLE 3 -
PHYSICAL DATA – MODELS 70–105
MODEL SIZE
70
75
80
90
105
COMPRESSOR DATA
Quantity/Size (Nominal HP)
6x10
4x11, 2x13
4x13, 2x11
4x15, 2x13
3x20, 3x15
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Capacity Steps (Qty x %)
6x16
4x16, 2x18
4x17, 2x15
4x18, 2x15
3x14, 3x19
SUPPLY FAN AND DRIVE
Quantity
1
1
1
1/1
1/1
Type
FC
FC
FC
AF
AF
Size
28-25
28-25
28-25
32
32
Motor Size Range (min. to max. HP)
10–50
10–50
10–50
10–50
10–50
Airflow Range (min. to max. CFM)
14,000–29,000 15,550–29,000 15,000–32,000 17,500–36,000 21,000–36,000
Static Pressure Range (min. to max. ESP)
0–4 inches
0–4 inches
0–4 inches
0–6 inches
0–6 inches
OPTIONAL AIRFOIL SUPPLY FAN
Quantity
1/1
1/1
1/1
1/1
1/1
Type
AF
AF
AF
AF
AF
Size
32
32
32
32
32
Motor Size Range (min. to max. HP)
15–50
15–50
15–50
15–50
15–50
Airflow Range (min. to max. CFM)
14,000–29,000 15,550–29,000 15,000–32,000 17,500–36,000 21,000–36,000
Static Pressure Range (min. to max. ESP)
0–6 inches
0–6 inches
0–6 inches
0–6 inches
0–6 inches
OPTIONAL DIRECT DRIVE PLENUM (DDP) SUPPLY FAN
Quantity
1
1
1
1
1
Type
DDP
DDP
DDP
DDP
DDP
Size
402-9-100/120 402-9-100/120 402-9-100/120 402-9-100/120 402-9-100/120
Motor Size Range (min. to max. HP)
10–75
10–75
10–75
10–75
10–75
Airflow Range (min. to max. CFM)
14,000–29,000 15,550–29,000 15,000–32,000 17,500–36,000 21,000–36,000
Static Pressure Range (min. to max. TSP)
1–8 inches
1–8 inches
1–8 inches
1–8 inches
1–8 inches
EXHAUST FAN
Quantity
2
2
2
2
2
Type
FC
FC
FC
FC
FC
Size
18-18
18-18
18-18
18-18
18-18
Motor Size Range (min. to max. HP
10–20
10–20
10–20
10–20
10–20
Airflow Range (min. to max. CFM)
4,000–32,000 4,000–32,000 4,000–32,000 4,000–32,000 4,000–32,000
Static Pressure Range (min. to max. ESP)
0–2 inches
0–2 inches
0–2 inches
0–2 inches
0–2 inches
OPTIONAL EXHAUST FAN
Quantity
2/1
2/1
2/1
2/1
2/1
Type
FC
FC
FC
FC
FC
Size
20-18
20-18
20-18
20-18
20-18
Motor Size Range (min. to max. HP, total
for two fans)
5–30
5–30
5–30
5–30
5–30
Airflow Range (min. to max. CFM)
4,000–36,000 4,000–36,000 4,000–36,000 4,000–36,000 4,000–36,000
Static Pressure Range (min. to max. iwg)
0–2 inches
0–2 inches
0–2 inches
0–2 inches
0–2 inches
OPTIONAL RETURN FAN
Quantity
2/2
2/2
2/2
2/2
2/2
Type
Plenum
Plenum
Plenum
Plenum
Plenum
Size
270
270
270
270
270
Motor Size Range (min. to max. HP, total
for two fans)
10–30
10–30
10–30
10–40
10–40
Airflow Range (min. to max. CFM)
4,000–32,000 4,000–32,000 4,000–32,000 4,000–36,000 4,000–36,000
Static Pressure Range (min. to max. iwg)
0–3 inches
0–3 inches
0–3 inches
0–3 inches
0–3 inches