background image

JOHNSON CONTROLS

19

FORM 160.69-N2 

ISSUE DATE: 7/31/2015

2

SECTION 2 - INSTALLATION

RIGGING UNIT TO FINAL LOCATION

Rig the unit to its final location on the floor or mount-

ing pad, lift the unit (or shell assembly) by means of an 

overhead lift and lower the unit to its mounting posi-

tion. (If optional shipping skids are used, remove them 

before lowering the chiller to its mounting position.)

At this point units shipped dismantled 

should be assembled under the supervi-

sion of a Johnson Controls representative.

If evaporator is to be field insulated, the insulation 

should be applied to the evaporator before the unit is 

placed in position while the unit is in the lift position. 

Be sure unit is properly supported. (See 

Insulation on 

page 23)

LOCATING AND INSTALLING ISOLATOR PADS 

(Refer to Figure 2 on page 11 or Figure 3 on page 

12)

After the isolator pads have been placed into position 

on the floor, lower the chiller onto the pads. When the 

unit is in place, remove the rigging equipment and 

check that the unit is level.  The unit should be level 

within 1/4" (6 mm) from one end to the other end and 

from front to the rear. If the chiller is not level within 

the amount specified, lift it and place shims between 

the isolation pad and the chiller tube sheets. (Shims 

furnished by the installer.) Lower unit again and re-

check to see that it is level.

CHECKING THE ISOLATION PAD 

DEFLECTION

All isolation pads should be checked for the proper de-

flection while checking to see if the unit is level. Each 

pad should be deflected approximately 0.10 inchs  (2.5 

mm) to 0.20 inchs (5 mm). If an isolation pad is under-

deflected, shims should be placed between the unit tube 

sheet and the top of the pad to equally deflect all pads.

LEVELING THE UNIT

The longitudinal alignment of the unit should be 

checked by placing a level on the top center of the evap-

orator shell. Transverse alignment should be checked 

by placing a level on top of the shell end sheets.

INSTALLING OPTIONAL SPRING ISOLATORS

When ordered, spring type isolator assemblies will be 

furnished with the unit. The 4 assemblies are identical 

and can be placed at any of the 4 corners of the unit. 

(Refer to Figure 4 on page 13.)

While the unit is still suspended by the rigging, the iso-

lators should be bolted to the unit by inserting the cap 

screws through the holes in the mounting bracket into 

the tapped hole in the top of the isolator leveling bolts. 

Then the unit can be lowered onto the floor.
The leveling bolts should now be rotated one (1) turn at 

a time, in sequence, until the unit end sheets are clear 

of the floor by the dimension shown in Fig. 7 or 8 and 

the unit is level. Check that the unit is level, both lon-

gitudinally and transversely (see Leveling the Unit). If 

the leveling bolts are not long enough to level unit due 

to an uneven or sloping floor or foundation, steel shims 

(grouted, if necessary) must be added beneath the iso-

lator assemblies as necessary.
After the unit is leveled, wedge and shim under each 

corner to solidly support the unit in this position while 

piping connections are being made, pipe hangers ad-

justed and connections checked for alignment. Then 

the unit is filled with water and checked for leaks. The 

leveling bolts should now be finally adjusted until the 

wedges and shims can be removed. The unit should 

now be in correct level position, clear of the floor or 

foundation and without any effect from the weight of 

the piping.

PIPING CONNECTIONS

After the unit is leveled (and wedged in place for op-

tional spring isolators) the piping connections may be 

made; chilled water, condenser water and refrigerant 

relief. The piping should be arranged with offsets for 

flexibility, and adequately supported and braced inde-

pendently of the unit to avoid strain on the unit and 

vibration transmission. Hangers must allow for align-

ment of pipe. Isolators (by others) in the piping and 

hangers are highly desirable, and may be required by 

specifications, in order to effectively utilize the vibra-

tion isolation characteristics of the vibration isolation 

mounts of the unit.

Check for piping alignment –

 Upon completion of 

Summary of Contents for York R-134A

Page 1: ...STYLE B R 134A COOLING ONLY WITH OPTIVIEW CONTROL CENTER AND ELECTRO MECHANICAL STARTER CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTION Supersedes 160 69 N2 912 Form 160 69 N2 715 Issue Date Jul...

Page 2: ...his document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in ques...

Page 3: ...anual or product owner Updated manuals if applicable can be obtained by contacting the nearest Johnson Controls Service office or accessing the John son Controls QuickLIT website at http cgproducts jo...

Page 4: ...5 J7 YD XH XD J2 DA B POWER SUPPLY for 60 Hz 5 for 50 Hz DESIGN LEVEL CONDENSER CODE KB KC KD KE K2 K3 K4 K5 HB HC HD HE H2 H3 H4 H5 GB GC GD GE G2 G3 G4 G5 FB FC FD FE F2 F3 F4 F5 EB EC ED EE E2 E3 E...

Page 5: ...ecking The Isolation Pad Deflection 19 Leveling The Unit 19 Installing Optional Spring Isolators 19 Piping Connections 19 Evaporator And Condenser Water Piping 20 Chilled Water 20 Condenser Water Circ...

Page 6: ...ompressor Units 15 FIGURE 7 Schematic of a Typical Piping Arrangement 21 FIGURE 8 Typical Refrigerant Vent Piping 21 FIGURE 9 Control Panel Positioning 22 FIGURE 10 Motor Connections Electro Mechanica...

Page 7: ...rigging the unit to its operating position and the assembly of components 4 Do not make final power supply connections to the compressor motors or control center 5 Do not charge the compressors with o...

Page 8: ...or under the supervision of a Johnson Controls representative See Form 160 69 NM3 When more than one chiller is involved the major parts of each unit will be marked to prevent mixing of assemblies Pip...

Page 9: ...or rigging Do not rig vertically The rigging and operating weights and overall dimen sions are given on pages 6 thru 8 as a guide in deter mining the clearances required for rigging Add 6 15 cm to ove...

Page 10: ...JOHNSON CONTROLS 10 FORM 160 69 N2 ISSUE DATE 7 31 2015 SECTION 1 Introduction LD09014a Figure 1 RIGGING...

Page 11: ...ORS LD19590a LD19571a SHELL END SHEET DIA HOLE See Detail A 10 254 8 203 5 127 C C and D D Up to 225 000 lbs 102 060 Kgs 9 229 LD19589a SHELL END SHEET DIA HOLE See Detail A 10 254 8 203 5 127 B B Up...

Page 12: ...060 Kgs 11 5 3176 11 279 10 254 8 D D Up to 225 000 lbs 102 060 Kgs 12 9 3887 11 279 10 254 8 E E Up to 280 000 lbs 127 005 Kgs 12 9 3887 11 279 12 305 8 F F Up to 280 000 lbs 127 005 Kgs 13 9 4192 1...

Page 13: ...12 SPRING ISOLATORS END SHEET CAP SCREW ADJUSTING BOLT 6 1 4 159 SHELL 4 SPRING ISOLATORS END SHEET CAP SCREW ADJUSTING BOLT 15 1 4 387 3 76 UNIT WEIGHT B B Up to 115 000 lbs 52 163 Kgs UNIT WEIGHT C...

Page 14: ...JOHNSON CONTROLS 14 FORM 160 69 N2 ISSUE DATE 7 31 2015 SECTION 1 Introduction Figure 5 MODEL YD CHILLER LD08634 OPTIVIEW CONTROL CENTER COMPRESSOR 1 EVAPORATOR MOTOR 1 MOTOR 2 CONDENSER COMPRESSOR 2...

Page 15: ...OLS 15 SECTION 1 Introduction FORM 160 69 N2 ISSUE DATE 7 31 2015 1 Figure 6 DIMENSIONS J COMPRESSOR UNITS LD09012 D L C A M 9 B FLOOR LINE EVAPORATOR CONDENSER F J E G H MOTORS COMPRESSORS LD09013 SH...

Page 16: ...1 6 1 4 464 1 6 7 8 479 1 6 7 8 479 H 0 11 11 16 297 1 1 3 4 297 1 2 5 8 371 1 2 5 8 371 1 3 5 8 397 1 3 5 8 397 1 4 1 4 413 1 4 1 4 413 J 1 7 5 8 498 1 9 1 4 498 2 1 1 2 648 2 1 1 2 648 2 2 660 2 2...

Page 17: ...6 938 3 147 3 342 1 516 6 842 3 103 10 638 4 825 4 523 2 051 9 112 4 133 D 10 692 4 849 6 554 2 973 13 316 6 039 18 095 8 207 9 508 4 312 18 186 8 248 E 10 692 4 849 6 554 2 973 13 316 6 039 18 095 8...

Page 18: ...109 5CV 800 5 800 2 636 CA 845 5 800 2 636 5CW 850 6 800 3 091 CB 900 5 800 2 636 5CX 900 6 800 3 091 DA 1000 6 800 3 091 5DA 1000 7 050 3 205 DB 1100 6 800 3 091 5DB 1100 7 300 3 318 DC 1200 7 050 3...

Page 19: ...ALLING OPTIONAL SPRING ISOLATORS When ordered spring type isolator assemblies will be furnished with the unit The 4 assemblies are identical and can be placed at any of the 4 corners of the unit Refer...

Page 20: ...ing connected to the chiller pumps or other equipment Permanent strainers supplied by others are required in both the evaporator and condenser water circuits to protect the chiller as well as the pump...

Page 21: ...EVAPORATOR Figure 8 TYPICAL REFRIGERANT VENT PIPING FLANGED JOINT TO PERMIT PIPING DISASSEMBLY CONDENSATION TRAP DUAL RELIEF VALVES VENT TO ATMOSPHERE SUPPORT VENT PIPING TO AVOID STRAIN ON RELIEF PIP...

Page 22: ...hly vented of all air at the high points REFRIGERANT RELIEF PIPING Each unit is equipped with pressure relief valves lo cated on the condenser on the evaporator and on the oil pump housing for the pur...

Page 23: ...rotation the starter power input and starter to motor connec tions must be check with a phase sequence indicator in the presence of the Johnson Controls representative DO NOT cut wires to final length...

Page 24: ...e contract price can be scheduled Notification to the Johnson Controls office should be by means of In stallation Check List and Request Form 160 69 CL1 in triplicate Table 5 MOTOR CONNECTIONS 3 PHASE...

Page 25: ...JOHNSON CONTROLS 25 FORM 160 69 N2 ISSUE DATE 7 31 2015 2 NOTES...

Page 26: ...nia USA 17405 1592 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2015 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 69 N2 715 Issue Date July 31 201...

Reviews: