23
GB
Technical characteristics, ROOFTOP D4IC, heat pump, B4IH
All data subject to change without notice.
Models
360
480
Total cooling capacity
Cooling capacity ()
kW
07.6
40
Nominal absorbed power in cool
kW
43
59.5
Heating capacity
Heating capacity () (2)
kW
27.
63.3
Nominal absorbed power in heat
kW
4.9
56.7
Capacity - electric heaters (400V) (2)
kW
37/50/60
37/50/60
Start-up/nominal power
A
85/67
2/272
N° of circuits
3
3
Limits of use
TAE maximum (DB) (winter) (3)
°C
46
46
TAE minimum (summer) (DB)
°C
7
7
TAE maximum (DB) (winter)
°C
20
20
TAE minimum (DB) (summer)
°C
-20
-20
Return air (DB) (summer) min./max.
°C
4/23
4/23
Return air (DB) (summer) min./max.
°C
20/32
20/32
Return air (DB) (winter) min./max.
°C
0/25
0/25
Refrigerant per circuit, depending upon model, R-407C
kg
3.7/3.7/3.7
3.7/3.7/27.9
Compressors (standard sump heater)
Type
(SCROLL)
Amount
3
3
Condensing unit fan
Nominal air flow
m
3
/h
000
000
Amount
3
4
Blade Ø
mm
630
630
Power
kW
.5
.5
Condensing unit coil
Distance between fins
mm
.8
.8/2.
Surface
m
2
7
8.5
Evaporating unit fan (4)
Nominal air flow
m
3
/h
2 000
25 000
Available pressure (at nominal flow)
Standard
Pa
300
275
With HPD accessory
Pa
480
465
Motor power
kW
9.2 (Standard)
(Optionall HPD)
(Standard)
5 (Optional HPD)
Transmission
Belt-pulley (adjustable diameter pulley)
Evaporating unit coil
Distance between fins
mm
.8
.8
Surface
m
2
2.9
3.7
Dimensions
Height
mm
85
85
Length (5)
mm
4 580
4 580
Width
mm
2 200
2 200
Weight (basic unit without accessories) (5)
kg
2 060
2 350
Summer conditions: Dry bulb indoor temperature: 27° C; wet bulb indoor temperature: 9° C.
DB - dry bulb. WB - wet bulb. TAE - outdoor air temperature.
() Data in accordance with EUROVENT conditions.
(2) Add consumption of interior motor.
(3) For temperatures of over 45° C, avoid direct sunlight. Should a lean-to roof be installed, it should not affect outdoor ventilation air flow.
(4) See technical information for indoor fan performances and adjustment.
(5) See technical information for dimensions and weights of accessories.
Summary of Contents for YORK B4IH 360
Page 2: ... ...
Page 3: ... Fig 1 Fig 2 Fig 3 Fig 5 Fig 6 Fig 4 Fig 7 ...
Page 4: ... Fig 8 Fig 9 Fig 10 Fig 11 ...
Page 11: ...11 Dimensiones espacios libres y accesos modelos D4IC y B4IH E ...
Page 12: ...12 E Resto de dimensiones y detalles segun D4IC B4IH ...
Page 20: ...20 GB Dimensions clearances and accesses models D4IC and B4IH ...
Page 29: ...29 F Dimensions dégagements nécessaires et accès modèles D4IC et B4IH ...
Page 38: ...38 P Dimensões espaços livres e acessos modelos D4IC e B4IH ...
Page 42: ...www johnsoncontrols com ...