4    W43A Humidistat Product/Technical Bulletin

IMPORTANT: Do not remove the humidistat cover

during installation.  The sensing
element must be carefully protected
against accidental damage.  All wiring
and mounting can be completed
without removing the cover.

!

  CAUTION: Shock hazard.  Disconnect

power supply before wiring
connections are made to prevent
electrical shock or possible
damage to the equipment.

To mount the W43A Humidistat:

1.

Select the proper mounting location (refer to the

Location Considerations

 section) and install a

vertical or horizontal wall box 4 to 5 feet
(1.2 to 1.5 m) above the floor.

2.

Run conduit or cable, as required by national
and/or local electric codes, from the wall box to the
equipment to be controlled.  Leave approximately
6 in. (152 mm) of wire for connection to the
humidistat terminals.

3.

Remove the humidistat mounting plate by
loosening the mounting plate locking screw (see
Figure 3), and lifting and removing the plate from
the base.

4.

Pull wires through the mounting plate and fasten
the plate, grounding screw end up, to the wall box
with the screws provided.

5.

Strip the wires and connect to the proper terminals
on the back of the humidistat.  See 

Wiring

Diagrams

 section.

Note:

Use the terminal screws furnished
(8-32 x 1/4 in. binder head).  Substitution
of other screws may cause problems in
making proper connections.

6.

Connect the grounding provision of the humidistat
to the branch circuit ground.

7.

Hook the two slots in the humidistat base over the
projections on the mounting plate and swing the
humidistat into place.  Push the wires back flush
into the wall box.

8.

Securely tighten the mounting plate locking screw.

O

ptional Horizontal Faceplate Installation

1.

Mount and wire the humidistat according to the
steps outlined in the 

Installation

 section.

2.

Pull the adjustment knob off the humidistat cover.

3.

Peel off the backing of the horizontal faceplate.

4.

Position the horizontal faceplate over the factory-
installed vertical faceplate.  Be sure to position the
plate straight and even over the existing plate.

5.

Firmly press the horizontal faceplate onto the
humidistat cover.

6.

Replace the adjustment knob.

W

iring Diagrams

Relay

Exhaust
Fan

Range

Kitchen

Dining Area
or Hall

120 VAC

N

L

H  C Humidistat

Manual
Fan
Switch

Figure 4:  Typical Wiring Diagram of a W43A Used to

Reduce Excessive Humidity in a Well-Constructed

Building by Manual or Automatic Control

of Exhaust Fan

Dehumidifier

Humidistat

L
H
C

120
VAC

L

N

Figure 5:  Dehumidification Control Wiring Diagram

Summary of Contents for W43A

Page 1: ...ng contacts rated to switch 1 4 hp motors It has a wide setpoint range of 0 to 70 Relative Humidity RH as well as off dial positions for humidification and dehumidification The differential of the W43A is fixed at approximately 6 RH Figure 1 W43A Humidistat with Vertical Faceplate Features and Benefits Human Hair Sensing Element Provides stable accurate measurement 1 4 hp 6A Rated Contacts Permits...

Page 2: ...uit is open and the C to L terminal controls the humidification equipment At any given setpoint the C to L circuit closes on a decrease in relative humidity and the C to H circuit closes on an increase in relative humidity The usual setting in winter is 30 to 40 RH Lower settings may be necessary in extremely cold weather to prevent condensation on windows doors etc The same setting should be used...

Page 3: ...1 27 32 0 25 6 1 59 40 4 71 120 2 34 59 3 22 82 1 20 30 1 41 36 0 80 20 Figure 2 W43A Dimensions in mm Mounting and Wiring Optional Concealed Adjustment Faceplate Adjustment Knob Mounting Plate Locking Screw Vertical Faceplate Mounting Plate Wall Box Cover Locking Screw Grounding Screw Figure 3 W43A Humidistat ...

Page 4: ... back of the humidistat See Wiring Diagrams section Note Use the terminal screws furnished 8 32 x 1 4 in binder head Substitution of other screws may cause problems in making proper connections 6 Connect the grounding provision of the humidistat to the branch circuit ground 7 Hook the two slots in the humidistat base over the projections on the mounting plate and swing the humidistat into place Pu...

Page 5: ...ures to set the high and low range stops High Range Stop 1 Set the adjustment knob to the maximum desired RH setting 2 Pull the adjustment knob off the humidistat cover 3 Loosen the bottom cover screw and remove the humidistat cover CAUTION Equipment damage hazard Avoid contact with human hair sensing element Contact with hair element can affect control accuracy and or product life 4 While holding...

Page 6: ...e bottom cover screw and remove the humidistat cover CAUTION Equipment damage hazard Avoid contact with human hair sensing element Contact with hair element can affect control accuracy and or product life 4 While holding the dial firmly in place keeping the setting in line with the calibrating mark depress the tab A and rotate it counterclockwise until it is against the stop C Depress the tab B an...

Page 7: ...ontrols Catalog Concealed Adjustment Faceplates Concealed adjustment faceplates are available on factory order at no extra cost For field changeover use the concealed faceplate kit and install directly over the faceplate on the cover See Table 3 for ordering information Table 3 Optional Accessories Item Product Code Number Concealed Adjustment Faceplate Vertical Mounting PLT333 12R Concealed Adjus...

Page 8: ...odized Aluminum Mounting Vertical or Horizontal 2 x 4 in 51 x 102 mm Wall Box Wiring Terminals Large 8 32 x 1 4 in Binder Head Screws Minimum Ambient Temperature 40 4 4 C Maximum Ambient Temperature 100 F 38 C Agency Listings UL Guide No XAPX File E6688 CSA Class No 4813 02 File LR948 Dimensions H x W x D 4 71 x 2 96 x 2 94 in 120 x 75 x 75 mm Shipping Weight 0 9 lb 0 4 kg The performance specific...

Reviews: