Table 8: Electrical data: single-phase gas heat, belt drive
ZDT03 through T05 - Without Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps
T03
(3)
208-1-60 15.4 83.9
24
2.3
17.4
None
-
-
-
39.5
50
230-1-60 15.4 83.9
24
2.3
17.4
None
-
-
-
39.5
50
T04
(4)
208-1-60 19.6
130
31
2.3
17.4
None
-
-
-
44.2
60
230-1-60 19.6
130
31
2.3
17.4
None
-
-
-
44.2
60
T05
(5)
208-1-60 24.4 144.2
38
4.4
17.4
None
-
-
-
52.3
70
230-1-60 24.4 144.2
38
4.4
17.4
None
-
-
-
52.3
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZDT03 through T05 - With Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages Amps
T03
(3)
208-1-60 15.4 83.9
24
2.3
17.4
20
None
-
-
-
49.5
60
230-1-60 15.4 83.9
24
2.3
17.4
20
None
-
-
-
49.5
60
T04
(4)
208-1-60 19.6
130
31
2.3
17.4
20
None
-
-
-
54.2
70
230-1-60 19.6
130
31
2.3
17.4
20
None
-
-
-
54.2
70
T05
(5)
208-1-60 24.4 144.2
38
4.4
17.4
20
None
-
-
-
62.3
80
230-1-60 24.4 144.2
38
4.4
17.4
20
None
-
-
-
62.3
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.