5742640-TIM-A-0419
8
Johnson Controls Ducted Systems
Figure 2: Unit 4 Point Load Weight
Figure 3: Unit 6 Point Load Weight
Figure 4: Center of Gravity
A
D
B
Front
C
A
F
C
B
Front
D
E
X
Y
LEFT
FRONT
Table 2: ZDT03 through TA6
Size
(Tons)
Weight (lbs.)
Center of
4 point Load Location (lbs.)
6 point Load Location (lbs.)
Shipping
Operating
X
Y
A
B
C
D
A
B
C
D
E
F
T03
(3)
475
470
34.5
18.25
111
80
117
162
78
62
51
74
91
114
T04
(4)
603
598
36
18.5
139
108
154
198
96
81
69
98
116
137
T05
(5)
637
632
37.5
18.2
139
117
171
204
96
85
76
111
124
140
TA6
(6)
670
665
35.5
17.75
150
114
173
228
104
86
72
111
132
160
Table 3: ZDT03 through TA6 Unit Accessory Weights
Unit Accessory
Weight (lbs.)
Shipping
Operating
Economizer
55
50
Power Exhaust
55
50
Electric Heat
1
28
28
Gas Heat
2
70
70
1. Weight given is for the maximum heater size available (30KW).
2. Weight given is for the maximum number of tube heat exchangers