5742640-TIM-A-0419
Johnson Controls Ducted Systems
17
T05
(5.0)
208-1-60
4
24.4 144.2
38
4.4
6.7
0
NONE
-
-
-
41.6
50
E05
4
1
19.2
41.6
50
E07
5.6
1
26.9
42
60
E10
8
1
38.5
56.5
60
E15
11.9
2
57.2
79.9
80
E20
15.9
2
76.4
103.9
110
E30
22.2
2
106.7
141.8
150
230-1-60
4
24.4 144.2
38
4.4
6.7
0
NONE
-
-
-
41.6
50
E05
5.3
1
22.1
41.6
50
E07
7.5
1
31.2
47.4
60
E10
10.6
1
44.2
63.6
70
E15
15.9
2
66.2
91.2
100
E20
21.2
2
88.3
118.8
125
E30
29.6
2
123.3
162.5
175
208-3-60
16
110
24.9
4.4
4.3
0
NONE
-
-
-
28.7
35
E05
4
1
11.1
28.7
35
E07
5.6
1
15.5
28.7
35
E10
8
1
22.2
33.1
40
E15
11.9
2
33
46.7
50
E20
15.9
2
44.1
60.5
70
E30
22.2
2
61.6
82.4
90
230-3-60
16
110
24.9
4.4
4.3
0
NONE
-
-
-
28.7
35
E05
5.3
1
12.7
28.7
35
E07
7.5
1
18
28.7
35
E10
10.6
1
25.5
37.2
40
E15
15.9
2
38.2
53.2
60
E20
21.2
2
51
69.1
70
E30
29.6
2
71.2
94.4
100
460-3-60
7.8
52
12.1
4.4
2.1
0
NONE
-
-
-
14.1
20
E07
6.8
1
8.2
14.1
20
E10
10.1
1
12.1
17.8
20
E15
13.6
2
16.4
23.1
25
E20
19.5
2
23.5
31.9
35
E30
28.8
2
34.6
45.9
50
575-3-60
5.7
38.9
8.9
4.4
1.9
0
NONE
-
-
-
10.8
15
E10
10.6
1
10.2
15.1
20
E15
15.9
2
15.3
21.5
25
E20
21.2
2
20.4
27.9
30
E30
30.4
2
29.3
38.9
40
TA6
(6.0)
208-3-60
19.6
136
27
4.4
4.3
None
-
-
-
33.2
45
E05
4
1
11.1
33.2
45
E07
5.6
1
15.5
33.2
45
E10
8
1
22.2
33.2
45
E15
11.9
1
33
46.6
50
E20
15.9
2
44.1
60.5
70
E30
22.2
2
61.6
82.4
90
230-3-60
19.6
136
27
4.4
4.3
None
-
-
-
33.2
45
E05
5.3
1
12.7
33.2
45
E07
7.5
1
18
33.2
45
E10
10.6
1
25.5
37.3
50
E15
15.9
1
38.2
53.1
60
E20
21.2
2
51
69.1
70
E30
29.6
2
71.2
94.4
100
460-3-60
9.4
66.1
13
2.4
2.1
None
-
-
-
16.3
25
E07
6.8
1
8.2
16.3
25
E10
10.1
1
12.1
17.8
25
E15
13.6
1
16.4
23.1
25
E20
19.5
2
23.5
32
35
E30
28.8
2
34.6
45.9
50
575-3-60
7.1
55.3
10
4.4
1.9
None
-
-
-
12.6
15
E10
10.6
1
10.2
15.1
20
E15
15.9
1
15.3
21.5
25
E20
21.2
2
20.4
27.9
30
E30
30.4
2
29.3
39
40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Electrical data for single phase gas heating units with belt drive is at the end of the electrical data section.
ZDT03 through TA6 - Without Powered Convenience Outlet (Belt Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC
FLA
FLA
FLA
Model
kW
Stages
Amps