® Networked Single Stage Thermostats Installation Instructions 

5

Use  the 

MENU

 key to:

-

access the Main User Menu or to exit the menu 
(See the 

Main User Menu

 section.)

-

access the Installer Configuration Menu or to 
exit the menu (See the 

Configuring the 

TEC22x1-3 Thermostat

 section.)

Use  the 

UP/DOWN

 arrow keys to change the 

configuration parameters and to activate a setpoint 
adjustment.

Backlit Liquid Crystal Display (LCD)

The TEC22x1-3 thermostat includes a 2-line, 
8-character backlit display. Low-level backlighting is 
present during normal operation, and it brightens when 
any user interface key is pressed. The backlight returns 
to low level when the thermostat is left unattended for 
45 seconds.

Light-Emitting Diodes (LEDs)

Three LEDs are included to indicate the fan status, call 
for heat, or call for cooling:

The 

FAN

 LED is on when the fan is on.

The 

HEAT

 LED is on when heating is on.

The 

COOL

 LED is on when cooling is on.

Programming Overview

There are three menus used to view, program, and 
configure the TEC22x1-3 thermostat.

The 

Status Display Menu

 is displayed during normal 

thermostat operation. This menu continuously scrolls 
through the following parameters:

Room Temperature

Clock (TEC2261-3 only)

System Mode

Occupancy Status – Occupied/Unoccupied/
Override

Outdoor Temperature – An outdoor air temperature 
sensor must be connected.

Applicable Alarms – The backlight lights up as an 
alarm condition is displayed.

Note:

Press the YES/SCROLL key to temporarily stop 

this menu from scrolling.

The 

Main User Menu

 is used to access and change 

the basic operating parameters of the thermostat. 
Access this menu by pressing the 

MENU

 key during 

normal thermostat operation.

The 

Installer Configuration Menu

 is used to set up 

the thermostat for application-specific operation. To 
access this menu, press and hold the 

MENU

 key for 

approximately 8 seconds.

Configuring the TEC22x1-3 Thermostat

The TEC22x1-3 thermostat comes from the factory 
with default settings for all configurable parameters. 
The default settings are shown in Table 2. To 
reconfigure the parameters via the thermostat, follow 
the steps in this section.

1.

To access the Installer Configuration Menu, press 
and hold the 

MENU

 key for approximately 8 

seconds. 

2.

Once the Installer Configuration Menu begins, 
press the 

NO

key to scroll through the parameters 

listed in Table 2. 

3.

When the desired parameter is displayed, use the 

YES

 key to choose the desired selection option. 

4.

Press the 

YES

 key and then the 

NO

 key to 

continue scrolling through the parameters.

When the thermostat is in the Installer Configuration 
Menu and left unattended for approximately 8 seconds, 
the thermostat reverts to the Status Display Menu.

To exit the Installer Configuration Menu any time, press 
the 

MENU

 key, and at the exit prompt, press the 

YES

 

key. To pass over a parameter without changing it, 
press the 

NO

 key.

For additional information on commissioning and 
configuring thermostats, adding thermostats to a 
Network Automation Engine (NAE), thermostat 
mapping, and remote themostat commanding, refer to 

TEC226x-3 and TEC220x-3 Series L

ON

W

ORKS

® 

Network Configurable Staged Thermostats Technical 
Bulletin (LIT-12011197)

.

Configuring the Thermostat’s Neuron® 
Identification

Press and hold the 

UP/DOWN

 arrow keys 

simultaneously for 5 seconds to broadcast the 
thermostat’s Neuron Identification on the L

ON

W

ORKS

 

network. 

If the cover is removed, you can see a green LED 
under the LON board flash when the thermostat 
broadcasts the Neuron ID. The Neuron ID is on a label 
on the Echelon® chip.

You cannot send the Neuron ID while in the Installer 
Configuration menu.

Summary of Contents for TEC22x1-3 LONWORKS

Page 1: ...ions Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x1 3 thermostat on a par...

Page 2: ...lly snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing...

Page 3: ...Bottom Connector MS OS Aux FIG trm_TEC22x1_3 L W Bus Terminals ON ORKS 2 3 4 5 6 7 11 12 13 14 15 16 10 Figure 6 Wiring the TEC22x1 3 Thermostat Cool 1 24 VAC Thermostat Power Heat 1 Y1 RC C RH W1 DI1...

Page 4: ...segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LONWORK...

Page 5: ...figuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x1 3 Thermostat The...

Page 6: ...ostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Input 2 De...

Page 7: ...er Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cyc...

Page 8: ...ge 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed...

Page 9: ...the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied overri...

Page 10: ...ress the YES key to change the occupied heating setpoint Press the NO key to advance to the unoccupied cooling setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to st...

Page 11: ...the desired fan mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu Selecting Schedule TEC2261 3 Only Programming the Daily Sche...

Page 12: ...for all the days of the week following the last entry for Sunday press the YES key to return to the Status Display Menu or press the NO key to start again at Monday Table 4 Programming the Daily Sched...

Page 13: ...y to copy the schedule from the previous day Press the NO key to set a different schedule If the YES key was pressed the next prompt is for Wednesday Repeat the procedure for all days of the week Afte...

Page 14: ...lacement thermostat contact the nearest Johnson Controls representative Table 7 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Ind...

Page 15: ...equipment can start Cooling setpoint is satisfied Lower the cooling setpoint Cooling lockout attained Mode is locked out based on outside air temperature Change configuration parameter C Lock to valu...

Page 16: ...to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditio...

Page 17: ...ished in U S A www johnsoncontrols com TEC22x1 3 LONWORKS Networked Single Stage Thermostats Installation Instructions 17 Controls Group 507 E Michigan Street Milwaukee WI 53202 2006 Johnson Controls...

Reviews: