® Networked Single Stage Thermostats Installation Instructions

14

5.

Press the 

UP/DOWN

 arrow keys to adjust the day. 

When the correct day is displayed, press the 

YES

 

key to store the day.

6.

Press the 

YES

 key to choose the time format or 

press the 

NO

 key to access the Main User Menu 

exit prompt.

7.

Press the 

UP/DOWN

 arrow keys to select the 

desired time format. Press the 

YES

 key to enter 

the format.

8.

Press the 

YES

 key to return to the Status Display 

Menu or press the 

NO

 key to return to the time set 

menu.

When the thermostat scrolls through the day and time, 
the new day and time should show on the display and 
no alarm or backlight should be present. If the day or 
time is incorrect, repeat the 

Setting the Day and Time

 

procedure.

Accessories

All the accessories in Table 7 include mounting 
hardware; contact the nearest Johnson Controls® 
representative to order any of these parts.

Note:

Review the technical specifications of the 

optional accessories prior to their use in an application.

Repair Information

If the TEC22x1-3 thermostat fails to operate within its 
specifications, see Table 8 for troubleshooting details 
and Table 9 for display messaging. For a replacement 
thermostat, contact the nearest Johnson Controls 
representative. 

   

 

 

   

Table 7:  Accessories (Order Separately)

Code Number

Description

SEN-600-1

Remote Indoor Air Temperature Sensor

SEN-600-4

Remote Indoor Air Temperature Sensor with Occupancy Override and LED

TE-6361M-1

1

Duct Mount Air Temperature Sensor

TE-636S-1

1

Strap-on Temperature Sensor

1.

Additional TE-636xx-x Series 10k Type II Thermistor Sensors are available; refer to the 

TE-6300 Series Temperature 

Sensors Product Bulletin (LIT-216320)

 for more details.

Table 8:  Troubleshooting Details (Part 1 of 2)

Symptom

Cause

Solution(s)

No display on the 
thermostat

Absent or incorrect 
supply voltage

1. Check power supply voltage between RC and C to be from 19-30 

VAC.

2. Check for tripped fuse or circuit breaker.

Overloaded power 
transformer

Verify that the transformer used is powerful enough (enough VAs) to 
supply all controlled devices including the thermostat.

Keyboard menu 
does not access all 
functions

Keyboard locked

1. Use the Installer Configuration menu to change the Lockout level to 0 

or 1.

2. Change the 

nciGenOpts

 Byte 27(28) lockout value to 0 or 1.

Temperature 
setpoints revert to 
original value after 
a certain time

Temporary setpoint 
active for a period of 
time set by 
parameter 
TOccTime

To do a permanent change to the setpoints, you must enter the menu 

RoomTemp Set

 and modify the setpoints at desired temperature.

Summary of Contents for TEC22x1-3 LONWORKS

Page 1: ...ions Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x1 3 thermostat on a par...

Page 2: ...lly snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing...

Page 3: ...Bottom Connector MS OS Aux FIG trm_TEC22x1_3 L W Bus Terminals ON ORKS 2 3 4 5 6 7 11 12 13 14 15 16 10 Figure 6 Wiring the TEC22x1 3 Thermostat Cool 1 24 VAC Thermostat Power Heat 1 Y1 RC C RH W1 DI1...

Page 4: ...segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LONWORK...

Page 5: ...figuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x1 3 Thermostat The...

Page 6: ...ostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Input 2 De...

Page 7: ...er Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cyc...

Page 8: ...ge 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed...

Page 9: ...the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied overri...

Page 10: ...ress the YES key to change the occupied heating setpoint Press the NO key to advance to the unoccupied cooling setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to st...

Page 11: ...the desired fan mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu Selecting Schedule TEC2261 3 Only Programming the Daily Sche...

Page 12: ...for all the days of the week following the last entry for Sunday press the YES key to return to the Status Display Menu or press the NO key to start again at Monday Table 4 Programming the Daily Sched...

Page 13: ...y to copy the schedule from the previous day Press the NO key to set a different schedule If the YES key was pressed the next prompt is for Wednesday Repeat the procedure for all days of the week Afte...

Page 14: ...lacement thermostat contact the nearest Johnson Controls representative Table 7 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Ind...

Page 15: ...equipment can start Cooling setpoint is satisfied Lower the cooling setpoint Cooling lockout attained Mode is locked out based on outside air temperature Change configuration parameter C Lock to valu...

Page 16: ...to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditio...

Page 17: ...ished in U S A www johnsoncontrols com TEC22x1 3 LONWORKS Networked Single Stage Thermostats Installation Instructions 17 Controls Group 507 E Michigan Street Milwaukee WI 53202 2006 Johnson Controls...

Reviews: