TEC22x1-3 L
ON
W
ORKS
® Networked Single Stage Thermostats Installation Instructions
10
Entering Temporary Temperature Setpoints
To temporarily change the setpoint, press the
UP/DOWN
arrow keys to change the temporary
setpoint for the current mode of operation.
Note:
Whether the thermostat is heating or cooling,
the respective setpoint is temporarily adjusted. To
toggle between the temporary heating and cooling
setpoints, press the
NO
key while changing the
temporary setpoints.
Ending Temporary Temperature Setpoints
The temporary setpoints remain in effect for the
duration set in the
TOccTime
parameter or until
manually released.
To release the temporary setpoint sooner, while in the
Main User Menu:
1.
Press the
YES
key to the first prompt that appears.
2.
If the thermostat does not immediately return to the
Status Display Menu, press the
MENU
key again
and press the
YES
key to exit the Main User Menu.
The setpoint reverts to the Permanent Temperature
Setpoint.
Press the
UP/DOWN
arrow keys to
set the temperature. Press the
YES
key to store the value and advance to
the next menu.
Press the
YES
key to change the
occupied heating setpoint. Press the
NO
key to advance to the unoccupied
cooling setpoint menu.
Press the
UP/DOWN
arrow keys to
set the temperature. Press the
YES
key to store the value and advance to
the next menu.
Press the
YES
key to change the
unoccupied cooling setpoint. Press
the
NO
key to advance to the
unoccupied heating setpoint.
Press the
UP/DOWN
arrow keys to
set the temperature. Press the
YES
key to store the value and advance to
the next menu.
Press the
YES
key to change the
unoccupied heating setpoint. Press
the
NO
key to advance to the
temperature display units.
Press the
UP/DOWN
arrow keys to
set the temperature. Press the
YES
key to store the value and advance to
the next menu.
Table 3: Entering Permanent Temperature
Setpoints (Part 2 of 3)
Thermostat
Display
Description
Cooling
75.0
°
F
Heating
set? Y/N
Heating
68.0
°
F
Unocc CL
set? Y/N
Unocc CL
80.0
°
F
Unocc HT
set? Y/N
Unocc HT
62.0
°
F
Press the
YES
key to set the display
units to °F or °C. Press the
NO
key to
advance to the temperature setpoint
type menu.
Press the
YES
key to return to the
Status Display Menu or press the
NO
key to reenter the temperature
setting menu.
Table 3: Entering Permanent Temperature
Setpoints (Part 3 of 3)
Thermostat
Display
Description
°
F/
°
C
set? Y/N
Exit?
Y/N