® Networked Single Stage Thermostats Installation Instructions 

13

Setting the Day and Time (TEC2261-3 only)

Upon initial power up (or after a power loss of greater 
than 6 hours), the thermostat shows a 

SetClock

 alarm 

on its display. As the thermostat scrolls through the 
Status Display Menu, the 

SetClock

 message causes 

the backlight to light up until the clock is set.

When changing the time, press the 

UP/DOWN

 arrow 

keys once to change the time in 1-minute increments; 
press and hold down the keys to change the time in 
30-minute increments.

To set the clock while in the Main User Menu:

1.

Press the 

NO

 key to all prompts until the clock set 

prompt appears on the display. Press the 

YES

 key 

to enter the clock set menu.

2.

Press the 

YES

 key to set the time or press the 

NO

 

key to advance to the day set menu.

3.

Press the 

UP/DOWN

 arrow keys to adjust the time. 

When the correct time is displayed, press the 

YES

 

key to store the time.

4.

Press the 

YES

 key to enter the day set menu or 

press the 

NO

 key to enter the clock format menu.

Press the 

YES

 key to copy the 

schedule from the previous day. 
Press the 

NO

 key to set a different 

schedule.

If the 

YES

 key was pressed, the next 

prompt is for Wednesday. Repeat the 
procedure for all days of the week.

After setting the schedule for all the 
days of the week, following the last 
entry for Sunday, press the 

YES

 key 

to return to the Status Display Menu 
or press the 

NO

 key to start again at 

Monday.

Table 5:  Programming the Daily Schedule – 

Four-Event (Part 2 of 2)

Thermostat 
Display

Description

Copy Y/N 
previous 

Wednesda 
set? Y/N 

Exit? 
 Y/N

 

Table 6:  Four-Event Office Schedule

Event 1

Event 2

Event 3

Event 4

Occupied

Unoccupied

Occupied 2

Unoccupied 2

Event

Cool

Heat

Cool

Heat

Cool

Heat

Cool

Heat

72°F 
(22°C)

70°F 
(21°C)

80°F 
(27°C)

62°F 
(17°C)

72°F 
(22°C)

70°F 
(21°C)

80°F 
(27°C)

62°F 

(17°C)

Monday

7:00 A.M.

5:00 P.M.

12:00 P.M.

1

 12:00 P.M.

1

Tuesday

7:00 A.M.

5:00 P.M.

12:00 P.M.

1

 12:00 P.M.

1

Wednesday

7:00 A.M.

5:00 P.M.

12:00 P.M.

1

 12:00 P.M.

1

Thursday

7:00 A.M.

5:00 P.M.

7:00 P.M.

10:30 P.M.

Friday

7:00 A.M.

5:00 P.M.

7:00 P.M.

10:30 P.M.

Saturday

12:00 P.M.

1

12:00 P.M.

1

12:00 P.M.

1

 12:00 P.M.

1

Sunday

12:00 P.M.

1

12:00 P.M.

1

12:00 P.M.

1

 12:00 P.M.

1

1.

Programming different events to the same time for that day cancels those events and leaves the thermostat in the 
unoccupied state.

Summary of Contents for TEC22x1-3 LONWORKS

Page 1: ...ions Cet appareil num rique de la Classe A respecte toutes les exigences du R glement sur le mat riel brouilleur du Canada Installation Location Considerations Locate the TEC22x1 3 thermostat on a par...

Page 2: ...lly snap it into the locking tabs on the thermostat mounting base 9 Pull the pull tabs on each of the connectors and remove the screw terminal blocks as illustrated in Figure 4 Wiring When an existing...

Page 3: ...Bottom Connector MS OS Aux FIG trm_TEC22x1_3 L W Bus Terminals ON ORKS 2 3 4 5 6 7 11 12 13 14 15 16 10 Figure 6 Wiring the TEC22x1 3 Thermostat Cool 1 24 VAC Thermostat Power Heat 1 Y1 RC C RH W1 DI1...

Page 4: ...segment a segment is a physically continuous length of wire The thermostat is not equipped with the ability to provide this termination therefore it cannot be located at the physical end of a LONWORK...

Page 5: ...figuration Menu is used to set up the thermostat for application specific operation To access this menu press and hold the MENU key for approximately 8 seconds Configuring the TEC22x1 3 Thermostat The...

Page 6: ...ostat RemNSB Remote Night Setback NSB via a time clock input an occupancy sensor or from a voltage free contact Contact open Occupied contact closed Unoccupied DI21 Configuration of Digital Input 2 De...

Page 7: ...er Heat cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cyc...

Page 8: ...ge 15 F 26 C to 120 F 49 C adjustable in 5F 5C increments C lock Discontinues cooling operation in response to the outdoor air temperature Requires that an outdoor air temperature sensor be installed...

Page 9: ...the unoccupied override mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied overri...

Page 10: ...ress the YES key to change the occupied heating setpoint Press the NO key to advance to the unoccupied cooling setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to st...

Page 11: ...the desired fan mode 3 Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu Selecting Schedule TEC2261 3 Only Programming the Daily Sche...

Page 12: ...for all the days of the week following the last entry for Sunday press the YES key to return to the Status Display Menu or press the NO key to start again at Monday Table 4 Programming the Daily Sched...

Page 13: ...y to copy the schedule from the previous day Press the NO key to set a different schedule If the YES key was pressed the next prompt is for Wednesday Repeat the procedure for all days of the week Afte...

Page 14: ...lacement thermostat contact the nearest Johnson Controls representative Table 7 Accessories Order Separately Code Number Description SEN 600 1 Remote Indoor Air Temperature Sensor SEN 600 4 Remote Ind...

Page 15: ...equipment can start Cooling setpoint is satisfied Lower the cooling setpoint Cooling lockout attained Mode is locked out based on outside air temperature Change configuration parameter C Lock to valu...

Page 16: ...to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditio...

Page 17: ...ished in U S A www johnsoncontrols com TEC22x1 3 LONWORKS Networked Single Stage Thermostats Installation Instructions 17 Controls Group 507 E Michigan Street Milwaukee WI 53202 2006 Johnson Controls...

Reviews: