background image

TEC22x6(H)-4 and TEC22x6H-4+PIR Series L

ON

W

ORKS

® Network Thermostat Controllers with

Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions

23

Table 7:  Display Messages

Display

Function

Service

Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2).

Filter

Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2).

Window

Indicates that an outside window or door is open and has cancelled the thermostat heating or 
cooling action in accordance with the programmable Binary Input (BI1).

Table 8:  Troubleshooting Details

Symptom

Cause

Solution(s)

No display on the 
thermostat

Absent or incorrect 
supply voltage

1. Check power supply voltage between RC and C to be from 19 to 30 VAC
2. Check for tripped fuse or circuit breaker

Overloaded power 
transformer

Verify that the transformer used is powerful enough (enough VAs) to supply all 
controlled devices including the thermostat

Keyboard menu 
does not access all 
functions

Keyboard locked

Change configuration parameter nviRemLockout to value 

0

 to access all 

levels of the menu.

Temperature 
setpoints revert to 
original value after 
a certain time

Temporary setpoint 
active for a period of 
time set by 
parameter TOccTime

To do a permanent change to the setpoints you must enter the 

Set type

 menu 

and change it from 

Temporar 

to 

Permnent

, then modify the setpoints to the 

desired temperature.

Thermostat does 
not call for heating

Wrong mode 
selected

Select heating mode

Thermostat in 
Unoccupied mode

Select Override to force the thermostat Occupied heating setpoint

Heating setpoint is 
satisfied

Raise the Heating setpoint

Thermostat does 
not call for cooling

Wrong mode 
selected

Select cooling mode

Thermostat in 
Unoccupied mode

Select Override to force the thermostat Occupied cooling setpoint

Cooling setpoint is 
satisfied

Lower the cooling setpoint

Digital display 
shows missing 
digits or erratic 
segments

Defective display

Replace thermostat

Reheat does not 
operate

Wrong mode 
selected

From the SeqOpera menu, set the value to 2, 3 or 5.

Heating or cooling  
does not function 
properly

Wrong reversing 
valve configuration

Note:

TEC2246-4, 

TEC2246H-4, 
TEC2246H-4+PIR, 
TEC2256-4, 
TEC2256H-4, and 
TEC2256H-4+PIR 
only

From the Rev Valve setting select either:
1. DA (Direct Acting) 0 to 100% = 0 to 10 VDC
or 
2. RA (Reverse Acting) 0 to 100% = 10 to 0 VDC

Summary of Contents for TEC2216-4

Page 1: ...e temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unconditioned areas not...

Page 2: ...right side of the thermostat mounting base and unlock the PCB Open the PCB to the left as illustrated in Figure 2 4 Pull approximately 6 in 152 mm of wire from the wall and insert the wire through the...

Page 3: ...sh any excess wire back into the wall Note Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto...

Page 4: ...2226H 4 TEC2226H 4 PIR TEC2236 4 TEC2236H 4 TEC2236H 4 PIR On Off or Floating Control TEC2246 4 TEC2246H 4 TEC2246H 4 PIR TEC2256 4 TEC2256H 4 TEC2256H 4 PIR Proportional Control 1 Fan H Fan H Fan H F...

Page 5: ...Service Alarm Voltage Free Contact Remote NSB Motion Window LON LON Supervisory Controller Twist wires together before inserting them into the terminals Thermostat to Network Connection FIG 22x6wir L...

Page 6: ...Off Control Two Pipe Applications Four Pipe Applications FIG TEC2226 H 4onoff 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 9 Wiring TEC2226 H 4 and TEC2236 H 4 Therm...

Page 7: ...ed at the physical end of a LONWORKS network segment unless a terminator is attached Refer to LONWORKS Network Layout Technical Bulletin LIT 1162150 for end of line solutions Setup and Adjustments The...

Page 8: ...models with dehumidification capability the default setting is no humidity reading on the display RH disp parameter is set to off The RH disp parameter must be set to on to display the current humidit...

Page 9: ...in Stand By mode for the 1 minute period The PIR functionality and local movement status LEDs are activated after the 1 minute warm up period has elapsed after the initial powering of the thermostat...

Page 10: ...4 TEC2xx6H 4 PIR and TEC2xx7 4 Series Thermostat Controllers Application Note LIT 12011594 Occupied Stand By Unoccupied Stand By 2 Hours Unoccupied Time 6 Hours Time Last Movement Detected by PIR Dev...

Page 11: ...Status Display Menu For additional information on commissioning and configuring thermostat controllers adding thermostat controllers to a Network Automation Engine NAE thermostat controller mapping a...

Page 12: ...ol Sequences for 4 Pipe Applications Sequence Control Curves Terminals Used See Figure 6 On Off Control Floating Control Proportional Control 0 Cooling Only See Figure 15 10 NO Cool 11 NC Cool 10 Open...

Page 13: ...Output FIG ht_on Figure 17 Cooling with Reheat Two or Four Pipe Applications Temperature Increase Increments of 1 F 0 5 C o o Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG cl_rht D...

Page 14: ...the medium setting Figure 21 This operation applies to the occupied mode when the fan is set to Auto Figure 20 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1...

Page 15: ...ime expires Window Cancels the thermostat heating or cooling action when a window is open The fan operation is only affected if the Fan Menu parameter is set to 4 On Auto and Auto is the selected fan...

Page 16: ...and Reheat applications SS Supply Air Sensor Monitoring MenuScro Gives the option of having the display continuously scroll the parameters Default on on The scroll is active off The scroll is inactiv...

Page 17: ...e selection option 0 Cooling Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only Choose the selection option 2 Cooling and Reheat when using a change...

Page 18: ...he capacity of the cooling coil St By TM Sets stand by timer value when used with occupancy sensor time delay between moment where occupancy sensor detected the last movement in the area and the time...

Page 19: ...efault 90 0 F 32 0 C Range 40 0 F 4 5 C to 90 0 F 32 0 C Cool min Sets the Occupied and Unoccupied minimum Cooling setpoint values Default 54 0 F 12 0 C Range 54 0 F 12 0 C to 100 F 37 5 C Pband Propo...

Page 20: ...ion of the Temporary Occupancy Time when the thermostat controller is in the Unoccupied mode and a Schedule Override Function is enabled using either the Main User Menu or BI1 or BI2 is configured as...

Page 21: ...mand Auto Fan Affects the auto mode of operation for the following Fan Menu parameter selection options only 2 Low Med High Auto 3 Low High Auto Default AS AS AD The fan is on Auto during occupied per...

Page 22: ...t systems 1 10 seconds six cycles per minute for various equipment with solid state relays that withstand short duty cycles such as electric heat UI3 dis Displays the supply or changeover temperature...

Page 23: ...lue 0 to access all levels of the menu Temperature setpoints revert to original value after a certain time Temporary setpoint active for a period of time set by parameter TOccTime To do a permanent ch...

Page 24: ...mistor Wire Size Unshielded Twisted Pair 22 AWG 0 6 mm Diameter Minimum 18 AWG 1 0 mm Diameter Recommended LONWORKS Network Standard 64 Devices Maximum without a Repeater 127 Devices Maximum with a Re...

Reviews: