TEC22x6(H)-4 and TEC22x6H-4+PIR Series L
ON
W
ORKS
® Network Thermostat Controllers with
Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Installation Instructions
23
Table 7: Display Messages
Display
Function
Service
Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2).
Filter
Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2).
Window
Indicates that an outside window or door is open and has cancelled the thermostat heating or
cooling action in accordance with the programmable Binary Input (BI1).
Table 8: Troubleshooting Details
Symptom
Cause
Solution(s)
No display on the
thermostat
Absent or incorrect
supply voltage
1. Check power supply voltage between RC and C to be from 19 to 30 VAC
2. Check for tripped fuse or circuit breaker
Overloaded power
transformer
Verify that the transformer used is powerful enough (enough VAs) to supply all
controlled devices including the thermostat
Keyboard menu
does not access all
functions
Keyboard locked
Change configuration parameter nviRemLockout to value
0
to access all
levels of the menu.
Temperature
setpoints revert to
original value after
a certain time
Temporary setpoint
active for a period of
time set by
parameter TOccTime
To do a permanent change to the setpoints you must enter the
Set type
menu
and change it from
Temporar
to
Permnent
, then modify the setpoints to the
desired temperature.
Thermostat does
not call for heating
Wrong mode
selected
Select heating mode
Thermostat in
Unoccupied mode
Select Override to force the thermostat Occupied heating setpoint
Heating setpoint is
satisfied
Raise the Heating setpoint
Thermostat does
not call for cooling
Wrong mode
selected
Select cooling mode
Thermostat in
Unoccupied mode
Select Override to force the thermostat Occupied cooling setpoint
Cooling setpoint is
satisfied
Lower the cooling setpoint
Digital display
shows missing
digits or erratic
segments
Defective display
Replace thermostat
Reheat does not
operate
Wrong mode
selected
From the SeqOpera menu, set the value to 2, 3 or 5.
Heating or cooling
does not function
properly
Wrong reversing
valve configuration
Note:
TEC2246-4,
TEC2246H-4,
TEC2246H-4+PIR,
TEC2256-4,
TEC2256H-4, and
TEC2256H-4+PIR
only
From the Rev Valve setting select either:
1. DA (Direct Acting) 0 to 100% = 0 to 10 VDC
or
2. RA (Reverse Acting) 0 to 100% = 10 to 0 VDC