Aux cont
Determines the auxiliary contact
function and configuration.
Default:
0
(0)
Not used,
or used for
reheat
If the Sequence of Operation is set to reheat
(2, 3, or 5), ignore this parameter.
(1)
Auxiliary
N.O.
Occupied = contact closed
Unoccupied = contact open
The output
aligns with
occupancy.
(2)
Auxiliary
N.C.
Occupied = contact open
Unoccupied = contact
closed
(3)
Auxiliary
N.O.
Occupied and fan On =
contact closed
Unoccupied and fan On or
Off = contact open
The output
aligns with
occupancy
and the
fan on
command.
(4)
Auxiliary
N.C.
Occupied and fan On =
contact open
Unoccupied and fan On or
Off = contact closed
(5)
Auxiliary On/Off control through the
auxiliary network command. The output
can be commanded through the network
for any required auxiliary functions via a
separate and dedicated network variable.
The output
aligns with
the
secondary
network
occupancy
command.
Auto Fan
Affects the auto mode of operation
for the following
Fan Menu
parameter selection options only:
•
(2):
Low-Med-High-Auto
•
(3):
Low-High-Auto
Default:
AS
(AS AD):
The fan is on Auto during occupied periods. The Med and
High speeds operate automatically on a temperature error from the
setpoint. The Low speed operates Auto on demand. When there is
no demand, the Low speed shuts down. The Low speed is only
re-activated when there is a heating or cooling demand.
(AS):
The fan is always on during occupied periods. The fan is on
Auto during unoccupied periods. The Low, Med, and High speeds
operate automatically on a temperature error from the setpoint.
FL time
Sets the maximum actuator stroke
timing.
Note:
Floating
CntrlTyp
TEC2226-4, TEC2226H-4,
TEC2226H-4+PIR, TEC2236-4,
TEC2236H-4, and
TEC2236H-4+PIR models only.
Default:
1.5 min
Range:
0.5 to 9.0 min
(adjustable in 0.5 minute increments)
Cph
Sets the maximum number of cycles
per hour.
Note:
TEC2216-4, TEC2216H-4,
TEC2216H-4+PIR, and on/off
CntrlTyp
TEC2226-4,
TEC2226H-4, TEC2226H-4+PIR,
TEC2236-4, TEC2236H-4, and
TEC2236H-4+PIR models only.
Default:
4
Range:
3 to 8
cycles per hour