Johnson Controls TEC2103-1 Installation Instructions Manual Download Page 9

 

TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions    

9

 

Enabling the Keypad Lockout (Lockout) 

The TEC2103-1 has four levels of keypad lockout. The 
levels and degree of lockout are shown in Table 3. 

To set the keypad lockout level while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the keypad lockout 

setup prompt appears in the display. Press YES to 
enter the keypad lockout menu. 

2.  Use the UP/DOWN arrow keys to locate the 

desired lockout level. Press YES to select the 
level. 

The display now shows the power delay setup prompt. 
See the

 Setting the Power-up Delay

 

(Pwr del)

 section 

for instructions. 

Table 3: Keypad Lockout Levels 

Function 

Level 0 

Level 1 

Level 2 

Occupancy 
Override

 

Yes access 

Yes access 

No access 

Temperature 
Setpoints 

Yes access 

No access 

No access 

System 
Mode Setting

 

Yes access 

Yes access 

No access 

Fan Mode 
Setting 

Yes access 

Yes access 

No access 

 

Setting the Power-up Delay (Pwr del) 

On initial power

-

up of the TEC2103-1 (or each time 

power is removed and reapplied), there is a delay 
before any operation is authorized (fan, cooling, and 
heating). The delay time is adjustable between 10 and 
120 seconds. This parameter can also be used to 
sequence the start-up of multiple units in one location. 

Note: 

When adjusting the time with the UP/DOWN 

arrow keys, holding the keys down changes the time 
by 10-second intervals. 

To set the delay time while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the power delay 

setup prompt appears in the display. Press YES to 
enter the power delay setup menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

power-up delay setting. Press YES to store the 
setting. 

The display now shows the frost protection setup 
prompt. See the

 Enabling Frost Protection (Frost pr)

 

section for instructions. 

Enabling Frost Protection (Frost pr) 

Frost protection establishes a minimum heating 
setpoint of 42

°

F (5.5

°

C) to prevent freezing in the zone 

controlled by the thermostat. If enabled, frost 
protection is activated even if the thermostat is set to 
the Off System Mode. If frost protection is active, it is 
displayed as an alarm (

Frost on

 with the backlight lit) 

on the Status Display Menu. 

To enable frost protection while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the frost protection 

setup prompt appears in the display. Press YES to 
enter the frost protection menu. 

2.  Use the UP/DOWN arrow keys to select 

off

 or 

on

Press YES to store the selection. 

The display now shows the maximum heating setpoint 
prompt. See the

 Setting the Maximum Heating 

Setpoint (Heat max)

 section for instructions. 

Setting the Maximum Heating Setpoint (Heat max) 

The maximum heating setpoint establishes the 
maximum temperature in the heating setpoint range 
that can be adjusted from the Main User Menu. The 
parameter is adjustable from 40 to 90

°

F (4.5 to 32

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

To set the maximum heating setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the maximum 

heating setpoint prompt appears in the display. 
Press YES to enter the maximum heating setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum heating setpoint temperature. Press 
YES to store the value. 

The display now shows the minimum cooling setpoint 
prompt. See the

 Setting the Minimum Cooling Setpoint 

(Cool min)

 section for instructions. 

Setting the Minimum Cooling Setpoint (Cool min) 

The minimum cooling setpoint establishes the 
minimum temperature in the cooling setpoint range 
that can be adjusted from the Main User Menu. The 
parameter is adjustable from 54 to 100

°

(12 to 37.5

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

Summary of Contents for TEC2103-1

Page 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Page 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Page 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Page 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Page 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Page 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Page 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Page 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Page 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Page 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Page 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Page 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Page 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Page 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Page 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Page 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Page 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Reviews: