Johnson Controls TEC2103-1 Installation Instructions Manual Download Page 12

 

12    

TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions 

Auxiliary Temperature/Outdoor Air Sensor 
Calibration (Cal OS) 

An offset can be added or subtracted to the actual 
displayed auxiliary/outdoor air temperature as needed. 
The range is 

±

5.0 F

°

 (

±

2.5 C

°

), adjustable in 

increments of 1 F

°

 (0.5 C

°

). 

To change the sensor calibration/offset while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the 

auxiliary/outdoor sensor calibration prompt 
appears in the display. Press YES to enter the 
auxiliary/outdoor sensor calibration menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

correction that should be applied to the sensor 
reading. Press YES to store the offset. 

The display now shows the heating stage setting 
prompt. See the

 Disable/Enable Second Heating 

Stage (H Stage)

 section for instructions. 

Disable/Enable Second Heating Stage (H Stage) 

This parameter reverts the operation of two stage 
thermostats to a single stage when the second heating 
stage is not needed. 

To enable or disable the second heating stage while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the setting heating 

stages prompt appears in the display. Press YES 
to enter the setting heating stages menu. 

2.  Using the UP/DOWN arrow keys; select 

1.0

 or 

2.0

 

stages. Press YES to store the selection. 

The display now shows the cooling stage setting 
prompt. See the

 Disable/Enable Second Cooling 

Stage (C Stage)

 section for instructions. 

Disable/Enable Second Cooling Stage (C Stage) 

This parameter reverts the operation of two-stage 
thermostats to a single stage when the second cooling 
stage is not needed. 

To enable or disable the second cooling stage while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the setting cooling 

stages prompt appears in the display. Press YES 
to enter the setting cooling stages menu. 

2.  Using the UP/DOWN arrow keys; select 

1.0

 or 

2.0

 

stages. Press YES to store the selection. 

The display now shows the heating lockout prompt. 
See the

 Setting the Heating Lockout (H lock)

 section 

for instructions. 

Setting the Heating Lockout (H lock) 

This feature disables heating operation based on 
auxiliary or outdoor air temperature (requires 
temperature sensor to be connected to the 
Auxiliary/Outdoor Air Sensor terminal OS for the 
function to be enabled). If the outdoor air temperature 
is above the heating lockout temperature, heating 
operation is disabled. 

The heating lockout temperature parameter is 
adjustable from -15 to 123

°

F (-26 to 51

°

C) in 

increments of 5 F/C

°

IMPORTANT: 

Setting the heating lockout to 

123

°

F (51

°

C) disables the heating lockout feature. 

 

If this parameter is being set at 123

°

F (51

°

C) to 

monitor discharge air temperature or temperatures 
above 122

°

F (50

°

C), note that the maximum 

temperature displayed for auxiliary temperature during 
operation is 122

°

F (50

°

C). The actual temperature 

may be above this point. 

To change the auxiliary/outdoor air temperature 
heating lockout while in the Installer Configuration 
Menu: 

1.  Answer NO to all prompts until the heating lockout 

prompt appears in the display. Press YES to enter 
the heating lockout menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the cooling lockout prompt. 
See the

 Setting the Cooling Lockout (C lock)

 section 

for instructions. 

Setting the Cooling Lockout (C lock) 

This feature disables cooling operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is below 
the cooling lockout temperature, cooling operation is 
disabled. 

The cooling lockout temperature parameter is 
adjustable from -40 to 95

°

F (-40 to 35

°

C) in 

increments of 5 F/C

°

Summary of Contents for TEC2103-1

Page 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Page 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Page 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Page 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Page 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Page 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Page 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Page 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Page 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Page 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Page 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Page 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Page 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Page 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Page 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Page 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Page 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Reviews: