Johnson Controls TEC2103-1 Installation Instructions Manual Download Page 15

 

TEC2103-1 Networked Multi-Stage Thermostat Installation Instructions    

15

 

Selecting the System Mode 

The TEC2103-1 has four system modes. 

 

Automatic Mode (auto) 

Automatic changeover between heating and 
cooling. This is the default setting. 

 

Cooling Mode (cool) 

Cooling operation only. 

 

Heating Mode (heat) 

Heating operation only. 

 

Off Mode (off) 

The TEC2103-1 is off; however, if frost protection 
is enabled and frost conditions are detected, the 
thermostat still calls for heat even if the system 
mode is set to Off. 

To set the system mode while in the Main User Menu: 
1.  Answer NO to all prompts until the system mode 

prompt appears in the display. Press YES to set 
the system mode. 

2.  Use the UP/DOWN arrow keys to locate the 

desired system mode. Press YES to select the 
desired system mode. 

3.  Press YES to return to the Status Display Menu or 

NO to return to the system mode selection menu. 

Fan Mode Setting 

The TEC2103-1 has three fan mode settings: 

 

On Fan Mode (on) 

Energizes the fan all the time for both occupied 
and unoccupied periods (even if the system mode 
is set to 

off

). 

 

Automatic Fan Mode (auto) 

Operates the fan only on a call for heating or 
cooling for both occupied and unoccupied periods. 
This is the default setting. 

 

Smart Fan Mode (smart) 

Energizes the fan all the time for occupied periods 
and only on a call for heating and cooling in 
unoccupied periods. 

To set the fan mode while in the Main User Menu: 

1.  Answer NO to all prompts until the fan mode 

prompt appears in the display. Press YES to set 
the fan mode. 

2.  Use the UP/DOWN arrow keys to locate the 

desired fan mode. Press YES to select the desired 
fan mode. 

3.  Press YES to return to the Status Display Menu or 

NO to return to the fan mode selection menu. 

Accessories 

Using the information in Table 5, contact the nearest 
Johnson Controls branch office or wholesale 
distributor to order these accessories. 

Table 5: Optional Accessories 
(Includes Mounting Hardware) 

Item Product 

Code 

Number 

Remote Indoor Temperature Sensor 

SEN-600-1 

Outdoor Air Temperature Sensor 

SEN-600-2 

Duct Mount Temperature Sensor 

SEN-600-3 

Remote Indoor Temperature Sensor 
with Occupancy Override and LED 

SEN-600-4 

 

Note: 

Review specifications of optional accessories 

prior to using in an application. 

Summary of Contents for TEC2103-1

Page 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Page 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Page 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Page 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Page 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Page 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Page 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Page 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Page 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Page 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Page 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Page 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Page 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Page 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Page 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Page 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Page 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Reviews: