background image

TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control 
Installation Instructions

8

Configuring the Wireless Mesh Network 
Settings

Use the following process to configure the wireless 
mesh network.

1.

Select a 

PAN ID

 and 

Channel

. Use these same 

values for every TEC Wireless Thermostat 
Controller (and the associated TEC20 Coordinator) 
on the same wireless mesh network. See Table 5.

2.

Select a 

Com Address

 for each TEC Wireless 

Thermostat Controller (1 to 254). This address 
must be unique to each TEC Wireless Thermostat 
Controller on the same wireless network (that is, 
unique to the 

PAN ID/Channel

 combination). See 

Table 5.

After configuring the wireless mesh network settings, 
refer to the 

TEC20xx-4 and TEC20xx-4+PIR Series 

Wireless Thermostat Controller System Technical 
Bulletin (LIT-12011596)

 for directions on integrating the 

TEC Wireless Thermostat Controllers and TEC20 
Coordinator with a supervisory controller. 

Table 5:  Installer Configuration Menu  (Part 1 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Pswrd

Sets the protective access 
password to prevent unauthorized 
access to the Installer Configuration 
Menu.
Default: 

0

Note:

The default setting does not 

lock out access to the Installer 
Configuration Menu.

Range: 

0

 to 

1,000

Com addr

Wireless address at the thermostat 
controller; Default: 

254

Range:

 000 

to 

254

Addresses of each item on the wireless bus must be uniquely 
numbered, increasing from 1.

Note:

Setting this parameter to 0 disables the function.

PAN ID

Sets the Personal Area Network 
Identification (PAN ID) of the 
wireless network. All devices on a 
network must have the same 
PAN ID setting to communicate with 
each other. Default: 

0

Range: 

0

 to 

500

Note:

Setting this parameter to 0 disables the function.

Channel

Sets the mesh network channel the 
device uses for communication. 
Only devices using the same mesh 
network channel can communicate 
with each other. Default: 

10

Range: 

11

 to 

26

Note:

Setting this parameter to 10 disables the function.

GET FROM

Parameter not available at this time.

N/A

Summary of Contents for TEC2045-4

Page 1: ...ipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful...

Page 2: ...n the Johnson Controls Portal intranet site Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Page 3: ...ntroller 1 Strip the ends of each wire 6 mm 1 4 in and connect them to the appropriate screw terminals as indicated in Figure 5 2 Carefully push any excess wire back into the wall Note Seal the hole i...

Page 4: ...11 Blank Close Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3 Figure 6 TEC2045 4 Thermostat Controller with Sep...

Page 5: ...o the Installer Configuration Menu See the Configuring the Thermostat Controller section UP DOWN arrow keys change the configuration parameters and activate a setpoint adjustment Figure 7 TEC2045 4 Th...

Page 6: ...To access the Installer Configuration Menu press and hold the OVERRIDE key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat controller dis...

Page 7: ...Cooling 1 Heating Only See Figure 10 10 Proportional Heating 2 Cooling and Reheat See Figure 11 6 and 7 Reheat 10 Proportional Cooling 3 Heating and Reheat See Figure 12 6 and 7 Reheat 10 Proportiona...

Page 8: ...ervisory controller Table 5 Installer Configuration Menu Part 1 of 6 Parameter Appearing on Display Description and Default Selection Options Pswrd Sets the protective access password to prevent unaut...

Page 9: ...or cooling outputs are enabled only when the contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Co...

Page 10: ...the display continuously scroll the parameters Default on off The scroll is inactive on The scroll is active AutoMode Enables the Auto function if Option 2 is chosen in the SeqOpera parameter to be vi...

Page 11: ...rature in 5 0F 5 0C increments St By CL Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Unoc...

Page 12: ...s the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated individually allowing the minimum configured...

Page 13: ...fan On contact open Unoccupied and fan On or Off contact closed 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxil...

Page 14: ...erature Sensor TE 636S 1 Strap Mount Temperature Sensor TEC 6 PIR3 Commercial Fan Coil Controller Cover for Occupancy Sensor TEC20 A 1 Replacement Antenna for TEC20 Coordinator TEC20 RA 14 Remote Ante...

Page 15: ...aximum 22 AWG 0 6 mm Diameter Recommended Recommended Transmission Range Through Walls 10 m 30 ft Line of Sight Open Space 30 m 100 ft RF Band Direct Sequence Spread Spectrum Transmission 2 4 GHz unli...

Reviews: