TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control

Installation Instructions

9

BI1

Configuration of Binary Input 1.
Default: 

None

(None):

 No function is associated with an input.

(Rem NSB):

 Remote Night Setback (NSB) via a time clock input, an 

occupancy sensor, or from a voltage-free contact. 
Contact open = Occupied; contact closed = Unoccupied.

(MotionNO*):

 Temporary occupancy request via a motion detector 

input. Contact open = Unoccupied. When the contact closes, the 
thermostat controller

 

enters the occupied mode for a specified 

TOccTime. Once the TOccTime begins, the thermostat controller 
remains in the occupied mode if the contact is open, until the 
TOccTime expires.

(MotionNC*):

 Temporary occupancy request via a motion detector 

input. Contact closed = Unoccupied. When the contact opens, the 
thermostat controller goes into the occupied mode for a specified 
TOccTime. Once the TOccTime begins, the thermostat controller 
remains in the occupied mode if the contact is closed, until the 
TOccTime expires.

(Window**):

 Cancels the heating or cooling action when a window 

is open. A Window alarm is displayed indicating that the window 
needs to be closed to resume heating or cooling.
* These settings disable any local override function.
**When this setting is selected, the heating and/or cooling outputs 
are enabled only when the contact is closed. If the fan is set to Auto, 
it is enabled only when the contact is closed. If the fan is set to On, it 
is not affected by this setting.

BI2

Configuration of Binary Input 2.
Default: 

None

(None):

 No function is associated with an input.

(Door Dry): 

Door contact only has an effect if BI1 is set to 

MotionNO

 or 

MotionNC

. (See the 

BI1 

parameter earlier in this 

table.) The occupancy is now dictated via BI1 and BI2. Any motion 
detected sets the zone to Occupied status. The zone remains 
permanently in occupied mode until the door contact switch opens 
momentarily. The thermostat then enters stand-by mode. If more 
movements are detected, the occupied mode resumes. Use a 
Normally Closed contact switching device. Contact opened = Door 
opened, Contact closed = Door closed.

(RemOVR):

 Temporary occupancy request by means of a remote 

input. This override function is controlled by a manual remote 
occupancy override. When enabled, this condition disables the 
override capability of the thermostat controller.

(Filter):

 A Filter alarm is displayed. This alarm can be connected to 

a differential pressure switch that monitors a filter.

(Service):

 A Service alarm is displayed on the thermostat controller 

when the input is energized. This input can be tied into the air 
conditioning unit control card, which provides an alarm should there 
be a malfunction.

Table 5:  Installer Configuration Menu  (Part 2 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC2045-4

Page 1: ...ipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful...

Page 2: ...n the Johnson Controls Portal intranet site Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Page 3: ...ntroller 1 Strip the ends of each wire 6 mm 1 4 in and connect them to the appropriate screw terminals as indicated in Figure 5 2 Carefully push any excess wire back into the wall Note Seal the hole i...

Page 4: ...11 Blank Close Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3 Figure 6 TEC2045 4 Thermostat Controller with Sep...

Page 5: ...o the Installer Configuration Menu See the Configuring the Thermostat Controller section UP DOWN arrow keys change the configuration parameters and activate a setpoint adjustment Figure 7 TEC2045 4 Th...

Page 6: ...To access the Installer Configuration Menu press and hold the OVERRIDE key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat controller dis...

Page 7: ...Cooling 1 Heating Only See Figure 10 10 Proportional Heating 2 Cooling and Reheat See Figure 11 6 and 7 Reheat 10 Proportional Cooling 3 Heating and Reheat See Figure 12 6 and 7 Reheat 10 Proportiona...

Page 8: ...ervisory controller Table 5 Installer Configuration Menu Part 1 of 6 Parameter Appearing on Display Description and Default Selection Options Pswrd Sets the protective access password to prevent unaut...

Page 9: ...or cooling outputs are enabled only when the contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Co...

Page 10: ...the display continuously scroll the parameters Default on off The scroll is inactive on The scroll is active AutoMode Enables the Auto function if Option 2 is chosen in the SeqOpera parameter to be vi...

Page 11: ...rature in 5 0F 5 0C increments St By CL Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Unoc...

Page 12: ...s the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated individually allowing the minimum configured...

Page 13: ...fan On contact open Unoccupied and fan On or Off contact closed 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxil...

Page 14: ...erature Sensor TE 636S 1 Strap Mount Temperature Sensor TEC 6 PIR3 Commercial Fan Coil Controller Cover for Occupancy Sensor TEC20 A 1 Replacement Antenna for TEC20 Coordinator TEC20 RA 14 Remote Ante...

Page 15: ...aximum 22 AWG 0 6 mm Diameter Recommended Recommended Transmission Range Through Walls 10 m 30 ft Line of Sight Open Space 30 m 100 ft RF Band Direct Sequence Spread Spectrum Transmission 2 4 GHz unli...

Reviews: