TEC2045-4 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control 
Installation Instructions

10

UI3

Configuration of Universal Input 3.
Default: 

None

(None):

 No function is associated with an input.

(COC/NH):

 Changeover Contact/Normally Heat: A dry contact input 

is used to signal seasonal hot/cold water changeover. The contact 
closes when cold water is present. Valid only for two-pipe systems.

(COC/NC):

 Changeover Contact/Normally Cool: A dry contact input 

is used to signal seasonal hot/cold water changeover. The contact 
closes when hot water is present. Valid only for two-pipe systems.

(COS):

 Changeover analog Sensor: Used for hot/cold water 

changeover switching. Valid only for two-pipe systems.

Note:

Choose the selection option 

(0): Cooling Only

 for the 

SeqOpera

 parameter to allow changeover to occur between 

Cooling Only

 and 

Heating Only

. Choose the selection option 

(2): 

Cooling and Reheat

 to allow changeover to occur between 

Cooling and Reheat

 and 

Heating and Reheat

.

(SS):

 Supply Air Sensor Monitoring

Note:

If 

UI3

 is set to 

None

COC/NH

, or 

COC/NC

, then 

UI3 Status

 

is available as a point for integration and 

Supply Temperature

 is 

not available as a point for integration. If 

UI3

 is set to 

COS

 or 

SS

then 

Supply Temperature

 is available as a point for integration and 

UI3 Status

 is not available as a point for integration.

MenuScro

Gives the option of having the 
display continuously scroll the 
parameters.
Default: 

on

(off):

 The scroll is inactive.

(on):

 The scroll is active.

AutoMode

Enables the Auto function (if 
Option 2 is chosen in the 

SeqOpera

 

parameter) to be visible within the 

MODE

 key menu. (The 

MODE

 key 

is the key at the far left of the cover.)
Default:

 on

(on):

 The Auto function is active (Off-Auto-Heat-Cool). Provides 

automatic changeover between heating and cooling.

(off):

 The auto function is inactive (Off-Heat-Cool).

C or F

Provides temperature scale options 
for display.
Default:

 °F

(°C): 

Celsius scale

(°F):

 Fahrenheit scale

Lockout

Selectable Lockout Levels for 
limiting end user keypad interaction.
Default: 

0

Lockout 
Level

Function

Mode 
Setting

Fan 
Setting

Local 
Override

Occupied 
Temperature 
Setpoints

(0)

Access

Access

Access

Access

(1)

Access

Access

No Access

Access

(2)

No Access

No Access

Access

Access

(3)

No Access

No Access

No Access

Access

(4)

No Access

No Access

Access

No Access

(5)

No Access

No Access

No Access

No Access

SeqOpera

Determines the sequence of 
operation.
Default:

 1

(0):

 Cooling Only (Off-Cool). The default is 

Cool

.

(1):

 Heating Only (Off-Heat). The default is 

Heat

.

(2):

 Cooling and Reheat (Off-Auto*-Heat-Cool). The default is 

Auto

.

(3):

 Heating and Reheat (Off-Heat). The default is 

Heat

.

* Auto can be disabled with the 

AutoMode

 parameter. When Auto is 

disabled, the default for 

(2)

 is 

Heat

.

Note:

Choose the selection option 

(0): Cooling Only

 when using a 

changeover sensor to allow changeover to occur between 

Cooling 

Only

 and 

Heating Only

.

Table 5:  Installer Configuration Menu  (Part 3 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC2045-4

Page 1: ...ipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful...

Page 2: ...n the Johnson Controls Portal intranet site Installing the Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw...

Page 3: ...ntroller 1 Strip the ends of each wire 6 mm 1 4 in and connect them to the appropriate screw terminals as indicated in Figure 5 2 Carefully push any excess wire back into the wall Note Seal the hole i...

Page 4: ...11 Blank Close Cool 12 BI1 Configurable Binary Input 1 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 Configurable Universal Input 3 Figure 6 TEC2045 4 Thermostat Controller with Sep...

Page 5: ...o the Installer Configuration Menu See the Configuring the Thermostat Controller section UP DOWN arrow keys change the configuration parameters and activate a setpoint adjustment Figure 7 TEC2045 4 Th...

Page 6: ...To access the Installer Configuration Menu press and hold the OVERRIDE key for approximately 8 seconds Note If the Password parameter is configured Password 0 appears on the thermostat controller dis...

Page 7: ...Cooling 1 Heating Only See Figure 10 10 Proportional Heating 2 Cooling and Reheat See Figure 11 6 and 7 Reheat 10 Proportional Cooling 3 Heating and Reheat See Figure 12 6 and 7 Reheat 10 Proportiona...

Page 8: ...ervisory controller Table 5 Installer Configuration Menu Part 1 of 6 Parameter Appearing on Display Description and Default Selection Options Pswrd Sets the protective access password to prevent unaut...

Page 9: ...or cooling outputs are enabled only when the contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Co...

Page 10: ...the display continuously scroll the parameters Default on off The scroll is inactive on The scroll is active AutoMode Enables the Auto function if Option 2 is chosen in the SeqOpera parameter to be vi...

Page 11: ...rature in 5 0F 5 0C increments St By CL Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Unoc...

Page 12: ...s the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated individually allowing the minimum configured...

Page 13: ...fan On contact open Unoccupied and fan On or Off contact closed 5 Auxiliary On Off control through the auxiliary network command The output can be commanded through the network for any required auxil...

Page 14: ...erature Sensor TE 636S 1 Strap Mount Temperature Sensor TEC 6 PIR3 Commercial Fan Coil Controller Cover for Occupancy Sensor TEC20 A 1 Replacement Antenna for TEC20 Coordinator TEC20 RA 14 Remote Ante...

Page 15: ...aximum 22 AWG 0 6 mm Diameter Recommended Recommended Transmission Range Through Walls 10 m 30 ft Line of Sight Open Space 30 m 100 ft RF Band Direct Sequence Spread Spectrum Transmission 2 4 GHz unli...

Reviews: