RJ SERIES INSTALLATION MANUAL
RJ Series Controls - Premier Microprocessor cont.
DIP Switch Settings
Prior to powering unit, ensure that all DIP switches on SW2 & SW3 are set properly according to the tables below.
FACTORY SETUP DIP SWITCHES (SW3)
DIP SWITCH
NUMBER
DESCRIPTION
OFF POSITION
ON POSITION
SW 3-
1
Dual Capacity/Single-Speed
Configures the control for single-speed compressor operation or dual capacity operation.
Dual Capacity
Operation
Single-Speed Operation
SW 3-
2
Zoned/Finish on Second Stage
This switch allows the unit to down stage with the thermostat when off and finish with second
stage when on. Finish on second stage reduces stage changing in reciprocating dual capac-
ity compressors.
Normal - All Other
Systems
Finish on 2nd - Unzoned Dual
Capacity E Series or Premier
2 Speed
SW 3-
3
No RPM/RPM
Configures the control to monitor the RPM output of an ECM/ECM2 blower motor. When us-
ing IntelliZone or a PSC fan motor, the control should be configured for “NO RPM” sensing.
PSC Fan/RPM
Monitoring Disabled
ECM-ECM2 Fan/RPM
Monitoring Enabled
SW 3-
4
Electric heat and ECM2
Allows backward compatibility with older P Series. In the Off position this switch allows older
electric heat board (17P501A01) and older ECM (square end) compatibility. On is for all
newer EH board (17P514A01) and ECM2 (round end).
Old EH & Old ECM
Normal
SW 3-
5
On dual capacity units this switch allows stage change: on the fly when off, and 1 minute
delay when on. A delay is required on all reciprocating dual capacity units.
RJ Series
E Series or P Series
FACTORY SETUP DIP SWITCHES (SW3)
DIP
SWITCH
NUMBER
DESCRIPTION
OFF POSITION
ON POSITION
SW 2-
1
Service Test Mode
On the control, allows field selection of “NORMAL” or “TEST” operational modes. Test mode
accelerates most timing functions 16 times to allow faster troubleshooting. Test mode also
allows viewing the “CURRENT” status of the fault inputs on the LED display.
Test Mode
Normal Speed Operation
SW 2-
2
Freeze Detection Sensing
This DIP switch allows field selection of low source water thermistor fault sensing for well
water (30°F) or antifreeze-protected (15°F) earth loops.
Loop Water Freeze
Detection 15° F
Well Water Freeze Detection
30° F
SW 2-
3
Accessory Relay
Allows field selection of the accessory relay to operate with the compressor or fan.
Acc Relay
Tracks Fan
Acc Relay
Tracks Compressor
SW 2-
4
Fan Speed Control
Allows field selection of reduced fan speed (85% of selected medium and high speed – ECM
only) for cooling in the dehumidification mode.
Dehumidification Fan
Speeds
Normal Fan Speeds
SW 2-
5
Auxiliary Off
Disables 3rd-stage Heating. Full emergency heat would still be available if needed.
Disable Heating
Stage 3
Enable Heating
Stage 3
SW 2-
6
Diagnostics Inputs
Allows viewing the inputs from the thermostat to the control board such as Y1, Y2, O, G, W,
SL1-In on the LED display.
Diagnostic Inputs
Viewed at LEDs
Normal Display
Viewed at LEDs
SW 2-
7
Diagnostics Outputs
Allows viewing the outputs from the control board such as compressor, reversing valve,
blower, hot water pump, and loop pump on the LED display.
Diagnostic Outputs
Viewed at LEDs
Normal Display
Viewed at LEDs
SW 2-
8
Thermostat Selection
Configures the control for a pulsed lockout signal (ComforTalk and FaultFlash thermostats) or
continuous 5 VAC lockout signal.
Pulsed “L” signal
Continuous “L” signal