![Johnson Controls RJ H Series Installation Operation & Maintenance Download Page 19](http://html1.mh-extra.com/html/johnson-controls/rj-h-series/rj-h-series_installation-operation-and-maintenance_2024194019.webp)
17
RJ SERIES INSTALLATION MANUAL
Electrical Connections cont.
Pump Wiring
See Figure 14 for electrical connections
from control box to pumps.
Electronic Thermostat
Position the thermostat subbase against the wall so that it is level and the thermostat wires
protrude through the middle of the subbase. Mark the position of the subbase mounting
holes and drill holes with a 3/16-inch bit. Install supplied anchors and secure base to the
wall. Thermostat wire must be 8-conductor, 18-AWG wire. Strip the wires back 1/4-inch
(longer strip lengths may cause shorts) and insert the thermostat wires into the connector
as shown. Tighten the screws to insure secure connections. The thermostat has the same
type connectors, requiring the same wiring. See instructions enclosed in the thermostat for
detailed installation and operation information.
Note:
DIP switch SW2-8 is required to be in the “OFF” position for the control to operate with
FaultFlash or ComforTalk thermostats. SW2-8 in the “ON” position configures the control to
operate with typical thermostats (continuous lockout signal). There must be a wire connecting Y2 on the microprocessor controller to 2nd
stage compressor on the thermostat for proper operation.
Figure 14: Pump Wiring 208-230/60/1
Figure 15: Thermostat Wiring
R
Y1
C
W
O
G
L
24VAC (Hot)
24VAC (Common)
Compressor (1st Stage)
Aux. Heat
Reversing Valve
Blower Relay
System Monitor
Microprocessor Controlle
r
Thermostat Connection
Y2
Compressor (2nd Stage)
L2
L1
TO PUMP
Auxiliary Heat Ratings
Model
KW
Stages
BTU/HR
Min
CFM
RJ Series Compatibility
208V
230V
208V
230V
009-012
015
018
022
026 - 030 036 - 049 060 - 072
EAS(H)4
2.9
3.8
1
9,700
12,900
250
●
EAM(H)5
3.6
4.8
1
12,300
16,300
450
●
●
●
●
EAM(H)8
5.7
7.6
2
19,400
25,900
550
●
●
●
EAM(H)10
7.2
9.6
2
24,600
32,700
650
●
EAL(H)10
7.2
9.6
2
24,600
32,700
1100
●
●
EAL(H)15
10.8
14.4
3
36,900
49,100
1250
●
●
EAL(H)15-3
10.8
14.4
3
36,900
49,100
1250
●
●
EAL(H)20
14.4
19.2
4
49,200
65,500
1500
●
"H" is used in part number for horizontal units