PG8932/PG9932 wireless heat detector
Installation and operating instructions
Read this instruction sheet thoroughly before installation and use of the PG8932/PG9932
Introduction
The PG8932/PG9932 is a wireless heat detector with a fixed temperature, a rate of rise heat
sensor, and an internal piezoelectric alarm. The detector is available in 915 and 868 MHz
versions. Only Model PG9932 operating in band 912-919MHz is UL/ ULC listed. Model
PG8932 operating in 868MHz band is CE and UKCA compliant.
Compatible devices
Model PG9932 is compatible with UL/ULC listed control panels
DSC/Tyco models: HS2128, HS2064, HS2032, HS2016,
HS3248, HS3128, HS3032 when using RF Transceiver
HSM2HOST9 or Keypads with integral transceiver
HS2LCDRF(P)9,
HS2LCDRFPRO9, HS2LCDICNRF9(P)
and Qolsys IQPanel2, IQHub, IQPanel4.
Operation
During normal operation, the green LED flashes every 12 seconds.
The detector goes into alarm when the heat level exceeds 135 ºF / 57.5 ºC and automatically
restores when the heat level falls below the threshold. The detector also goes into alarm
when the temperature rapidly increases over a short period of time. During an alarm, the
LED flashes once per second and the sounder emits the evacuation temporal pattern.
Detector trouble
If the detector has a general fault, the yellow LED blinks once every four seconds and the
detector emits a chirp every 48 seconds. After four hours, the panel displays a fire trouble
message.
Table: Detector and Status Indication
Status
LEDs
Sounder
Normal
Green flash every 12 seconds
Off
Heat Alarm Red flash every 1 second
ANSI S3.41 temporal 3
Heat Test
Red flash every 1 second
ANSI S3.41 temporal 3
Test Alarm
(button
press)
Red flash every 1 second
ANSI S3.41 temporal 3
Detector
Trouble
Yellow flash every 4 seconds
One chirp every 48 seconds
Low Battery Yellow flash every 12 seconds
One chirp every 48 seconds
(press button to hush for 12 hours)
Power-up
Red, yellow, green, flash sequence
One chirp at the end of the power-up
sequence
Tamper
Red, yellow, green flash sequence every
12 seconds
Off
Wireless transmissions
A supervisory message is transmitted at 128 s intervals. If the signal is not received, the
control panel determines that the detector is missing.
The detector transmits the following:
•
Idle (normal operation):
The detector is in normal state without any faults or
alarms.
•
Operating temperature:
32°F to 100°F (0°C to 37.8°C)
•
Heat Alarm:
Active when the detector is above 135°F (57.5°C) or the rate of
rise of temperature is above 15°F/min (8.3°C/min).
•
Tamper / Tamper Restore:
(tamper switch activated) ten-second
maximum delay on restore before transmission.
•
Low battery pre-warning:
Low battery state is sent to the panel.
•
Low Battery:
(battery voltage falls below threshold). Low Battery Trouble is
indicated on the detector by LED flash and chirp and sent to the control
panel.
•
Detector Trouble:
Troubles are transmitted at the time of occurrence (one
trouble per supervisory interval).
Summary of Contents for PG8932
Page 29: ...Rev 0 10 21 ...