![Johnson Controls P2000 Installation Manual Download Page 31](http://html.mh-extra.com/html/johnson-controls/p2000/p2000_installation-manual_2023595031.webp)
VPN/DSL Security Option
Configuration
24-10618-155 Rev. A
2-19
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2012 Johnson Controls, Inc.
N
OTE
To configure the Digi Etherlite and install the driver, refer to the
manufacturer’s instructions.
Figure 2-9: Digi One SP Converter DIP Switch Settings
Table 2-3: Digi One SP Converter DIP Switch Positions
DIP Switch
Position
1
Down/OFF
2
Down/OFF
3
Up/ON
4
Down/OFF
Installing the Digi One® SP (S321 Connection Only)
Installation of the Digi One SP is required only if connecting to an S321 controller.
The Digi One SP device enables an S321 controller to connect to the router via the
controller’s serial port.
To install the Digi One SP converter:
1. Change the DIP switch settings on the bottom of the Digi One SP converter
according to Figure 2-9 and Table 2-3.
Digi One SP Converter
(Back View)
1
2
3
4
2. Using Belden® 9773 (18 AWG, shielded, 3 twisted pair) or equivalent, wire
the pins from the S321 serial port to a DB-9F connector according and Figure
2-10 and Table 2-4.
Summary of Contents for P2000