Introduction—ASC and N2 Bus Networking and Troubleshooting Guide 31
Installing UNTs Used with Gas
Ignition Devices
Gas ignition devices for rooftop units require that you use shielded wiring
to a UNT Controller. These devices generate very high levels of electrical
noise that can interfere with N2 communication. For information about
how to install these devices in rooftop units, refer to the UNT Controller
Technical Bulletin in this manual.