38 Introduction—ASC and N2 Bus Networking and Troubleshooting Guide
The configuration shown in Figure 18 indicates how to use shielded cable
between ASCs and devices that are in two separate enclosures.
Notes:
Hard ground (HG) the N2 Bus shield within 1 inch of each enclosure.
Soft ground (SG) the N2 Bus shield within 1 inch of entering the
enclosure with a 560 pF capacitor.
UNT
LCP
AHU
Companion PC or
Panel/
LTD
N2 Bus
HG
SG
N2 Bus
N2 Bus
Metal Enclosure
HG
VAV
EXAMPLE3
Metal Enclosure
AHU
N2 Bus
HG
N2
Bus
N2
Bus
SG
SG
Tape back
shield
Figure 18: N2 Bus with Devices Divided in Two Separate
Enclosures