36 Introduction—ASC and N2 Bus Networking and Troubleshooting Guide
The configuration shown in Figure 16 indicates how to use shielded cable
between ASCs that are in separate enclosures.
Figure 16: N2 Bus with ASCs in Separate Enclosures
Sample
Installations
with Shielded
Cable
ASC
EXAMPLE1
REF
N2-
N2+
MM-CVT101-x or
Pane/ LTD Companion
Enclosure
ASC
Enclosure
REF
N2-
N2+
Enclosure
Ground within 1 inch
of enclosure's EXIT.
HG
Ground within 1 inch
of enclosure's ENTRY.
SG
Ground within 1 inch
of enclosure's ENTRY.
N2 Bus
N2 Bus
SG
HG
HG
Notes:
Hard ground (HG) the N2 Bus shield within 1 inch of each enclosure.
Soft ground (SG) the N2 Bus shield within 1 inch of entering enclosure with a 560 pF capacitor.
560 pF
REF
N2-
N2+
560 pF