background image

2    M9200 Series Electric Spring Return Actuator Product/Technical Bulletin

A

pplication Overview

IMPORTANT: This device is not designed or

intended to be used in or near
environments where explosive vapors
or gases could be present, or
environments where substances
corrosive to the device’s internal
components could be present.

M9200 actuators are designed to position air dampers
and valves in HVAC systems. Applications include:

 

positioning return air, exhaust, or outdoor air
dampers

 

controlling face and bypass dampers

 

positioning blades for variable volume fans

 

positioning valves used with an M9000-5xx Valve
Linkage

Refer to the manufacturer’s information to properly size
the damper, valve, and/or actuator.

O

peration

IMPORTANT:

All M9200 Series actuators are
designed for use only in
conjunction with operating controls.
Where an operating control failure
would result in personal injury
and/or loss of property, it is the
responsibility of the installer to add
safety devices or alarm systems
that protect against, and/or warn of,
control failure.

M9200 actuators operate on 24 VAC at 50/60 Hz
or 24 VDC. They use a DC motor with stall detection
circuitry that operates throughout the entire stroke. The
proportional and resistive actuators employ noise
filtering techniques on the control signal to eliminate
response to spurious noise.

Rotation is mechanically limited to 93° by integral
end-stops. The position of the actuator is visually
indicated from 0 to 90° on the cover. An anti-rotation
bracket prevents lateral movement of the actuator.

The damper position can be set manually with the
manual override feature in the event of a power failure.

I

nstallation

Parts Included

 M9216 

actuator

 

NPT conduit adaptor (two included for actuators
with switches or a feedback potentiometer)

 

anti-rotation bracket

 

two No. 12-24 sheet metal screws

 

5 mm manual crank

Tools Required

 

1/4 in. (7 mm) and 1/8 in. (3 mm) flat-blade
screwdrivers

 

Phillips No. 2 screwdriver

 center 

punch

 

adjustable wrench or 7 mm and 10 mm nut drivers

 needle-nose 

pliers

 

DVM or M9000-200 Commissioning Tool (for
models with zero and span potentiometers)

Summary of Contents for M9200 Series

Page 1: ... 2 to 10 VDC signal Figure 1 M9200 Series Spring Return Actuator Features and Benefits Bi directional Fail safe Spring Return Allows selectable rotation spring return direction simplifying installation Four Control Input Types Meets the needs of most applications Wide Range Resistive Input Interfaces to 3 wire resistive controllers from 100 to 10 000 ohms Zero and Span Adjustment on Proportional M...

Page 2: ...ler to add safety devices or alarm systems that protect against and or warn of control failure M9200 actuators operate on 24 VAC at 50 60 Hz or 24 VDC They use a DC motor with stall detection circuitry that operates throughout the entire stroke The proportional and resistive actuators employ noise filtering techniques on the control signal to eliminate response to spurious noise Rotation is mechan...

Page 3: ...or the Locking Clip Smooth Half of Sleeve Locking Clip Limit Stop Position Indicator Splines Tab Coupler Back of the Actuator Widest Gap in Sleeve Teeth Figure 3 Changing the Spring Return Direction 3 Insert the sleeve into the back of the actuator with the smooth half of the sleeve inserted first Note Make sure the widest gap in the sleeve teeth align with the two guide marks on the back of the a...

Page 4: ...or slot to prevent actuator binding and premature wear 1 Refer to the A Dimensions in Table 1 and Figure 5 to ensure the anti rotation bracket tab fits midway in the actuator slot Table 1 Shaft Sizes and Distances from the Anti rotation Bracket to Shaft Center Shaft Diameter 5 8 in 1 2 in 3 8 in A Dimensions 8 1 4 in 8 5 16 in 8 3 8 in See Figure 5 209 mm 211 mm 213 mm 0 U bolt with Clamp Nuts 2 A...

Page 5: ...ition and retighten the screws to a maximum of 30 lb in 3 4 N m Examples of rotation limiter adjustments For a range of 30 adjust both limiters fully up To set a rotation range of 45 adjust one rotation limiter to 30 and the other to 15 To set a range of 60 adjust one limiter to 30 and leave the other at 0 5 Reinsert the manual crank into the manual override gear 6 Repeat Steps 2 through 5 to set ...

Page 6: ... 2 3 4 5 6 Resistive Input Control Models JGA and JGC 1 2 3 4 5 6 COM CCW CW On Off Control Models BGA and BGC CW 1 2 3 24 VAC 24 VDC 1 Common 2 Power 3 Calibration Out 4 Current Input 5 Voltage Input 6 Feedback Output 100 10k ohms 0 10V 24V Terminal Block 2 CW 0 100 11 12 13 Feedback Potentiometer Models AGD 0 135 ohms AGE 0 1000 ohms NC NO NO NC 21 22 23 24 25 26 Switch S1 10 Switch S2 80 Auxili...

Page 7: ...ring diagrams in Figure 9 5 Replace the actuator cover and retighten the cover screw With the Conduit Adaptor M9000 100 included Refer to Figure 11 and proceed as follows 1 Push the plastic plug out of the conduit opening with fingertip 2 Slide the capture nut into the slot located inside of the conduit opening See Figure 11 Capture Nut Figure 11 Capture Nut 3 Insert the conduit adaptor into the c...

Page 8: ...tional Models Direction of Action Drive direction is dependent on the position of Jumper W1 and the spring return direction as shown in Table 2 To change the spring return direction see the Spring Return Direction section Table 2 Settings for Direction of Action Location of Jumper W1 Direction of Spring Return Drive Direction with a Minimum Input Signal Drive Direction with a Maximum Input Signal ...

Page 9: ...he calibration output 5 Use a 1 8 in 3 mm flat blade screwdriver to turn the zero potentiometer fully CW and the span potentiometer fully CCW 6 Apply the minimum zero point control signal required for positioning the actuator at the minimum position 7 Monitor DC calibration output To adjust the zero potentiometer turn it CCW until the voltmeter displays 0 volts or slightly less 0 1 volt 8 Adjust t...

Page 10: ...ments Edge of Switch Cam S1 Edge of Switch Cam S2 0 CCW Figure 14 Switch Cam Angle Settings Note The normally closed contact closes and the normally open contact opens See Figure 9 Terminal Block 2 Auxiliary Switches Adjusting Switch Cam S2 To change the angle of Switch Cam S2 to 70 1 Push in and turn the manual crank CW Using the 0 to 90 nodule guides rotate the coupler until the position indicat...

Page 11: ...trols CD 1300 direct mount applications DMPR KC254 Inside Frame Mounting Kit for Johnson Controls damper applications requiring the actuator within the airstream M9000 100 Conduit Adaptor Kit M9000 103 14 VA Transformer 120 24 VAC 60 Hz M9000 104 14 VA Transformer 230 24 VAC 60 Hz M9000 151 Base Mount Linkage Kit for remote inside duct floor mounting M9000 153 Crank Arm Kit for remote mounting M90...

Page 12: ... Double Throw rated at 24 VAC 1 5A inductive 3A resistive 35 VA maximum per switch Spring Return Factory Setting CCW Direction is selectable with the coupler Mechanical Output Running torque 140 lb in 16 N m Rotation Range Adjustable from 30 to 90 mechanically limited to 93 Rotation Timing 70 to 130 seconds for 0 to 140 lb in 0 to 16 N m 90 seconds nominal at 50 rated load Powered rotation is fast...

Reviews: