Johnson Controls IOM3733 Installation Instructions Manual Download Page 2

Physical features

The following figure displays the physical features

of the IOM, and the accompanying table provides a

description of the physical features and a reference

to further information where required.

Figure 1: IOM3733 physical features

Table 1: IOM3733 feature callouts and

descriptions

Callo

ut

Physical feature: description and references

1

Binary Output (BO) Terminal Block (see Table 2)

2

Mounting Clip (Three Total) (see Figure 1)

3

Device Address DIP Switch Block (see  )

4

24 VAC, Class 2 Supply Power Terminal Block (see 

Supply

Power Terminal Block

)

5

Cover Lift Tab (One of Two) (see 

Removing the expansion

module cover

)

6

Sensor Actuator (SA) Bus / Field Controller (FC) Bus

Terminal Block (see 

SA/FC bus terminal block

)

7

End-of-Line (EOL) Termination Switch (see 

Setting the

End-of-Line (EOL) switch

)

8

Binary Input (BI) Terminal Block (see Table 2)

9

LED Status Indicators

Mounting

Observe these guidelines when mounting a

controller.
• Ensure the mounting surface can support the

controller, DIN rail, and any user-supplied

enclosure.

• Mount the controller horizontally on 35 mm DIN

rail whenever possible.

• Mount the controller in the proper mounting

position.

• Mount the controller on a hard, even surface

whenever possible in wall-mount applications.

• Use shims or washers to mount the controller

securely and evenly on the mounting surface.

• Mount the controller in an area free of corrosive

vapors and observe the Ambient Conditions

requirements in 

Technical specifications

.

• Provide for sufficient space around the controller

for cable and wire connections for easy cover

removal and good ventilation through the

controller (50 mm [2 in.] minimum on the top,

bottom, and front of the controller).

• Do not mount the controller on surfaces prone to

vibration, such as duct work.

• Do not mount the controller in areas where

electromagnetic emissions from other

devices or wiring can interfere with controller

communication.

IOM3733 Input/Output Module Installation Guide

2

Summary of Contents for IOM3733

Page 1: ...e pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipmen...

Page 2: ...Observe these guidelines when mounting a controller Ensure the mounting surface can support the controller DIN rail and any user supplied enclosure Mount the controller horizontally on 35 mm DIN rail...

Page 3: ...op of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To...

Page 4: ...ortant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed inf...

Page 5: ...ock Wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wi...

Page 6: ...output cables Shielded cable is required for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs or outputs with cables less than 30 m 100 ft typically do...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded...

Page 8: ...terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements required cable type FC or SA Bus Communications COM Signal...

Page 9: ...s Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output...

Page 10: ...but do not interfere with bus operation Set a valid and unique device address on the expansion module before applying power to the expansion module on the bus To set the device addresses on Metasys e...

Page 11: ...r to the MS TP Communications Bus Technical Bulletin LIT 12011034 3 If the controller is a terminating device on the FC bus set the EOL switch to ON If the controller is not a terminating device on th...

Page 12: ...ve Accessories Table 8 Accessories Ordering Information Product Code Number Description Mobile Access Portal MAP Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify...

Page 13: ...Product Code Number Description AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 IOM3733 In...

Page 14: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module...

Page 15: ...2 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact informatio...

Page 16: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: