Setup and Adjustments

Setting the device address

Metasys

 expansion modules are master devices

on MS/TP (SA or FC) buses. Before operating an

expansion module on a bus, set a valid and unique

device address for each expansion module on

the bus. You set an expansion module's device

address by setting the positions of the switches on

the DIP switch block at the top of the expansion

module. Device addresses 4 through 127 are the

valid addresses for these expansion modules.

The following table describes the FC bus and SA

bus device addresses for Johnson Controls MS/TP

communications bus applications.

Table 6: SA/FC Bus Device Address Descriptions

Device

Address

Use on Descriptions

0

(Switch 128

Off)

Reserved for FC Bus Supervisory

Controller (not for use on

controllers or expansion modules).

1-3

(Switch 128

Off)

Reserved for peripheral devices

(not for use on controllers or

expansion modules).

4-127

(Switch 128

Off)

Used for MSTP master devices

(controllers and expansion

modules) that are hardwired to an

SA bus or FC bus.

The DIP switch block has eight switches numbered

128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1

are device address switches. Switch 128 must be set

to 

OFF

 for all hard-wired SA and FC Bus applications.

Figure 8: Device address DIP switch Block set to

address 21

Note: 

 

Metasys

 field controllers ship with switch

128 ON and the remaining address switches

off rendering the controllers wired subordinate

devices, which do not operate on MSTP buses,

but do not interfere with bus operation. Set

a valid and unique device address on the

expansion module before applying power to

the expansion module on the bus.

To set the device addresses on 

Metasys

expansion modules, complete the following

steps:

1. Set 

all

 of the switches on the address DIP

switch block (128 through 1) to OFF.

2. Set one or more of the seven address switches

(64 though 1) to ON, so that the sum of the

switch numbers set to ON equals the intended

device address, and ensure that switch 128

remains set to OFF.

Note: 

To do this, set the highest number switch

that is less than or equal to the intended device

address to ON. Then continue setting lower

numbered switches until the total equals the

intended address. For example, if the intended

device address is 21, set switches 16, 4, and 1 to

ON (16+4+1= 21) and all other switches to OFF.

3. Set a unique and sequential device address for

each of the expansion module connected on

the SA or FC bus, starting with device address 4.

Note: 

 To ensure the best bus performance, set

sequential device addresses with no gaps in the

device address range (for example, 4, 5, 6, 7, 8,

9). The controllers/expansion modules do 

not

need to be physically connected on the bus in

their numerical device address order.

4. Write each expansion module's device address

on the white label below the DIP switch block

on the expansion module's cover.

Removing the expansion module
cover

Important: 

Electrostatic discharge can damage

expansion module components. Use proper

electrostatic discharge precautions during

installation, setup, and servicing to avoid

damaging the expansion module.

IOM3733 Input/Output Module Installation Guide

10

Summary of Contents for IOM3733

Page 1: ...e pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipmen...

Page 2: ...Observe these guidelines when mounting a controller Ensure the mounting surface can support the controller DIN rail and any user supplied enclosure Mount the controller horizontally on 35 mm DIN rail...

Page 3: ...op of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To...

Page 4: ...ortant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed inf...

Page 5: ...ock Wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wi...

Page 6: ...output cables Shielded cable is required for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs or outputs with cables less than 30 m 100 ft typically do...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded...

Page 8: ...terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements required cable type FC or SA Bus Communications COM Signal...

Page 9: ...s Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output...

Page 10: ...but do not interfere with bus operation Set a valid and unique device address on the expansion module before applying power to the expansion module on the bus To set the device addresses on Metasys e...

Page 11: ...r to the MS TP Communications Bus Technical Bulletin LIT 12011034 3 If the controller is a terminating device on the FC bus set the EOL switch to ON If the controller is not a terminating device on th...

Page 12: ...ve Accessories Table 8 Accessories Ordering Information Product Code Number Description Mobile Access Portal MAP Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify...

Page 13: ...Product Code Number Description AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 IOM3733 In...

Page 14: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module...

Page 15: ...2 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact informatio...

Page 16: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: