I/O terminal blocks, ratings, and

requirements table

Table 2: IOM3733 terminal blocks, functions, ratings, requirements, and cables

Terminal block label Terminal

label

Function, ratings, requirements

Determine wire size and

maximum cable length

Binary Input - Dry Contact Maintained Mode

0.01 second minimum pulse width
Internal 16V, 10K ohm pull up

IN

n

Binary Input - Pulse Counter/Accumulator Mode

0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 16V, 10K ohm pull up

BINARY INPUT

ICOM

n

Binary Input Common

 for all Binary Input (IN) terminals

See Guideline A in Table 3.

OUT

n

Binary Output - 24 VAC Triac (External Power)

Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current

BINARY OUPUT

(External Power Source

Only)

OCOM

n

Binary Output Common

 (for OUT

n

 terminal)

See Guideline C in Table 3.

Cable length guidelines for required wire

sizes

The following table defines cable length guidelines

for the various wire sizes that may be used for

wiring low-voltage (<30 V) input and outputs

Table 3: Cable length guidelines for required wire sizes for low-voltage (<30 V) inputs and outputs

Guideline

Wire size/Gauge and type

Maximum cable length

and type

Assumptions

1.0 mm (18 AWG) stranded copper

457 m (1,500 ft) twisted

wire

0.8 mm (20 AWG) stranded copper

297 m (975 ft) twisted wire

0.6 mm (22 AWG) stranded copper

183 m (600 ft) twisted wire

A

0.5 mm (24 AWG) stranded copper

107 m (350 ft) twisted wire

100 mV maximum voltage drop
Depending on cable and the connected input

or output device, you may have to define an

offset in the setup software for the input or

output point.

1.0 mm (18 AWG) stranded copper

229 m (750 ft) twisted wire

0.8 mm (20 AWG) stranded copper

137 m (450 ft) twisted wire

0.6 mm (22 AWG) stranded copper

91 m (300 ft) twisted wire

B

0.5 mm (24 AWG) stranded copper

61 m (200 ft) twisted wire

100 mV maximum voltage drop
Depending on cable and the connected input

or output device, you may have to define an

offset in the setup software for the input or

output point.

C

See Figure 7 to select wire size/gauge.

Use stranded copper wire

See Figure 7 to determine

cable length. Use twisted

wire cable.

N/A

Maximum wire length by current and

wire size

Use the following figure to estimate the maximum

cable length relative to the wire size and the load

current (in mA) when wiring inputs and outputs.

This figure applies to low-voltage (<30 V) inputs and

outputs only.

IOM3733 Input/Output Module Installation Guide

7

Summary of Contents for IOM3733

Page 1: ...e pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipmen...

Page 2: ...Observe these guidelines when mounting a controller Ensure the mounting surface can support the controller DIN rail and any user supplied enclosure Mount the controller horizontally on 35 mm DIN rail...

Page 3: ...op of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To...

Page 4: ...ortant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed inf...

Page 5: ...ock Wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wi...

Page 6: ...output cables Shielded cable is required for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs or outputs with cables less than 30 m 100 ft typically do...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded...

Page 8: ...terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements required cable type FC or SA Bus Communications COM Signal...

Page 9: ...s Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output...

Page 10: ...but do not interfere with bus operation Set a valid and unique device address on the expansion module before applying power to the expansion module on the bus To set the device addresses on Metasys e...

Page 11: ...r to the MS TP Communications Bus Technical Bulletin LIT 12011034 3 If the controller is a terminating device on the FC bus set the EOL switch to ON If the controller is not a terminating device on th...

Page 12: ...ve Accessories Table 8 Accessories Ordering Information Product Code Number Description Mobile Access Portal MAP Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify...

Page 13: ...Product Code Number Description AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 IOM3733 In...

Page 14: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module...

Page 15: ...2 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact informatio...

Page 16: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: