Figure 7: Maximum wire length for low-voltage

Inputs and Outputs by current and wire size

Communication bus and supply power

wiring guidelines

Communications bus and supply power terminal

blocks, ratings, and requirements 

 provides

information about the functions, ratings, and

requirements for the communication bus and

supply power terminals; and guidelines for wire

sizes, cable types, and cable lengths when wiring

the controller's communication buses and 24 VAC

supply power.
In addition, observe these guidelines when wiring

an SA or FC bus and supply power:
• Run all low-voltage wiring and cables separate

from high-voltage wiring.

• All SA and FC bus cables, regardless of wire size,

should be twisted, insulated, stranded copper

wire.

• Shielded cable is strongly required for all SA and

FC bus cables.

• Refer to the 

MS/TP Communications Bus

Technical Bulletin (LIT-12011034)

 for detailed

information regarding wire size and cable length

requirements for the SA and FC buses.

Communications bus and supply power terminal blocks, ratings, and requirements

Table 4: Communications bus and supply power terminal blocks, functions, ratings, requirements, and

cables

Terminal block/Port

label

Terminal labels Function, electrical ratings/Requirements

required cable type

+
-

FC or SA Bus Communications

COM

Signal Reference (Common) for FC or SA Bus

communications

FC BUS

or

SA BUS

SHLD

or

SA PWR

SHLD on FC Bus:

 Isolated terminal (optional

shield drain connection)

SA PWR on SA Bus:

 15 VDC power lead

connection.

Note: 

The SA PWR terminal on an IOM

expansion module does not supply 15

VDC. The SA bus supervisor supplies 15

VDC to devices on the SA bus requiring

power.

FC Bus: 0.6 mm (22 AWG) stranded, 3-wire

twisted, shielded cable required.
SA Bus: 0.6 mm (22 AWG) stranded, 4-wire

(2 twisted-pairs), shielded cable required.

Note: 

On the SA Bus, the + and - wire

are one twisted pair, and the COM

and SA PWR are the second twisted

pair of wires.

HOT

24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24 VAC)

24~

COM

24 VAC Power Supply - Common

0.8 mm to 1.0 mm
(18 AWG) 2-wire

Note: 

See 

Maximum wire length by current

and wire size

 to determine wire size and cable

lengths for cables.

Note: 

The SA Bus and FC Bus wiring

recommendations in this table are for MS/

TP bus at 38,400 baud. For more information,

refer to the 

MS/TP Communications Bus Technical

Bulletin (LIT-12011034)

.

IOM3733 Input/Output Module Installation Guide

8

Summary of Contents for IOM3733

Page 1: ...e pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipmen...

Page 2: ...Observe these guidelines when mounting a controller Ensure the mounting surface can support the controller DIN rail and any user supplied enclosure Mount the controller horizontally on 35 mm DIN rail...

Page 3: ...op of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To...

Page 4: ...ortant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed inf...

Page 5: ...ock Wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wi...

Page 6: ...output cables Shielded cable is required for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs or outputs with cables less than 30 m 100 ft typically do...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded...

Page 8: ...terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements required cable type FC or SA Bus Communications COM Signal...

Page 9: ...s Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output...

Page 10: ...but do not interfere with bus operation Set a valid and unique device address on the expansion module before applying power to the expansion module on the bus To set the device addresses on Metasys e...

Page 11: ...r to the MS TP Communications Bus Technical Bulletin LIT 12011034 3 If the controller is a terminating device on the FC bus set the EOL switch to ON If the controller is not a terminating device on th...

Page 12: ...ve Accessories Table 8 Accessories Ordering Information Product Code Number Description Mobile Access Portal MAP Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify...

Page 13: ...Product Code Number Description AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 IOM3733 In...

Page 14: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module...

Page 15: ...2 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact informatio...

Page 16: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: