Johnson Controls IOM3733 Installation Instructions Manual Download Page 3

Observe these additional guidelines when mounting

a controller in a panel or enclosure:
• Mount the controller so that the enclosure walls

do not obstruct cover removal or ventilation

through the controller.

• Mount the controller so that the power

transformer and other devices do not radiate

excessive heat to the controller.

• Do not install the controller in an airtight

enclosure.

Figure 2: Controller mounting positions

Mounting features and dimensions

Figure 3: Back of controller showing extended

mounting clips, DIN rail channel, and mounting

dimensions, mm (in.)

DIN rail mount applications

Mounting the controller horizontal on 35 mm DIN

rail is the preferred mounting method. To mount a

controller on 35 mm DIN rail, complete the following

steps:

1. Securely mount a 20 cm (8 in.) or longer section

of 35 mm DIN rail horizontally and centered in

the desired space so that the controller mounts

in the horizontal position.

2. Pull the two bottom mounting clips outward

from the controller to the extended position.

3. Hang the controller on the DIN rail by the hooks

at the top of the (DIN rail) channel on the back

of the controller, and position the controller

snugly against the DIN rail.

4. Push the bottom mounting clips inward (up) to

secure the controller on the DIN rail. To remove

the controller from the DIN rail, pull the bottom

mounting clips out to the extended position

and carefully lift the controller off the DIN rail.

Wall-mount applications

To mount the controller directly on a wall or other

flat vertical surface, complete the following steps:

1. Pull the two bottom mounting clips outward

and ensure they are locked in the extended

position.

2. Mark the mounting hole locations on the wall

using the dimensions in Figure 3 and one of the

mount positions shown in Figure 2. Or hold the

controller up to the wall or surface in a proper

mount position and mark the hole locations

through the mounting clips.

3. Drill holes in the wall or surface at the marked

locations, and insert appropriate wall anchors

in the holes (if necessary).

4. Hold the controller in place, and insert the

screws through the mounting clips and into the

holes (or anchors). Carefully tighten all of the

screws.

Important: 

Do not overtighten the mounting

screws. Overtightening the screws may

damage the mounting clips.

IOM3733 Input/Output Module Installation Guide

3

Summary of Contents for IOM3733

Page 1: ...e pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipmen...

Page 2: ...Observe these guidelines when mounting a controller Ensure the mounting surface can support the controller DIN rail and any user supplied enclosure Mount the controller horizontally on 35 mm DIN rail...

Page 3: ...op of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To...

Page 4: ...ortant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed inf...

Page 5: ...ock Wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wi...

Page 6: ...output cables Shielded cable is required for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs or outputs with cables less than 30 m 100 ft typically do...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded...

Page 8: ...terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements required cable type FC or SA Bus Communications COM Signal...

Page 9: ...s Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output...

Page 10: ...but do not interfere with bus operation Set a valid and unique device address on the expansion module before applying power to the expansion module on the bus To set the device addresses on Metasys e...

Page 11: ...r to the MS TP Communications Bus Technical Bulletin LIT 12011034 3 If the controller is a terminating device on the FC bus set the EOL switch to ON If the controller is not a terminating device on th...

Page 12: ...ve Accessories Table 8 Accessories Ordering Information Product Code Number Description Mobile Access Portal MAP Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify...

Page 13: ...Product Code Number Description AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 IOM3733 In...

Page 14: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module...

Page 15: ...2 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact informatio...

Page 16: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: