Johnson Controls IOM3733 Installation Instructions Manual Download Page 5

When connecting the IOM to an SA bus, wire the bus

terminal block plugs on the expansion module and

other SA bus devices in a daisy-chain configuration

using 4-wire twisted, shielded cable as shown in

Figure 5.

Figure 5: SA bus terminal block wiring

Note: 

The SA PWR/SHLD terminal does not

supply 15 VDC. The SA PWR/SHLD terminal

is isolated and can be used to connect (daisy

chain) the 15 VDC power leads on the SA bus

(Figure 5) or the cable shields on the FC bus

(Figure 4). The SA bus supervisor (FAC, FEC, or

VMA) supplies 15 VDC to devices on the SA bus

requiring power.

Supply Power Terminal Block

The 24 VAC supply power terminal block is a gray,

removable, 3-terminal plug that fits into a board-

mounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the

transformer to the HOT and COM terminals on the

terminal plug as shown in the following figure:

Figure 6: 24 VAC Supply Power Terminal Block

Wiring

Note: 

The supply power wire colors may

be different on transformers from other

manufacturers. Refer to the transformer

manufacturer’s instructions and the project

installation drawings for wiring details.

Important: 

Connect 24 VAC supply power to

the controller and all other network devices so

that transformer phasing is uniform across the

network devices. Powering network devices

with uniform 24 VAC supply power phasing

reduces noise, interference, and ground loop

problems. The controller does not require an

earth ground connection.

Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements

Input and output wiring guidelines

The following table provides information and

guidelines about the functions, ratings, and

requirements for the controller input and

output terminals; and references guidelines for

determining proper wire sizes and cable lengths.
In addition to the wiring guidelines in the following

table, observe these guidelines when wiring

controller inputs and outputs:
• Run all low-voltage wiring and cables separate

from high-voltage wiring.

IOM3733 Input/Output Module Installation Guide

5

Summary of Contents for IOM3733

Page 1: ...e pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipmen...

Page 2: ...Observe these guidelines when mounting a controller Ensure the mounting surface can support the controller DIN rail and any user supplied enclosure Mount the controller horizontally on 35 mm DIN rail...

Page 3: ...op of the DIN rail channel on the back of the controller and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To...

Page 4: ...ortant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed inf...

Page 5: ...ock Wiring Note The supply power wire colors may be different on transformers from other manufacturers Refer to the transformer manufacturer s instructions and the project installation drawings for wi...

Page 6: ...output cables Shielded cable is required for input and output cables that are exposed to high electromagnetic or radio frequency noise Inputs or outputs with cables less than 30 m 100 ft typically do...

Page 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded...

Page 8: ...terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements required cable type FC or SA Bus Communications COM Signal...

Page 9: ...s Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output...

Page 10: ...but do not interfere with bus operation Set a valid and unique device address on the expansion module before applying power to the expansion module on the bus To set the device addresses on Metasys e...

Page 11: ...r to the MS TP Communications Bus Technical Bulletin LIT 12011034 3 If the controller is a terminating device on the FC bus set the EOL switch to ON If the controller is not a terminating device on th...

Page 12: ...ve Accessories Table 8 Accessories Ordering Information Product Code Number Description Mobile Access Portal MAP Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify...

Page 13: ...Product Code Number Description AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 IOM3733 In...

Page 14: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module...

Page 15: ...2 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact informatio...

Page 16: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: