P00877Q
71
Code
Category
Content of Abnormality
Leading Cause
31
System
Incorrect Capacity Setting of Outdoor Unit and
Indoor Unit
Incorrect Capacity Code Setting of Combination
Excessive or Insufficient Indoor Unit Total
Capacity Code
35
Incorrect Setting of Indoor Unit No.
Duplication of Indoor Unit No. in same Refrigerant Group
36
Incorrect Indoor Unit Combination
Indoor Unit is Designed for R22
38
Problem with Protective Pickup Circuit
in Outdoor Unit
Failure of Protection Detecting Device
(Incorrect Wiring of Outdoor PCB)
39
Compressor
Problem with Running Current at
Constant Speed Compressor
Overcurrent, Blown Fuse, Current Sensor Failure,
Instantaneous Power Failure, Voltage Drop,
Abnormal Power Supply
3A
Outdoor Unit
Problem with Running Outdoor Unit Capacity
Outdoor Unit Capacity > 360 MBH
3b
Incorrect Setting of Outdoor Unit Models
Combination or Voltage
Incorrect Combination between Inverter PCB
and Outdoor PCB
Communication Problem between Inverter PCB
and Outdoor PCB
Incorrect Setting of Main and Sub Unit(s)
Combination or Voltage
3d
3E
Communication Problem between Main Unit
and Sub Unit(s)
Incorrect Wiring, Disconnected Wire, Broken Wire,
PCB Failure
43
Protection
Device
Activation of Compression Ratio Decrease
Protection Device
Defective Compression (Failure of Compressor
of Inverter, Loose Power Supply Connection)
44
Activation of Low Pressure Increase Protection
Device
Overload at Cooling, High Temperature at Heating,
Expansion Valve Locking (Loose Connector)
45
Activation of High Pressure Increase Protection
Device
Overload Operation (Clogging, Short-Pass), Pipe
Clogging, Excessive Refrigerant, Inert Gas Mixing
47
Activation of Low Pressure Decrease Protection
Device (Vacuum Operation Protection)
Insufficient Refrigerant, Refrigerant Piping,
Clogging, Expansion Valve Locking at
Open Position (Loose Connector)
48
Activation of Inverter Overcurrent Protection Device
Overload Operation, Compressor Failure
51
Sensor
Problem with Inverter Current Sensor
Current Sensor Failure
53
Inverter
Inverter Error Signal Detection
Driver IC Error Signal Detection (Protection for
Overcurrent, Low Voltage, Short Circuit)
54
Abnormality of Inverter Fin Temperature
Abnormal Inverter Fin Thermistor,
Heat Exchanger Clogging, Fan Motor Failure
55
Inverter Failure
Inverter PCB Failure
57
Fan
Controller
Activation of Fan Controller Protection
Driver IC Error Signal Detection (Protection for Overcurrent,
Low Voltage, Short Circuit), Instantaneous Overcurrent
5A
Abnormality of Fan Controller Fin Temperature
Fin Thermistor Failure, Heat Exchanger Clogging,
Fan Motor Failure
5b
Activation of Overcurrent Protection
Fan Motor Failure
5C
Problem with Fan Controller Sensor
Failure of Current Sensor (Instantaneous Overcurrent,
Increase of Fin Temperature, Low Voltage,
Ground Fault, Step-Out)
EE
Compressor
Compressor Protection Alarm
(It can not be reset from Wired Controller)
This alarm code appears when the following alarms*
occurs three times within 6 hours.
*02, 07, 08, 39, 43 to 45, 47
b1
Outdoor Unit
No. Setting
Incorrect Setting of Unit and Refrigerant System
Number
There are 64 or more numbers Set for Address or
Refrigerant System.
b5
Indoor Unit
No. Setting
Incorrect Indoor Unit Connection No. Setting
There are 17 or More Non-Corresponding to H-LINK II
Units are Connected to One System.
Summary of Contents for (H,Y)VAHP072B31CW
Page 2: ......
Page 6: ......
Page 79: ......
Page 80: ...P00877Q Code No LIT 12012285 Issued March 2016 2016 Johnson Controls Inc ...