14 G
G670 Intermittent Pilot Ignition Controls Technical Bulletin
Correct
End
Correct
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Start
Does spark stay on
for more than 30 seconds
after the pilot lights?
Is 24 VAC
between Terminal 3
and ground?
Is inlet gas pressure
per manufacturer’s
specifications?
Correct
gas pressure
Replace
G670
Make sure sensor cable
and high voltage cable are
separated and not wrapped
around any pipe or accessories.
Is sensor cable
securely connected
to Terminal 4 and
flame sensor?
Connect
securely
Is main
valve wiring
securely connected to
Terminal 3 and
ground?
Replace
main valve
Is sensor
ceramic cracked?
Is cable
grounded out?
Is sensor or
sensor connector
shorted out to metal
surface?
Is there
continuity and good
insulation in the
sensor cable?
Replace
cable
Disconnect main valve
lead from Terminal 3
Disconnect sensor
cable from Terminal 4
Replace
sensor
Connect DC microammeter
between sensor cable terminal and
Terminal 4. Observe correct polarity.
See Figure 20.
Replace
G670
Is DC current
0.2 microamperes or
greater with pilot only
operation?
Check for:
- proper gas pressure
- clean pilot assembly
- tight mechanical and electrical connections
If there is not improvement, change the
flame sensor length or the orifice size and
perform any necessary turn down tests.
Connect
securely
Figure 13: Pilot Lights, but Main Burner Does Not Come On