G
G670 Intermittent Pilot Ignition Controls Technical Bulletin
13
Yes
No
Yes
No
No
Yes
Yes
No
No
Yes
Start
Is gas at pilot?
End
Is pilot valve wiring
securely connected to
Terminal 1 and
ground?
Connect
securely
Is 24 VAC present
between Terminal 1
and ground?
Replace
G670
Make sure pilot line is not
kinked or obstructed. Check
for clean orifice.
Is inlet gas pressure
per manufacturer’s
specifications?
Replace
pilot valve
Correct gas
pressure
Is pilot spark gap
0.1 in. and located in
pilot gas stream?
Correct or
replace pilot
Check for drafts. Shield
as necessary and check
for clean orifice.
!
WARNING: Explosion Hazard.
Do not use a match to
test for presence of gas.
Figure 12: Spark is Present, but Pilot Does Not Light