12 G
G670 Intermittent Pilot Ignition Controls Technical Bulletin
No
Yes
No
Yes
Yes
No
No
No
Yes
Yes
No
No
Yes
Yes
No
Yes
No
Yes
Yes
No
No
Yes
Repair
Start
Repair
End
Replace
G670
Is 24 VAC present
between Terminal 6
and ground?
Is 24 VAC present
between Terminal 1
and ground?
Turn off
supply voltage
Visually
check. Is Lead 5
connected securely
to ground?
Connect
securely
Is 24 VAC present
between Terminal 2
and ground?
Is circuit wiring
providing 24 VAC to
Terminal 2?
Are thermostat
and limit contacts
closed?
Close
contacts
Check for proper
voltage at transformer
primary and secondary
Is circuit
wiring providing 24 VAC
to Terminal 6?
Replace
cable
Is high voltage
cable in good condition
(not brittle, burnt, or
cracked)?
Turn on
supply voltage
Connect
securely
Is spark gap
0.1 in. and located in
pilot gas stream?
Is spark
electrode ceramic
cracked?
Correct or replace
pilot burner
Replace pilot
burner
Turn on
supply voltage
Operate system
several complete
cycles
Replace
G670
Is high voltage
cable connected to spark
transformer?
In some instances a
jumper is used between
Terminals 2 and 6
to power Terminal 6.
Note:
Figure 11: No Spark, and System Does Not Work