G670 Intermittent Pilot Ignition Controls Technical Bulletin
Table 1: Specifications
Ignition Type
Indirect
Ignition Source
High voltage spark, capacitive discharge
High Voltage Cable
Length
915 mm (36 in.) maximum
Flame Detection Means
Flame rectification
Flame Detection Types
Remote sensing
Minimum Flame Current
0.2 microampere
Flame Failure Response
Time
0.8 second, maximum
Spark Gap
2.5 mm (0.1 in.) nominal
Ignition Trial Time
Infinite
Power Requirements
Control:
24 VAC, 50/60 Hz, nominal
Operation Current: 0.15A n valves
Contact Rating
Main Valve:
2A continuous, 5A inrush
Pilot Valve:
2A continuous, 5A inrush
Ambient Operating and
Storage Temperature
-40 to 66
°
C (-40 to 150
°
F)
Humidity
95% RH non-condensing
Types of Gas
Natural
(Liquefied Petroleum [LP], manufactured, mixed, or
LP gas-air mixture may be used in a well vented or
outdoor application.)
Agency Listing
CSA (AGA/CGA) Certificate Number 112520-0-19
Specification Standards
ANSI Standard Z21.20
CSA C22.2-No. 199
The performance specifications are nominal and conform to acceptable industry
standards. For application at conditions beyond these specifications, consult the
local Johnson Controls office. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
The following definitions describe operating conditions.
•
Trial for Ignition
--Period during which the pilot valve and spark are
activated attempting to ignite gas at the main burner. The
trial-for-ignition period is infinite for the G670s and ends once the
pilot flame is detected or the call for heat ends.
•
Run
--The main valve remains energized and the spark is turned off
after successful ignition.
•
Flameout
--Loss of proven flame. Should a flameout occur, the main
valve closes and the spark recurs within 0.8 second.
Operating
Mode
Definitions