Materials and Special Tools Needed
You may require the following materials and tools for
installation:
•
a suitable power module, such as one of the following
types:
-
24 VAC or 24 VDC, in-line, DIN mount capable,
with grounding wire
-
120-240 VAC, in-line, DIN mount capable, with
grounding wire
-
FX-PM: external wall-mount power adapter (input
90-254 VAC, 50-60 Hz, output: 15 VDC, 1A),
where FX-PM varies by AC wall plug, for
installation locale (for example, FX-PMUS for U.S.
or Japan installation, FX-PMEU for European
installations, type C plug, or FX-PMUK for United
Kingdom installations, type B plug)
•
if using a 24 VAC power module, either one of the
following:
-
UL listed, Class 2, 24 VAC transformer, rated at
minimum of 7.5 VA to 20 VA (approximate range
of controller alone, to fully expanded unit with four
additional NDIO16 modules and other option
boards). A dedicated transformer is required.
-
24 VDC power supply, capable of supplying at
least 1 A (24 W)
•
DIN Rail: type NS35/7.5 (35 x 7.5 mm) and DIN rail
end clips. Length of DIN rail depends on the number
of optional DIN rail mounted options.
•
suitable tools and fasteners for mounting unit and
accessories.
•
#2 Phillips screwdriver: used to install and remove
any option card.
•
small flat-blade screwdriver: used for making wiring
connections to removable screw terminal plugs and
mounting and removing modules from the DIN Rail.
Safety Precautions
The following information relates to the installation and
startup of the FX30E/FX60E.
Risk of Electric Shock
. Disconnect the power supply
before making electrical connections. Contact with
components carrying hazardous voltage can cause
electric shock and may result in severe personal injury
or death.
AVERTISSEMENT: Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout
branchement électrique. Tout contact avec des
composants conducteurs de tensions dangereuses
risque d'entraîner une décharge électrique et de
provoquer des blessures graves, voire mortelles.
Important:
Use copper conductors only. Make all wiring
connections in accordance with local,
national, and regional regulations. Do not
exceed the FX30E/FX60E electrical ratings.
Important:
Do not install or use the FX30E/FX60E in
or near environments where corrosive
substances or vapor could be present.
Exposure of the FX30E/FX60E to corrosive
environments may damage the device's
internal components, and will void the
warranty.
Important:
Use this FX30E/FX60E only as an operating
control. Where failure or malfunction of the
FX30E/FX60E could lead to personal injury
or property damage to the controlled
equipment or other property, additional
precautions must be designed in the control
system. Incorporate and maintain other
devices, such as supervisory or alarm
systems or safety or limit controls, intended
to warn of or protect against failure or
malfunction of the FX30E/FX60E.
2
FX30E/FX60E Supervisory Controllers Installation Instructions