5. The station running on the FX30E/FX60E opens with
the FX Workbench application, which has a
Navigation Tree on the left and a Display Window on
the right. In the Navigation Tree, open the
Administration folder. Double-click the TCP IP
Configuration option.
6. On the TCP/IP Configuration screen, make sure the
Interfaces field is expanded so that the IP Address
and Subnet Mask fields appear. Modify the Gateway,
IP Address and Subnet Mask fields, and click Save.
When prompted to Reboot Now, click Yes. Give the
FX30E/FX60E a couple of minutes to reboot and
restart the station that is installed.
Note:
If the following message appears, just click
OK. The changes are saved anyway.
Platform Daemon Credentials
An FX30E/FX60E Series controller is shipped with the
following Platform Daemon (Administrator) credentials:
User Name:
jci
Password:
explorer
Initially, you use these default credentials to open a
platform connection (log in) to the FX30E/FX60E. Like
the factory-assigned IP address, default credentials are
intended to be temporary. Change these credentials to
be something unique, and
guard them closely
.
1. Start the FX Workbench application.
2. On the File Menu, click Open Remote Station. When
prompted, enter the Remote Site Address (for
example, 192.168.1.149), Remote Username (
jci
),
and Remote Password (
explorer
). Click OK. When
the Authentication dialog box appears, enter the
Username (
admin
), leave the password field empty,
and click OK.
3. On the Tools menu, click Change Remote Platform
Login Credentials. In the Change Remote Login
Credentials dialog box, fill in the Username,
Password, and Confirm Password fields, then click
OK. The next time you log into the FX30E/FX60E,
use these new credentials.
Restoring a Backed Up Station
If the FX30E/FX60E ever gets into an erroneous condition
where you cannot fix a station, you can restore a
previously backed up station by using the Restore Backed
Up Station menu item under the Tools menu.
1. Run the FX Workbench application.
2. On the File Menu, click Open Remote Station. When
prompted, enter the Remote Site Address (for
example, 192.168.1.149), Remote Platform User
Name (
jci
), and Remote Password (
explorer
). Click
OK. When the Authentication dialog box appears,
enter the Station User Name (
admin
), Password
(optional), and click OK.
3. On the Tools menu, click Restore Backed Up Station.
In the Restore Backed Up Station dialog box, enter
the Remote Site IP Address, Remote Username,
Remote Password, and select the .dist (station
backup) file. Click OK. The FX30E/FX60E reboots
automatically.
Note:
You can back up a station by using the Backup
Station menu item from the station node's
popup menu in the Navigation Tree. We
recommend that you back up a station daily
to minimize the chance of information loss.
Cleaning
If dust or metal filings are present inside the unit, clean
with vacuum or compressed air. Otherwise, no cleaning
inside the unit is required. Optionally, if the outer
enclosure becomes dirty, you can wipe it with a damp
cloth and mild detergent.
NiMH Required Battery
Installation Maintenance
Installing or Replacing the Optional
NiMH Battery
The optional NiMH battery pack is sold as an assembly.
The NiMH battery is a custom battery pack with an
attached cable and connector plug, mounted on a bracket.
To install (or replace) the battery, you must remove power
to the controller and remove its cover. Then you mount
the battery assembly on top of the option card area.
22
FX30E/FX60E Supervisory Controllers Installation Instructions