background image

5. The station running on the FX30E/FX60E opens with

the FX Workbench application, which has a
Navigation Tree on the left and a Display Window on
the right. In the Navigation Tree, open the
Administration folder. Double-click the TCP IP
Configuration option.

6. On the TCP/IP Configuration screen, make sure the

Interfaces field is expanded so that the IP Address
and Subnet Mask fields appear. Modify the Gateway,
IP Address and Subnet Mask fields, and click Save.
When prompted to Reboot Now, click Yes. Give the
FX30E/FX60E a couple of minutes to reboot and
restart the station that is installed.

Note:

If the following message appears, just click
OK. The changes are saved anyway.

Platform Daemon Credentials

An FX30E/FX60E Series controller is shipped with the
following Platform Daemon (Administrator) credentials:

User Name:

jci

Password:

explorer

Initially, you use these default credentials to open a
platform connection (log in) to the FX30E/FX60E. Like
the factory-assigned IP address, default credentials are
intended to be temporary. Change these credentials to
be something unique, and

guard them closely

.

1. Start the FX Workbench application.

2. On the File Menu, click Open Remote Station. When

prompted, enter the Remote Site Address (for
example, 192.168.1.149), Remote Username (

jci

),

and Remote Password (

explorer

). Click OK. When

the Authentication dialog box appears, enter the
Username (

admin

), leave the password field empty,

and click OK.

3. On the Tools menu, click Change Remote Platform

Login Credentials. In the Change Remote Login
Credentials dialog box, fill in the Username,
Password, and Confirm Password fields, then click
OK. The next time you log into the FX30E/FX60E,
use these new credentials.

Restoring a Backed Up Station

If the FX30E/FX60E ever gets into an erroneous condition
where you cannot fix a station, you can restore a
previously backed up station by using the Restore Backed
Up Station menu item under the Tools menu.

1. Run the FX Workbench application.

2. On the File Menu, click Open Remote Station. When

prompted, enter the Remote Site Address (for
example, 192.168.1.149), Remote Platform User
Name (

jci

), and Remote Password (

explorer

). Click

OK. When the Authentication dialog box appears,
enter the Station User Name (

admin

), Password

(optional), and click OK.

3. On the Tools menu, click Restore Backed Up Station.

In the Restore Backed Up Station dialog box, enter
the Remote Site IP Address, Remote Username,
Remote Password, and select the .dist (station
backup) file. Click OK. The FX30E/FX60E reboots
automatically.

Note:

You can back up a station by using the Backup
Station menu item from the station node's
popup menu in the Navigation Tree. We
recommend that you back up a station daily
to minimize the chance of information loss.

Cleaning

If dust or metal filings are present inside the unit, clean
with vacuum or compressed air. Otherwise, no cleaning
inside the unit is required. Optionally, if the outer
enclosure becomes dirty, you can wipe it with a damp
cloth and mild detergent.

NiMH Required Battery
Installation Maintenance

Installing or Replacing the Optional
NiMH Battery

The optional NiMH battery pack is sold as an assembly.
The NiMH battery is a custom battery pack with an
attached cable and connector plug, mounted on a bracket.
To install (or replace) the battery, you must remove power
to the controller and remove its cover. Then you mount
the battery assembly on top of the option card area.

22

FX30E/FX60E Supervisory Controllers Installation Instructions

Summary of Contents for FX30E

Page 1: ... which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada Installation Parts Included Unpack the FX30E FX60E and accessories pow...

Page 2: ...il Safety Precautions The following information relates to the installation and startup of the FX30E FX60E Risk of Electric Shock Disconnect the power supply before making electrical connections Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death AVERTISSEMENT Risque de décharge électrique Débrancher l alimentation avant de ...

Page 3: ...t circuit ou connectés de façon incorrecte risquent d endommager irrémédiablement l équipement Each accessory module has a DIN mount base and typically provides two 20 pin connectors that allow you to chain multiple accessories see DIN Rail Mounting Instructions Table 1 lists the currently available modules Accessory Module Details Table 1 Accessory Module Details Notes Description Model Install o...

Page 4: ...d to remove the cover before mounting Mount the FX30E FX60E in any orientation Mount the unit on a 35 mm wide DIN rail recommended The FX30E FX60E unit base and its accessories have molded DIN rail slots and locking clips Mounting these components on a DIN rail ensures accurate alignment of connectors between all modules If DIN rail mounting is impractical use screws in mounting tabs on the FX30E ...

Page 5: ...Figure 2 Tab Mounting Dimension in mm 5 FX30E FX60E Supervisory Controllers Installation Instructions ...

Page 6: ...Figure 3 DIN Rail Mounting Figure 4 Using End Clips to Secure Modules 6 FX30E FX60E Supervisory Controllers Installation Instructions ...

Page 7: ...o the base with four plastic tabs two on each end To remove the cover press in the four tabs on both ends of the unit and lift off the cover Note If accessory modules are plugged into the FX30E FX60E you may need to slide them away from the unit to get to the cover tabs To replace the cover position it so the cutout area for the communication ports is correct then push inward to snap in place Figu...

Page 8: ... ships with onboard static RAM SRAM that can provide station backup during power loss and also has two open option card slots for a variety of available option cards Note An optional NiMH battery pack is included but not connected For connection instructions see Backup Configurations Figure 7 FX30E FX60E Board Layout Details 8 FX30E FX60E Supervisory Controllers Installation Instructions ...

Page 9: ...to the connector properly with its pins properly aligned Option cards typically provide additional communication capabilities such as those listed in Table 2 For a list of supported COM port and slot assignments for the option cards see Table 3 Table 2 Option Card Details Number of Option Cards Allowed per Controller Description Model One or two LONWORKS FTT 10A adapter with a 2 position removable...

Page 10: ...N1 COM2 COM1 GPRS COM3 COM4 LON LON1 COM2 Disabled None Wireless TEC COM1 COM2 Disabled RS 232 COM3 Wireless TEC COM1 COM2 Disabled RS 485 COM3 COM4 Wireless TEC COM1 COM2 Disabled LON LON1 Wireless TEC COM1 COM2 Disabled Sedona COM3 Wireless TEC COM1 COM2 Disabled GPRS COM3 COM4 Wireless TEC COM1 COM2 COM1 None Sedona COM3 COM2 COM1 RS 232 COM4 Sedona COM3 COM2 COM1 RS 485 COM4 COM5 Sedona COM3 C...

Page 11: ...hat shipped with the option card 2 Connect the supplied earth grounding wires with spade connector from the earth ground lug on the FX30E FX60E and any accessory modules if used to a nearby earth grounding point See Grounding for details 3 Prepare power wiring leave the unit powered off See Power Wiring for details 4 Connect communications cables See Communications Wiring for ports available on th...

Page 12: ...d Wiring LP FXPM24 0 Power Module The LP FXPM24 0 module lets you power the FX30E FX60E and if installed the NDIO16 modules from a dedicated Class 2 24 VAC transformer or from a 24 VDC power supply If installing NDIO16 modules install the power module as the last end module in the chain See Figure 5 Important If powering from a 24 VAC transformer do not power any other equipment with it Otherwise ...

Page 13: ...Figure 8 LP FXPM Power Module Wiring Connections 13 FX30E FX60E Supervisory Controllers Installation Instructions ...

Page 14: ...h components carrying hazardous voltage can cause electric shock and may result in personal injury or death AVERTISSEMENT Risque de décharge électrique Débrancher l alimentation avant de réaliser tout branchement électrique Tout contact avec des composants conducteurs de tensions dangereuses risque d entraîner une décharge électrique et de provoquer des blessures graves voire mortelles Note The 6 ...

Page 15: ...rrecte risquent d endommager irrémédiablement l équipement Communication Wiring Connect communications wiring to the ports on the bottom of the FX30E FX60E Note Prior to connecting cables provide strain relief for them to prevent damage to the controller Figure 10 FX30E FX60E Bottom Side Cover Removed Ethernet Port Two female 10 100 Mbit Ethernet connections are provided on the FX30E FX60E These c...

Page 16: ...t to send RTS 8 Clear to send CTS 9 Not used on the FX30E FX60E RS 485 Port An RS 485 non isolated port uses a 3 position screw terminal connector and always operates as COM2 Use shielded 18 22 AWG wire for this connector refer to the Telecommunications Industry Association Electronic Industries Alliance TIA EIA 485 standard As shown in Table 4 the screw terminals from left to right are shield plu...

Page 17: ...h components carrying hazardous voltage can cause electric shock and may result in personal injury or death AVERTISSEMENT Risque de décharge électrique Débrancher l alimentation avant de réaliser tout branchement électrique Tout contact avec des composants conducteurs de tensions dangereuses risque d entraîner une décharge électrique et de provoquer des blessures graves voire mortelles If the cont...

Page 18: ... 485 port with 2 pin shorting blocks installed on one pin each 2 To add biasing remove and replace both shorting blocks back onto the jumper pins Reassembling the Controller 1 Carefully replace the processor module board onto the 50 pin connector with its corner mounting holes aligned on the four lower standoffs Press down on the connector to fully seat the board 2 Refasten the four metal hex stan...

Page 19: ...backup protection This configuration allows the FX30E FX60E to handle brief power outages while also protecting against a weak or aged battery SRAM The FX30E FX60E includes an on board SRAM and associated circuitry allowing battery less operation A separate SRAM option card is not needed or supported in an FX30E FX60E controller The default station backup configuration is to use SRAM via the platf...

Page 20: ...he FX30E FX60E boots the yellow BEAT heartbeat LED begins to blink with a typical rate of about one blink per second Blinking should begin within 30 seconds after power is applied If after applying power the STATUS LED goes out or the BEAT LED comes on steady and stays lit for longer than 2 minutes contact your technical support representative for assistance See also Using Status LEDs Using Status...

Page 21: ...ing Wizard or Software Manager in the Platform view If you are changing login credentials use the Change Remote Login Credentials menu item Preparing for Setup Providing Power and Connectivity Perform the initial startup of an FX30E FX60E in your office before physically mounting it in place at a job site After you complete the commissioning process mount and wire the FX30E FX60E at the job site m...

Page 22: ...e you log into the FX30E FX60E use these new credentials Restoring a Backed Up Station If the FX30E FX60E ever gets into an erroneous condition where you cannot fix a station you can restore a previously backed up station by using the Restore Backed Up Station menu item under the Tools menu 1 Run the FX Workbench application 2 On the File Menu click Open Remote Station When prompted enter the Remo...

Page 23: ...mbly is already mounted unplug the battery from the connector on the controller board See Figure 13 6 Remove the four screws that secure both option slot end plates and if installed the existing battery assembly bracket Set the screws aside Remove any existing battery assembly if applicable 7 Plug the battery connector plug of the new battery assembly into the battery connector on the controller S...

Page 24: ...N modem and I O connectors from the FX30E FX60E 5 Unplug the earth ground wire 6 If an NDIO accessory module is installed If DIN rail mounting with DIN end clips were used you may be able to remove the DIN rail a end clip that secures the FX30E FX60E end of the assembly and then slide the FX30E FX60E away from the rest of the assembly Then remove the FX30E FX60E from the DIN rail see Figure 3 leav...

Page 25: ...he saved station database Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Johnson Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2015 Johnson Controls Inc www johnsoncontrols com Published in U S A 25 FX30E FX60E Supervisory Controllers Installation Instructions ...