Binary Output (BO) source power selection
jumpers
CAUTION
Risk of Electric Shock
Disconnect supply power to the field controller before
attempting to adjust the Binary Output Source Power
Selection Jumpers. Failure to disconnect the supply
power may result in electric shock.
ATTENTION
Mise En Garde: Risque de décharge électrique
Débrancher l'alimentation de l'controller avant tout
réglage du Binary Output Source Power Selection
Jumpers. Le non-respect de cette précaution risque
de provoquer une décharge électrique.
Important:
Do
not
connect an external power
source to a BO when the BO power source jumper
is in the internal power (INT) position. Connecting
external power to a BO that sources internal power
can damage the controller and void any warranties.
The BO source power selection jumpers determine
whether a BO provides internal power (sourced from
the field controller) to the output load (INT position) or
requires an external power source (EXT position) for the
output load. Figure 12 shows an example of a controller
BOs and the associated power selection jumpers to the
right of the BOs terminal block.
Figure 12: Example binary Outputs and the associated
source power jumper positions
UI current loop jumpers
The UI current loop fail-safe jumpers are on the circuit
board under the controller cover near the UI terminals.
When a UI is defined (in the system software) as a 4-20
mA Analog Input and the UI’s current loop jumper is
in the Disabled (default) position (Figure 13), the 4-20
mA current loop circuit opens whenever power to the
controller is interrupted or off.
Figure 13: Current loop jumper positions
Setting the current loop jumper to the Enabled position
(Figure 13) connects an internal 100 ohm resistor
across the UI terminals, which maintains the 4-20 mA
current loop circuit even when power to the controller is
interrupted or off.
Important:
Current Loop jumpers must be in the
Disabled (default) position for all UIs that are not set
up to operate as 4-20 mA analog inputs.
FAC2611 current loop jumper ID table
Table 7 identifies the current loop switches associated
with each UI on the FAC2611 controller.
Table 7: FAC2611 UI Inputs and jumper labels
Universal Input
Label
Switch Label on Current Loop DIP Switch
Block Board
IN1
J20
IN2
J21
IN3
J22
IN4
J23
IN5
J24
IN6
J25
Setting up a local display
FAC2611 models do not have an integral display, but
can be connected to a DIS1710 Local Controller Display.
For detailed information on setting up and operating
either an integral user interface or a remotely connected
DIS1710 display, refer to the
DIS1710 Local Controller
Display Technical Bulletin (LIT-12011270)
.
Commissioning Field controllers
You commission controllers with the CCT software, either
via a Bluetooth
®
Wireless Commissioning Converter, a
ZFR wireless dongle, MAP 4.2+/ BACnet Router (Mobile
Access Portal (MAP) Gateway at version 4.2 or above), or
in passthrough mode when connected to an NAE or NCE.
FAC2611 Advanced Application Field Equipment Controller Installation Guide