Table  2: FAC2611 terminal blocks, functions, ratings, requirements, and cables

Terminal block label Terminal

label

Function, ratings, requirements

Determine wire size and

maximum cable length

Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1,000 ohm or more.

Note: 

The Analog Output (AO) operates in the Voltage

Mode when connected to devices with impedances

greater than 1,000 ohm. Devices that drop below 1,000

ohm may not operate as intended for Voltage Mode

applications.

OUT

n

Analog Output - Current Mode (4–20 mA)

Requires an external load between 0 and 300 ohm.

Note: 

The Analog Output (AO) operates in the Current

Mode when connected to devices with impedances less

than 300 ohm. Devices with impedances greater than

300 may not operate as intended for Current Mode

applications.

ANALOG

(Outputs)

OCOM

n

Analog Output Signal Common

 for all Analog OUT terminals.

Note: 

All Analog Output Common terminals (OCOM

n

)

share a common, which is isolated from all other

commons.

See Guideline 

C

 in Table 3.

OUT

n

Binary Output - 24 VAC Triac 

(External Power Source)

Connects OUT

to OCOM

n

 when activated.

External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220BGx-3
40 mA minimum load current

BINARY

(Output)
Power Selection Jumper

positioned to External

(

EXT

) power.

OCOM

n

Binary Output Common

 (for OUT

n

 terminal)

Note: 

Each Binary Output Common terminal (OCOM

n

) is

isolated from 

all

 other commons, including other Binary

Output Common terminals.

See Guideline 

C

 in Table 3.

OUT

n

Binary Output - 24 VAC Triac 

(Internal Power Source)

Sources internal 24VAC power (24~ HOT).

BINARY

(Output)
Power Selection Jumper

positioned to Internal

(

INT

) power.

OCOM

n

Binary Output - 24 VAC Triac 

(Internal Power Source)

Connects OCOM

n

 to 24~ when activated.

Internal Power Source:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles/hour with M9220BGx-3
40 mA minimum load current

See Guideline 

C

 in Table 3.

FAC2611 Advanced Application Field Equipment Controller Installation Guide

8

Summary of Contents for FAC2611

Page 1: ...s and characteristics of the FEC Family Controllers must be programmed with CCT support SA Bus devices support WRZ wireless sensors from the controller using the WRZ 7860 receiver most models are available in Buy American versions most models are listed for UL 864 UUKL ORD C100 13 UUKLC 10th Edition Smoke Control some models N2 is now supported as part of the Metasys 10th Edition listing for Smoke...

Page 2: ... Binary Input BI Terminal Block Dry Contact Maintained or Pulse Counter Accumulator Mode see Table 2 12 Universal Inputs UI Terminal Block Can be defined as Voltage Analog Input 0 10 VDC Current Analog Input 4 20 mA Resistive Analog Inputs 0 600k ohm or Dry Contact Binary Input see Table 2 Table 1 FAC2611 physical features Physical feature description and references 13 End of Line EOL Switch locat...

Page 3: ...DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remove the controller from the DIN rail pull the bot tom mounting clips out to the extended position and care fully lift the controller off the DIN rail Wall mount applications To mount a field controller directly on a wall or other flat vertical surface 1 Pull the two bottom mounting clips outward and ...

Page 4: ...bus ports See Figure 1 for terminal block and bus port locations on the FAC2611 controller Observe the following guidelines when wiring a controller Input and Output terminal blocks On most field controller models all of the fixed input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are mounted on the top of the controller See Table 2 for more informatio...

Page 5: ...12 6 position modular jack that provides a connection for MAP Gateway the Bluetooth Commissioning Converter BTCVT the VAV Balancing Tool specified network sensors or other SA Bus devices with RJ 12 plugs A DIS1710 Local Controller Display also can be connected to the SA Bus port but only on FEC models without integral display and push buttons The Sensor port is connected internally to the SA bus t...

Page 6: ...etting the device addresses 4 Set DIP switch 128 to ON which enables wireless operation on the controller For more information on the ZFR Pro Wireless Field Bus system refer to the WNC1800 ZFR182x Pro Series Wireless Field Bus System Product Bulletin LIT 12012320 For more information on the ZFR 1800 Wireless Field Bus system refer to the ZFR1800 Series Wireless Field Bus Sys tem Product Bulletin L...

Page 7: ...hm potentiometer RTD 1k Nickel Johnson Controls sensor 1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 second minimum pulse width Internal 12 V 15k ohm pull up See Guideline A in Table 3 UNIVERSAL Inputs ICOMn Universal Input Common for all Universal Input terminals Note All Univer...

Page 8: ...s OCOMn share a common which is isolated from all other commons See Guideline C in Table 3 OUTn Binary Output 24 VAC Triac External Power Source Connects OUTn to OCOMn when activated External Power Source Requirements 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle Maximum 6 cycles hour with M9220BGx 3 40 mA minimum load current BINARY Output Power Selection Jumpe...

Page 9: ...ed by the load connected to the relay and local national or regional electrical codes Table 3 Cable length guidelines for recommended wire sizes for low voltage 30 V Inputs and Outputs Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 ...

Page 10: ...mm 22 AWG stranded 3 wire twisted shielded cable recommended FC BUS 1 Port FC Bus RJ 12 6 Position Modular Connector provides FC Bus Communications FC Bus Signal Reference and 15 VDC Common 15 VDC 180 mA Power for Bluetooth Commissioning Converter or ZFR or ZFR Pro Wireless Router Bluetooth Commissioning Converter retractable cable or 24 AWG 3 pair CAT 3 Cable 30 5 m 100 ft SA Bus Communications C...

Page 11: ...Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI Current Input External Source Isolated UI FAC2611 Advanced Application Field Equipment Controller Installation Guide 11 ...

Page 12: ...ination diagrams Current Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI or BI FAC2611 Advanced Application Field Equipment Controller Installation Guide 12 ...

Page 13: ...s 0 10 VDC Output to Actuator Internal Source CO or AO 0 10 VDC Output to Actuator External Source CO or AO Current Output CO or AO 24 VAC Triac Output Switch Low External Source CO or AO Analog Output Current AO FAC2611 Advanced Application Field Equipment Controller Installation Guide 13 ...

Page 14: ...t Output Termination diagrams 4 20 mA Output to Actuator AO 4 20 mA Output to Actuator AO Incremental Control to Actuator Switch Low Externally Sourced Triac Jumpers Where Applicable BO FAC2611 Advanced Application Field Equipment Controller Installation Guide 14 ...

Page 15: ...ch High Externally Sourced Triac Jumpers Where Applicable BO Incremental Control to Actuator Switch High Externally Sourced Triac Jumpers Where Applicable BO Network Stat with Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection FAC2611 Advanced Application Field Equipment Controller Installation Guide...

Page 16: ...16 8 4 2 and 1 Figure 9 Switches 64 through 1 are device address switches Switch 128 is a mode switch that enables a controller to operate on a ZFR ZFR Pro Series Wireless Field Bus Switch 128 must be set to Off for all hard wired SA and FC bus applications Set switch 128 to ON for wireless FC bus applications only Figure 9 Device address DIP switch block set to address 21 Note Metasys field contr...

Page 17: ...trollers 1 to 3 Switch 128 Off Reserved for peripheral devices not for use on controllers 4 to 127 Switch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus Table 6 SA FC bus device address descriptions Device address Use on description 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note Metasys field contro...

Page 18: ...oller has an EOL switch which when set to ON sets the controller as a terminating device on the bus See Removing the Controller cover for the EOL switch location The default EOL switch position is Off Figure 11 End of Line switch positions To set the EOL switch on a field controller 1 Determine the physical location of the field controller on the FC bus 2 Determine if the controller must be set as...

Page 19: ... and the UI s current loop jumper is in the Disabled default position Figure 13 the 4 20 mA current loop circuit opens whenever power to the controller is interrupted or off Figure 13 Current loop jumper positions Setting the current loop jumper to the Enabled position Figure 13 connects an internal 100 ohm resistor across the UI terminals which maintains the 4 20 mA current loop circuit even when...

Page 20: ... polyswitch resettable fuse is open Check Output wiring for short circuits and cycle power to controller On Steady Power Connected FAULT Red Off Steady Off Steady No Faults On Steady Device Fault no application loaded Main Code download required if controller is in Boot mode or a firmware mismatch exists between the FAC and the ZFR1811 Wireless Field Bus Router Blink 2 Hz Download or Startup in pr...

Page 21: ... Router for use in ZFR1800 Wireless Field Bus System For more information refer to the WNC1800 ZFR182x Pro Series Wireless Field Bus System Bulletin LIT 12012356 TP 2420 Transformer 120 VAC Primary to 24 VAC secondary 20 VA Wall Plug Y65T31 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Foot Mount 8 in Primary Leads and Secondary Screw Terminals Class 2 Note Additional Y6x x Serie...

Page 22: ...B Random Access Memory RAM Real Time Clock Backup Power Supply Super capacitor maintains power to the onboard real time clock for a minimum of 72 hours when supply power to the controller is disconnected Input and Output Capabilities 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mode 3 ...

Page 23: ...ASC The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Product warranty This product is covered by a limited warranty details of which can be found at www john...

Page 24: ...FAC2611 Advanced Application Field Equipment Controller Installation Guide 24 ...

Reviews: